Fault codes › SMA › Sunny Boy 3.0-7.7-US (SBx.x-1SP/1TP-US-40)

SMA SB-US-40 3501

Code
3501
Shown as
Insulation failure > Check generator
Page
49
ID
fc:sma-sb-us-40-3501
IRI
https://solarlattice.org/kb/fc/sma-sb-us-40-3501
Status
active
Also known as
3501, SMA 3501, Insulation failure > Check generator
Category
Inverters
Class fault verified · fact
Production stops drafted · lead
Clears not stated

Decoded

Reports ground fault alarm or trip, low insulation resistance; may indicate loss of electrical insulation; look at PV array, DC cable, DC connector; confirm with insulation resistance testing, open-circuit voltage measurement, DC voltage measurement, visual inspection, infrared thermography; do: DC wiring check.

What can be behind Ground fault alarm or trip

Failure modes that present as the reported condition, and the tests that tell them apart.

What can be behind Low insulation resistance

Failure modes that present as the reported condition, and the tests that tell them apart.

Defined in

The manufacturer's own cause and corrective text is not reproduced here.

Same condition on other equipment

ABB / FIMER
ABB / FIMER PVS-166-175-TL E018, ABB / FIMER PVS-166-175-TL E025, ABB / FIMER PVS-166-175-TL E037, ABB / FIMER PVS-60-TL E018, ABB / FIMER PVS-60-TL E025, ABB / FIMER PVS-60-TL E037, ABB / FIMER TRIO-20.0-27.6-TL E018, ABB / FIMER TRIO-20.0-27.6-TL E025, ABB / FIMER TRIO-20.0-27.6-TL E037, ABB / FIMER UNO-DM-3.3-5.0-PLUS E018, ABB / FIMER UNO-DM-3.3-5.0-PLUS E025, ABB / FIMER UNO-DM-6.0-PLUS E018, ABB / FIMER UNO-DM-6.0-PLUS E025
CPS
CPS SCA25KTL-208 IsolationErr, CPS SCA25KTL-480 IsolationErr, CPS SCA36KTL IsolationErr, CPS SCA50-100K-T PFault0040, CPS SCA50-100K-T Protect0190, CPS SCA50-100K-T Protect0200, CPS SCA50-60KTL IsolationErr, CPS SCH100-125KTL IsolationErr, CPS SCH125KTL-AIO IsolationErr, CPS SCH200-250K-T IsolationErr, CPS SCH275KTL IsolationErr, CPS SCH350KTL IsolationErr
Canadian Solar
Canadian Solar 125K-T600GL02 PV ISO-PRO 01/02, Canadian Solar 125K-T600GL02 PV-MID-ISO, Canadian Solar 185-255K PV ISO-PRO 01/02, Canadian Solar 23-28KTL-CT IsolationErr, Canadian Solar 25-40K-T480GL01 PV ISO-PRO 01/02, Canadian Solar 50-66K-T480GL01 PV ISO-PRO 01/02, Canadian Solar 75-100K-T480GL02 PV ISO-PRO 01/02
Enphase
Enphase IQ7 DC Resistance Low - Power Off, Enphase IQ8 DC Resistance Low - Power Off, Enphase IQ9N DC Resistance Low - Power Off, Enphase M215-M250 DC Resistance Low - Power Off, Enphase M215-M250 GFI Tripped
Fronius
Fronius Galvo 475, Fronius Galvo 502, Fronius Primo 447, Fronius Primo 475, Fronius Primo 502, Fronius Symo 447, Fronius Symo 475, Fronius Symo 502
Huawei
Huawei SUN2000-100KTL-USH0 2031, Huawei SUN2000-100KTL-USH0 2062, Huawei SUN2000-25-30KTL-US 313, Huawei SUN2000-45KTL-US-HV-D0 313
KACO new energy
KACO new energy blueplanet TL3 181, KACO new energy blueplanet TL3 182, KACO new energy blueplanet TL3 183
SMA
SMA SB-US-40 3601, SMA SB-US-40 3701, SMA SB-US-41 3501, SMA SB-US-41 3601, SMA SB-US-41 3701, SMA SBSE-US-50 3501, SMA SBSE-US-50 3601, SMA SBSE-US-50 3701, SMA PEAK3-US 3501, SMA PEAK3-US 3601, SMA PEAK3-US 3701, SMA CORE1-US 3501, SMA CORE1-US 3701, SMA STP-TL-US 3501, SMA STP-TL-US 3601, SMA STP-TL-US 3701, SMA STP-X-US 3501, SMA STP-X-US 3601, SMA STP-X-US 3701, SMA SC-CP-XT 3501, SMA SC-CP-XT 3502, SMA SC-CP-XT 3504, SMA SC-CP-XT 3507, SMA SC-CP-XT 3510, SMA SC-CP-XT 3511, SMA SC-CP-XT 3512, SMA SC-CP-XT 3515, SMA SC-CP-XT 3601, SMA SC-CP-XT 6487
Schneider Electric
Schneider Electric CL125 033, Schneider Electric CL125 039, Schneider Electric CL125 055
Solis
Solis 1P-4G-US PV ISO-PRO 01/02, Solis 3P-5G-US PV ISO-PRO 01/02, Solis RHI-1P-HV PV ISO-PRO 01/02, Solis S5-GC PV ISO-PRO 01/02, Solis S6-EH1P PV ISO-PRO 01/02, Solis S6-EH2P PV ISO-PRO01, Solis S6-EH2P PV ISO-PRO02, Solis S6-EH3P30-60K PV ISO-PRO01, Solis S6-EH3P30-60K PV ISO-PRO02, Solis S6-EH3P75-150K PV ISO-PRO01, Solis S6-EH3P75-150K PV ISO-PRO02, Solis S6-GC PV ISO-PRO 01/02, Solis S6-GU PV ISO-PRO 01/02
Sungrow
Sungrow SG-CX-US 039, Sungrow SG200HX 1600-1615, Sungrow SG200HX 1632-1655, Sungrow SG200HX 039, Sungrow SG250HX 1600-1615, Sungrow SG250HX 1632-1655, Sungrow SG250HX 39, Sungrow SG350HX 1600-1615, Sungrow SG350HX 1632-1655, Sungrow SG350HX 039
Yaskawa Solectria
Yaskawa Solectria PVI-25TL-R IsolationErr, Yaskawa Solectria PVI-TL IsolationErr, Yaskawa Solectria SGI-XTM DC GND Fault, Yaskawa Solectria SGI-XTM RCM Fault, Yaskawa Solectria XGI-1500-1MW CRIT-7, Yaskawa Solectria XGI-1500 CRIT-7, Yaskawa Solectria XGI-1500-DCG CRIT-7

