Battery management system error

ID
symptom:battery-management-error
IRI
https://solarlattice.org/kb/symptom/battery-management-error
Status
active
Also known as
Internal error in battery management, XA12Bms, XW12Bms

The Sunny Island battery inverter reports an internal error in the battery management system as error F931 at level 3 or as warning W947 at level 1. The message does not come from the inverter itself: the external battery management system sends it over the SiCom link. The fix for both codes is to remove the cause inside the external battery management system, using the battery manufacturer's documentation. Other SiCom codes cover specific battery conditions, such as overvoltage, undervoltage, short circuit or a general battery error. If one of those appears, it points to a more specific cause than this internal management error. If the inverter detects external battery management that has not been configured, it raises a separate error. In that case, run the quick configuration guide (QCG) and set up a system with external energy management.

Claims

observed_as

c1 verified · fact Battery management error message

Sunny Island shows F931 (XA12Bms, level 3 error) or W947 (XW12Bms, level 1 warning). Both report an internal battery-management error passed on over SiCom by the external battery management system.

verified by: review-workflowverified on: 2026-10-23