Backup mode unavailable

ID
symptom:backup-mode-unavailable
IRI
https://solarlattice.org/kb/symptom/backup-mode-unavailable
Status
active
Also known as
Backup operation not possible, SPS mode, Secure Power Supply

On the Smart Energy inverter, the usual cause is that the inverter still sees an active utility grid connection, so SPS mode does not start. Check first whether the grid is really down, or whether the AC breaker has actually cut the inverter's AC supply. Next, check the backup parameters. Backup can be set in Energy management or in the SMA 360° commissioning wizard. That includes the backup type, which must be set to automatic backup operation if the transfer switch should change over by itself when the grid fails. On Sunny Boy Storage US-10 units, the same event means the battery has too little charge to run the loads in Secure Power Supply mode. Check the battery state of charge there. On those storage units the event can also show up where SPS is not activated or not used, and then it does not change how the system behaves. Firmware 3.00.23 or later stops the event in that case. Keep this separate from the event saying input power is too low for backup operation. That one points to not enough input power, not a grid connection that is still live.