Fault codes › SMA
SMA fault codes
Sunny Boy 3.0-7.7-US (SBx.x-1SP/1TP-US-40)
Sunny Boy 3.0-7.7-US (SBx.x-1SP-US-41)
Sunny Boy Smart Energy 3.8-11.5-US (SBSEx.x-US-50)
Sunny Highpower PEAK3 (SHP 125-172-US)
Sunny Tripower CORE1-US (STP 33/50/62-US-41)
Sunny Tripower 12000-30000TL-US (STP xxxxxTL-US-10)
Sunny Tripower X 13-30-US (STP xx-US-50)
Sunny Central 500CP XT-1000CP XT
Sunny Island 4548-US / 6048-US
| Code | Shown as | Class | Production | Clears | Reports | Page |
|---|---|---|---|---|---|---|
| E101 | Waiting mode | 205 | ||||
| E102 | Startup process | 205 | ||||
| E103 | Operation | 205 | ||||
| E104 | Operating on the generator (at external input) | informational | unaffected | 205 | ||
| E105 | Operation on utility grid (at external input) | informational | unaffected | 205 | ||
| E106 | Feeding-in grid operation (at external input) | informational | unaffected | 205 | ||
| E107 | Sleep mode (slave in single-phase systems) | informational | 206 | |||
| E108 | Silent mode on utility grid | informational | 206 | |||
| E110 | Shutdown due to error | fault | stops | Inverter shutdown | 206 | |
| E115 | Emergency charge | 206 | ||||
| E118 | Automatic start | 206 | ||||
| E119 | Manual start (transition from standby mode to operation) | informational | 206 | |||
| E120 | Manual stop (transition from operation to standby mode) | informational | stops | 206 | ||
| E121 | Start of energy saving mode | informational | 206 | |||
| E122 | End of energy saving mode | informational | 206 | |||
| E129 | External start (remote) | informational | 206 | |||
| E130 | External stop (remote) | informational | stops | Remote shutdown | 206 | |
| E131 | Start of automatic frequency synchronization | informational | 206 | |||
| E132 | End of automatic frequency synchronization | informational | 206 | |||
| E202 | (Partial) reset of BMS due to new battery | informational | 206 | |||
| E203 | State change, battery charging algorithm for float charge | informational | 206 | |||
| E204 | State change, battery charging algorithm for boost charge | informational | 206 | |||
| E205 | State change, battery charging algorithm for full charge | informational | 206 | |||
| E206 | State change into silent mode option | informational | 206 | |||
| E207 | State change, battery charging algorithm for equalization charge | informational | 206 | |||
| E221 | Status change battery-preservation mode level 1 | informational | 206 | |||
| E222 | Status change battery-preservation mode level 2 | informational | 206 | |||
| E223 | Status change battery-preservation mode level 3 | informational | 206 | |||
| E401 | informational | 206 | ||||
| E402 | informational | 206 | ||||
| E403 | Manual generator start | informational | 206 | |||
| E404 | Manual generator stop | informational | 207 | |||
| E405 | Manual error acknowledgment of generator error | informational | 207 | |||
| E406 | Source of generator request | informational | 207 | |||
| E407 | Current-regulated generator operation initiated | informational | 207 | |||
| E408 | Current-controlled generator operation stopped | informational | 207 | |||
| E501 | Grid request due to SOC (insufficient value) | informational | 207 | |||
| E502 | Release of grid due to SOC (exceeds) | informational | 207 | |||
| E503 | Grid request due to exceeding the power limit | informational | 207 | |||
| E504 | informational | 207 | ||||
| E505 | Manual grid request | informational | 207 | |||
| E506 | Manual grid release | informational | 207 | |||
| E507 | Feed-in started | informational | 207 | |||
| E508 | Feed-in stopped | informational | 207 | |||
| E601 | Relay 1 off | informational | 207 | |||
| E602 | Relay 1 on | informational | 207 | |||
| E603 | Relay 1 slave 1 off | informational | 207 | |||
| E604 | Relay 1 slave 1 on | informational | 207 | |||
| E605 | Relay 1 slave 2 off | informational | 207 | |||
| E606 | Relay 1 slave 2 on | informational | 207 | |||
| E607 | Relay 1 slave 3 off | informational | 207 | |||
| E608 | Relay 1 slave 3 on | informational | 207 | |||