Same code in other families

Claims

defined_in

c1 drafted · lead SBxx-US-1XP-40-BA-en-13

reports

c2 drafted · lead Ground fault alarm or trip

c3 drafted · lead Low insulation resistance

indicates

c4 drafted · lead Loss of electrical insulation

Defective insulation or faulty plug connections are named as the frequent cause.

affects

c5 drafted · lead PV array

c6 drafted · lead DC cable

c7 drafted · lead DC connector

detected_by

c8 drafted · lead Insulation resistance testing

c9 drafted · lead Open-circuit voltage measurement

review note: support check: partial - Open-circuit voltage measurement is listed as a verification step, but not explicitly as detection of this fault.

c10 drafted · lead DC voltage measurement

String pole-to-ground voltage measurement.

c11 drafted · lead Visual inspection

c12 drafted · lead Infrared thermography

review note: support check: partial - IR camera is only a tip for support, not a stated detection method.

mitigated_by

c13 drafted · lead DC wiring check

has_event_class

c14 verified · fact Fault (device stops or needs intervention)

verified by: review-workflowverified on: 2026-10-23review note: support check: partial - Inverter disconnects/does not operate, but 'Fault' classification isn't explicitly stated.

has_production_effect

c15 drafted · lead Trip (production stops)

Inverter disconnects from grid or fails to connect during self-test.

applies_to

c16 drafted · lead Sunny Boy 3.0-7.7-US-40 proposed

Data