Solar Lattice

Symptom

Invalid internal supply voltage

ID
symptom:supply-voltage-invalid
IRI
https://solarlattice.org/kb/symptom/supply-voltage-invalid
Status
active

On SMA Sunny Central CP XT inverters, this symptom appears as error 6410 when the 24 V internal supply voltage is invalid, and as error 6417 when the 15 V supply voltage is invalid. For both errors, the inverter behavior table gives a 5 min entry in the S1 and S2 columns. SMA systems with a Multicluster Box have a related event, 6466, which reports a system failure because the 15 V or 24 V voltage supply in the box is defective. These messages point to a defect in the device's own low-voltage supply, which suggests an internal power supply fault rather than a PV array or grid problem. The documentation gives no field repair: write down the error number and contact the SMA Service Line.