| E609 | Transfer relay open | informational | 207 | |||
| E610 | Transfer relay closed | informational | 207 | |||
| E611 | Transfer relay on slave 1 open | informational | 207 | |||
| E612 | Transfer relay on slave 1 closed | informational | 207 | |||
| E613 | Transfer relay on slave 2 open | informational | 207 | |||
| E614 | Transfer relay on slave 2 closed | informational | 208 | |||
| E615 | Transfer relay on slave 3 open | informational | 208 | |||
| E616 | Transfer relay on slave 3 closed | informational | 208 | |||
| E617 | Relay 2 open | informational | 208 | |||
| E618 | Relay 2 closed | informational | 208 | |||
| E619 | Relay 2 slave 1 open | informational | 208 | |||
| E620 | Relay 2 slave 1 closed | informational | 208 | |||
| E621 | Relay 2 slave 2 open | informational | 208 | |||
| E622 | Relay 2 slave 2 closed | informational | 208 | |||
| E623 | Relay 2 slave 3 open | informational | 208 | |||
| E624 | Relay 2 slave 3 closed | informational | 208 | |||
| E625 | Digital input OFF (Low) | informational | 208 | |||
| E626 | Digital input ON (High) | informational | 208 | |||
| E627 | Digital input slave 1 to OFF (low) | informational | 208 | |||
| E628 | Digital input slave 1 to ON (high) | informational | 208 | |||
| E629 | Digital input slave 2 to OFF (low) | informational | 208 | |||
| E630 | Digital input slave 2 to ON (high) | informational | 208 | |||
| E631 | Digital input slave 3 to OFF (low) | informational | 208 | |||
| E632 | Digital input slave 3 to ON (high) | informational | 208 | |||
| E705 | Device start | 208 | ||||
| E706 | date, time changed | informational | 208 | |||
| E707 | New system configured in QCG | informational | 208 | |||
| E708 | Part 1 of firmware updated | informational | 208 | |||
| E709 | Part 2 of firmware updated | informational | 208 | |||
| E710 | Cluster firmware updated | informational | 208 | |||
| E711 | MMC/SD memory card inserted | informational | 208 | |||
| E712 | Parameters from MMC/SD memory card loaded | informational | 208 | |||
| E851 | Sunny Island Charger #1 detected | informational | 208 | |||
| E852 | Sunny Island Charger #2 detected | informational | 208 | |||
| E853 | Sunny Island Charger #3 detected | informational | 209 | |||
| E854 | Sunny Island Charger #4 detected | informational | 209 | |||
| E901 | SOC recalibration started | informational | 209 | |||
| E902 | SOC recalibration stopped | informational | 209 | |||
| E903 | Derating started | 209 | ||||
| E904 | Derating stopped | 209 | ||||
| E905 | stops | Battery deep discharge protection | 209 | |||
| F109 | Transformer overtemperature | fault | 210 | |||
| F113 | Overtemperature heat sink | fault | Inverter overtemperature | 210 | ||
| F117 | fault | AC overcurrent | 210 | |||
| F121 | Inverter overvoltage | fault | 210 | |||
| F141 | Inverter undervoltage | fault | 210 | |||
| F158 | Voltage on output AC1 | fault | Voltage on AC output | 210 | ||
| F201 | Measuring range of battery voltage exceeded | fault | Battery voltage out of range | 211 | ||
| F206 | Battery overtemperature | fault | 211 | |||
| F208 | Battery overvoltage error | fault | Battery overvoltage | 211 | ||
| F213 | Warning low battery voltage | fault | Battery undervoltage | 211 | ||
| F221 | fault | Configuration error | 211 | |||
| F314 | External voltage failure | fault | Grid loss | 211 | ||
| F605 | Transfer relay does not open | fault | 214 | |||
| F702 | DSP reset | fault | 214 | |||
| F703 | Timeout during a task | fault | 214 | |||
| F704 | Invalid DSP calibration | fault | Calibration failure | 214 | ||
| F706 | fault | 215 | ||||
| F710 | Autostart meter elapsed (several autostarts in succession) | fault | 215 | |||
| F716 | Measuring range of battery voltage exceeded | fault | Battery voltage out of range | 215 | ||
| F720 | fault | 215 | ||||
| F721 | fault | 215 | ||||
| F731 | Error in cluster configuration | fault | Configuration error | 215 | ||
| F732 | Error in address assignment of cluster devices | fault | Configuration error | 215 | ||
