Backup outlet short circuit

ID
symptom:backup-outlet-short-circuit
IRI
https://solarlattice.org/kb/symptom/backup-outlet-short-circuit
Status
active
Also known as
Short circuit in backup operation

The inverter has found a short circuit at the outlet used for manual secure power supply (SPS) operation, and it logs event 9203. Depending on the model, the event text reads either short circuit in backup operation or short circuit in the SPS power outlet. The event can also come from an overload rather than a true short: the starting load was too high, or the appliance drew more than the permitted SPS load current for longer than 5 s. First check that the outlet is wired correctly and that the connected appliance works properly. Next, unplug the appliance and switch SPS operation on again. If the outlet now works, the appliance or the load was the cause. If the load is the problem, reduce the load on the SPS terminal or use an appliance with a lower starting current.