| F733 | No message from cluster master (only slave) | fault | Communication loss | 215 | ||
| F739 | Internal communication of the master is interrupted | fault | Internal communication failure | 215 | ||
| F743 | Internal CAN communication of the master is interrupted | fault | Internal communication failure | 215 | ||
| F754 | Communication with Multicluster Box interrupted | fault | Communication loss | 216 | ||
| F758 | No output voltage measured from the main cluster | fault | No output voltage measured | 216 | ||
| F781 | fault | stops | Internal device fault | 216 | ||
| F782 | Failure of the grid monitoring | fault | Grid monitoring failure | 216 | ||
| F783 | Slave does not receive a Syncpuls | fault | Missing synchronization pulse | 216 | ||
| F801 | fault | Switching device status fault | 217 | |||
| F806 | Multicluster Box settings do not match software settings. | fault | Configuration error | 217 | ||
| F809 | Error Q10 contactor (load shedding) | fault | Switching device status fault | 217 | ||
| F810 | fault | Invalid internal supply voltage | 217 | |||
| F811 | fault | Invalid internal supply voltage | 217 | |||
| F816 | Error Q7 contactor | fault | Switching device status fault | 217 | ||
| F817 | Error Q9 contactor | fault | Switching device status fault | 217 | ||
| F818 | fault | stops | Phase loss | 217 | ||
| F890 | Interference at external measurement point of Multicluster Box | fault | Measurement signal error | 218 | ||
| F891 | fault | Measurement signal error | 218 | |||
| F892 | fault | Measurement signal error | 218 | |||
| F893 | fault | Measurement signal error | 218 | |||
| F920 | Error message via SiCom: General | fault | 218 | |||
| F921 | Error message via SiCom: Battery overvoltage | fault | Battery overvoltage | 218 | ||
| F922 | Error message via SiCom: Battery undervoltage | fault | Battery undervoltage | 218 | ||
| F923 | Error message via SiCom: Battery overtemperature | fault | High battery temperature | 218 | ||
| F924 | Error message via SiCom: Battery undertemperature | fault | Low battery temperature | 218 | ||
| F925 | fault | High battery temperature | 218 | |||
| F926 | fault | Low battery temperature | 218 | |||
| F927 | fault | Excessive battery charging current | 218 | |||
| F928 | fault | Excessive battery charging current | 218 | |||
| F929 | Error message via SiCom: Error in the battery | fault | 218 | |||
| F930 | Error message via SiCom: Short circuit | fault | Short circuit | 218 | ||
| F931 | fault | Battery management system error | 218 | |||
| F932 | fault | Battery cell charge imbalance | 219 | |||
| F935 | Error message via SiCom: Error in the generator | fault | 219 | |||
| F952 | Time for external battery management exceeded | fault | External battery management timeout | 219 | ||
| W110 | Overtemperature transformer slave 1 | warning | Inverter overtemperature | 210 | ||
| W111 | Overtemperature transformer slave 2 | warning | Inverter overtemperature | 210 | ||
| W112 | Overtemperature transformer slave 3 | warning | Inverter overtemperature | 210 | ||
| W114 | Overtemperature heat sink slave 1 | warning | Inverter overtemperature | 210 | ||
| W115 | Overtemperature heat sink slave 2 | warning | Inverter overtemperature | 210 | ||
| W116 | Overtemperature heat sink slave 3 | warning | Inverter overtemperature | 210 | ||
| W118 | warning | AC overcurrent | 210 | |||
| W119 | warning | AC overcurrent | 210 | |||
| W120 | warning | AC overcurrent | 210 | |||
| W122 | Inverter overvoltage slave 1 | warning | Inverter overvoltage | 210 | ||
| W123 | Inverter overvoltage slave 2 | warning | Inverter overvoltage | 210 | ||
| W124 | Inverter overvoltage slave 3 | warning | Inverter overvoltage | 210 | ||
| W137 | Derating due to temperature (heat sink or transformer) | warning | reduced | Inverter power derating, Inverter overtemperature | 210 | |
| W138 | warning | reduced | Inverter power derating, Inverter overtemperature | 210 | ||
| W139 | warning | reduced | Inverter power derating, Inverter overtemperature | 210 | ||
| W140 | warning | reduced | Inverter power derating, Inverter overtemperature | 210 | ||
| W142 | Inverter undervoltage slave 1 | warning | Inverter undervoltage | 210 | ||
| W143 | Inverter undervoltage slave 2 | warning | Inverter undervoltage | 210 | ||
| W144 | Inverter undervoltage slave 3 | warning | Inverter undervoltage | 210 | ||
| W159 | Voltage on output AC1 slave 1 | warning | Voltage on AC output | 210 | ||
| W160 | Voltage on output AC1 slave 2 | warning | Voltage on AC output | 210 | ||
| W161 | Voltage on output AC1 slave 3 | warning | Voltage on AC output | 210 | ||
| W202 | warning | Battery voltage out of range | 211 | |||
| W203 | warning | Battery voltage out of range | 211 | |||
| W204 | warning | Battery voltage out of range | 211 | |||
| W209 | Battery overvoltage error | warning | Battery overvoltage | 211 | ||
| W210 | Battery overvoltage warning | warning | Battery overvoltage | 211 | ||
| W211 | Low battery temperature warning | warning | Low battery temperature | 211 | ||
| W212 | High battery temperature warning | warning | High battery temperature | 211 | ||
| W220 | Warning SOH < 70% | warning | Low battery state of health | 211 | ||
| W309 | Relay protection | warning | 211 | |||
| W310 | Relay protection slave 1 | warning | 211 | |||
| W311 | Relay protection slave 2 | warning | 211 | |||
| W312 | Relay protection slave 3 | warning | 211 | |||
| W315 | warning | Grid undervoltage | 211 | |||
| W316 | warning | Grid undervoltage | 211 | |||
| W317 | warning | Grid undervoltage | 211 | |||
| W318 | warning | Grid undervoltage | 211 | |||
| W319 | warning | Grid overvoltage | 211 | |||
| W320 | warning | Grid overvoltage | 212 | |||
| W321 | warning | stops | Grid overvoltage | 212 | ||
| W322 | warning | stops | Grid overvoltage | 212 | ||
| W323 | warning | stops | Grid underfrequency | 212 | ||
| W324 | warning | stops | Grid underfrequency | 212 | ||
| W325 | warning | stops | Grid underfrequency | 212 | ||
| W326 | warning | stops | Grid underfrequency | 212 | ||
| W327 | warning | stops | Grid overfrequency | 212 | ||
| W328 | warning | stops | Grid overfrequency | 212 | ||
| W329 | warning | stops | Grid overfrequency | 212 | ||
| W330 | warning | stops | Grid overfrequency | 212 | ||
| W331 | Disconnection from utility grid/generator due to islanding | warning | stops | Islanding detected | 212 | |
| W332 | warning | stops | Islanding detected | 212 | ||
| W333 | warning | stops | Islanding detected | 212 | ||
| W334 | warning | stops | Islanding detected | 212 | ||
| W335 | warning | stops | Grid voltage out of range | 212 | ||
| W336 | warning | stops | Grid voltage out of range | 212 | ||
| W337 | warning | stops | Grid voltage out of range | 212 | ||
| W338 | warning | stops | Grid voltage out of range | 212 | ||
| W339 | warning | stops | Grid overvoltage | 212 | ||
| W340 | warning | stops | Grid overvoltage | 213 | ||
| W341 | warning | stops | Grid overvoltage | 213 | ||
| W342 | warning | stops | Grid overvoltage | 213 | ||
| W343 | warning | stops | 213 | |||
| W344 | warning | stops | 213 | |||
| W345 | warning | 213 | ||||
| W346 | warning | 213 | ||||
| W347 | Disconnection from external source due to excessive load | warning | Inverter overload | 213 | ||
| W348 | warning | Inverter overload | 213 | |||
| W349 | warning | Inverter overload | 213 | |||
| W350 | warning | Inverter overload | 213 | |||
| W351 | warning | External short circuit | 213 | |||
| W352 | warning | External short circuit | 213 | |||
| W353 | warning | External short circuit | 213 | |||
| W354 | warning | External short circuit | 213 | |||
| W377 | warning | AC overcurrent | 213 | |||
| W378 | warning | AC overcurrent | 213 | |||
| W379 | warning | AC overcurrent | 213 | |||
| W380 | warning | AC overcurrent | 213 | |||
| W401 | Reverse power protection (generator) | warning | Reverse power flow | 214 | ||
| W402 | warning | Generator management locked | 214 | |||
| W501 | Grid reverse current prevented (quick grid disconnection) | warning | stops | Reverse power flow | 214 | |
| W502 | warning | stops | Reverse power flow | 214 | ||
| W503 | warning | stops | Reverse power flow | 214 | ||
| W504 | warning | stops | Reverse power flow | 214 | ||
| W505 | warning | AC overcurrent | 214 | |||
| W506 | warning | AC overcurrent | 214 | |||
| W507 | warning | AC overcurrent | 214 | |||
| W508 | warning | AC overcurrent | 214 | |||
| W606 | Transfer relay does not open slave 1 | warning | 214 | |||
| W607 | Transfer relay does not open slave 2 | warning | 214 | |||
| W608 | Transfer relay does not open slave 3 | warning | 214 | |||
| W705 | Watchdog DSP has been tripped | warning | 214 | |||
| W707 | warning | 215 | ||||
| W708 | warning | 215 | ||||
| W709 | warning | 215 | ||||
| W713 | Watchdog has been tripped | warning | Internal device fault | 215 | ||
| W717 | warning | Battery voltage out of range | 215 | |||
| W718 | warning | Battery voltage out of range | 215 | |||
| W719 | warning | Battery voltage out of range | 215 | |||
| W722 | Short circuit on battery temperature sensor | warning | 215 | |||
| W723 | Cable break on battery temperature sensor | warning | 215 | |||
| W724 | Autostart meter slave 1 elapsed | warning | Automatic restart limit reached | 215 | ||
| W725 | Autostart meter slave 2 elapsed | warning | Automatic restart limit reached | 215 | ||
| W726 | Autostart meter slave 3 elapsed | warning | Automatic restart limit reached | 215 | ||
| W734 | No message from cluster slave 1 | warning | Communication loss | 215 | ||
| W735 | No message from cluster slave 2 | warning | Communication loss | 215 | ||
| W736 | No message from cluster slave 3 | warning | Communication loss | 215 | ||
| W738 | Synchronization not successful | warning | 215 | |||
| W740 | Internal device communication of slave 1 interrupted | warning | Internal communication failure | 215 | ||
| W741 | Internal device communication of slave 2 interrupted | warning | Internal communication failure | 215 | ||
| W742 | Internal device communication of slave 3 interrupted | warning | Internal communication failure | 215 | ||
| W744 | Internal CAN communication of slave 1 is interrupted | warning | Internal communication failure | 216 | ||
| W745 | Internal CAN communication of slave 2 is interrupted | warning | Internal communication failure | 216 | ||
| W746 | Internal CAN communication of slave 3 is interrupted | warning | Internal communication failure | 216 | ||
| W747 | warning | 216 | ||||
| W748 | warning | 216 | ||||
| W749 | warning | 216 | ||||
| W750 | warning | 216 | ||||
| W751 | warning | 216 | ||||
| W752 | warning | 216 | ||||
| W753 | Invalid system time | warning | Inaccurate clock time | 216 | ||
| W755 | Battery-preservation mode 1 (LBM) | warning | Battery protection mode active | 216 | ||
| W756 | Battery-preservation mode 2 (LBM) | warning | Battery protection mode active | 216 | ||
| W757 | Battery-preservation mode 3 (LBM) | warning | Battery protection mode active | 216 | ||
| W759 | warning | No output voltage measured | 216 | |||
| W760 | warning | No output voltage measured | 216 | |||
| W761 | warning | No output voltage measured | 216 | |||
| W784 | Slave does not receive a Syncpuls Slave 1 | warning | Missing synchronization pulse | 216 | ||
| W785 | Slave does not receive a Syncpuls Slave 2 | warning | Missing synchronization pulse | 216 | ||
| W786 | Slave does not receive a Syncpuls Slave 3 | warning | Missing synchronization pulse | 216 | ||
| W791 | DSP reset detected on slave 1 | warning | Signal processor reset | 216 | ||
| W792 | DSP reset detected on slave 2 | warning | Signal processor reset | 216 | ||
| W793 | DSP reset detected on slave 3 | warning | Signal processor reset | 216 | ||
| W797 | Failure of the grid monitoring slave 1 | warning | Grid monitoring failure | 216 | ||
| W798 | Failure of the grid monitoring slave 2 | warning | Grid monitoring failure | 216 | ||
| W799 | Failure of the grid monitoring slave 3 | warning | Grid monitoring failure | 216 | ||
| W804 | Grid operation not possible | warning | Operation inhibited | 217 | ||
| W805 | Generator operation not possible | warning | Operation inhibited | 217 | ||
| W807 | No valid line voltage for requested grid operation | warning | Grid voltage out of range | 217 | ||
| W808 | Error Q4 contactor | warning | Switching device status fault | 217 | ||
| W815 | Error Q5 contactor | warning | Switching device status fault | 217 | ||
| W824 | Error Q4 contactor | warning | Switching device status fault | 217 | ||
| W851 | warning | Reverse polarity, External short circuit | 217 | |||
| W852 | Battery overvoltage Sunny Island Charger 1 | warning | Battery overvoltage | 217 | ||
| W853 | Overvoltage PV array Sunny Island Charger 1 | warning | DC overvoltage | 217 | ||
| W854 | warning | Abnormal PV input | 217 | |||
| W855 | warning | Abnormal temperature reading | 217 | |||
| W856 | Overtemperature Sunny Island Charger 1 | warning | Charge controller overtemperature | 217 | ||
| W857 | warning | Communication loss | 217 | |||
| W861 | warning | Reverse polarity, External short circuit | 217 | |||
| W862 | Battery overvoltage Sunny Island Charger 2 | warning | Battery overvoltage | 217 | ||
| W863 | Overvoltage PV array Sunny Island Charger 2 | warning | DC overvoltage | 217 | ||
| W864 | warning | Abnormal PV input | 217 | |||
| W865 | warning | Abnormal temperature reading | 217 | |||
| W866 | Overtemperature Sunny Island Charger 2 | warning | Charge controller overtemperature | 217 | ||
| W867 | warning | Communication loss | 217 | |||
| W871 | warning | Reverse polarity, External short circuit | 217 | |||
| W872 | Battery overvoltage Sunny Island Charger 3 | warning | Battery overvoltage | 217 | ||
| W873 | Overvoltage PV array Sunny Island Charger 3 | warning | DC overvoltage | 217 | ||
| W874 | warning | Abnormal PV input | 218 | |||
| W875 | warning | Abnormal temperature reading | 218 | |||
| W876 | Overtemperature Sunny Island Charger 3 | warning | Charge controller overtemperature | 218 | ||
| W877 | warning | Communication loss | 218 | |||
| W881 | warning | Reverse polarity | 218 | |||
| W882 | Battery overvoltage Sunny Island Charger 4 | warning | Battery overvoltage | 218 | ||
| W883 | Overvoltage PV array Sunny Island Charger 4 | warning | DC overvoltage | 218 | ||
| W884 | warning | Abnormal PV input | 218 | |||
| W885 | warning | Abnormal temperature reading | 218 | |||
| W886 | Overtemperature Sunny Island Charger 4 | warning | Charge controller overtemperature | 218 | ||
| W887 | warning | Communication loss | 218 | |||
| W915 | DSP failure | warning | 218 | |||
| W936 | Warning via SiCom: General | warning | 219 | |||
| W937 | Warning via SiCom: Battery overvoltage | warning | Battery overvoltage | 219 | ||
| W938 | Warning via SiCom: Battery undervoltage | warning | Battery undervoltage | 219 | ||
| W939 | Warning via SiCom: Battery overtemperature | warning | High battery temperature | 219 | ||
| W940 | Warning via SiCom: Battery undertemperature | warning | Low battery temperature | 219 | ||
| W941 | Warning via SiCom: Battery overtemperature in charge mode | warning | High battery temperature | 219 | ||
| W942 | Warning via SiCom: Battery undertemperature in charge mode | warning | Low battery temperature | 219 | ||
| W943 | Warning via SiCom: battery charging current too high | warning | Excessive battery charging current | 219 | ||
| W944 | warning | Excessive battery charging current | 219 | |||
| W945 | Warning via SiCom: error in the battery | warning | Battery error reported | 219 | ||
| W946 | Warning via SiCom: short circuit | warning | Short circuit | 219 | ||
| W947 | Warning via SiCom: internal error in battery management | warning | Battery management system error | 219 | ||
| W948 | warning | Battery cell charge imbalance | 219 | |||
| W951 | Warning via SiCom: Generator | warning | 219 | |||
| W953 | Time for external battery management exceeded | warning | External battery management timeout | 219 |
Codes are sorted by vendor prefix and number. Each row links to the code's record; concepts link to their reading rule.