Code
PV ISO-PRO 01/02
Shown as
Ground Protect ion
Page
71
ID
fc:solis-s5-gc-us-pvisopro0102
IRI
https://solarlattice.org/kb/fc/solis-s5-gc-us-pvisopro0102
Status
active
Also known as
PV ISO-PRO 01/02, pvisopro0102, Solis PV ISO-PRO 01/02, Ground Protect ion
Category
Inverters
Class fault verified · fact
Production not stated
Clears after a manual reset verified · fact

Decoded

Reports low insulation resistance; may indicate loss of electrical insulation; look at DC cable, PV array; confirm with insulation resistance testing, fault localization; do: DC wiring check, inverter restart, inverter replacement.

What can be behind Low insulation resistance

Failure modes that present as the reported condition, and the tests that tell them apart.

Defined in

The manufacturer's own cause and corrective text is not reproduced here.

Same condition on other equipment

ABB / FIMER
ABB / FIMER PVS-166-175-TL E025, ABB / FIMER PVS-166-175-TL E037, ABB / FIMER PVS-60-TL E025, ABB / FIMER PVS-60-TL E037, ABB / FIMER TRIO-20.0-27.6-TL E025, ABB / FIMER TRIO-20.0-27.6-TL E037, ABB / FIMER UNO-DM-3.3-5.0-PLUS E025, ABB / FIMER UNO-DM-6.0-PLUS E025
CPS
CPS SCA25KTL-208 IsolationErr, CPS SCA25KTL-480 IsolationErr, CPS SCA36KTL IsolationErr, CPS SCA50-100K-T Protect0190, CPS SCA50-60KTL IsolationErr, CPS SCH100-125KTL IsolationErr, CPS SCH125KTL-AIO IsolationErr, CPS SCH200-250K-T IsolationErr, CPS SCH275KTL IsolationErr, CPS SCH350KTL IsolationErr
Canadian Solar
Canadian Solar 125K-T600GL02 PV ISO-PRO 01/02, Canadian Solar 125K-T600GL02 PV-MID-ISO, Canadian Solar 185-255K PV ISO-PRO 01/02, Canadian Solar 23-28KTL-CT IsolationErr, Canadian Solar 25-40K-T480GL01 PV ISO-PRO 01/02, Canadian Solar 50-66K-T480GL01 PV ISO-PRO 01/02, Canadian Solar 75-100K-T480GL02 PV ISO-PRO 01/02
Enphase
Enphase IQ7 DC Resistance Low - Power Off, Enphase IQ8 DC Resistance Low - Power Off, Enphase IQ9N DC Resistance Low - Power Off, Enphase M215-M250 DC Resistance Low - Power Off
Fronius
Fronius Galvo 502, Fronius Primo 447, Fronius Primo 502, Fronius Symo 447, Fronius Symo 502
Huawei
Huawei SUN2000-100KTL-USH0 2062, Huawei SUN2000-25-30KTL-US 313, Huawei SUN2000-45KTL-US-HV-D0 313
KACO new energy
KACO new energy blueplanet TL3 181, KACO new energy blueplanet TL3 182, KACO new energy blueplanet TL3 183
SMA
SMA SB-US-40 3501, SMA SB-US-41 3501, SMA SBSE-US-50 3501, SMA PEAK3-US 3501, SMA CORE1-US 3501, SMA STP-TL-US 3501, SMA STP-X-US 3501, SMA SC-CP-XT 3501, SMA SC-CP-XT 3504, SMA SC-CP-XT 3510, SMA SC-CP-XT 3511
Schneider Electric
Schneider Electric CL125 039, Schneider Electric CL125 055
Solis
Solis 1P-4G-US PV ISO-PRO 01/02, Solis 3P-5G-US PV ISO-PRO 01/02, Solis RHI-1P-HV PV ISO-PRO 01/02, Solis S6-EH1P PV ISO-PRO 01/02, Solis S6-GC PV ISO-PRO 01/02, Solis S6-GU PV ISO-PRO 01/02
Sungrow
Sungrow SG-CX-US 039, Sungrow SG200HX 039, Sungrow SG250HX 39, Sungrow SG350HX 039
Yaskawa Solectria
Yaskawa Solectria PVI-25TL-R IsolationErr, Yaskawa Solectria PVI-TL IsolationErr

Same code in other families

Claims

defined_in

c1 drafted · lead Solis Manual S5 (75-100)K US V2,3(20230623)

reports

c2 verified · fact Low insulation resistance

verified by: review-workflowverified on: 2026-10-20

detected_by

c3 verified · fact Insulation resistance testing

Repeat under the same weather as the alarm if first result is normal.

verified by: review-workflowverified on: 2026-10-20

c4 drafted · lead Fault localization

affects

c5 verified · fact DC cable

verified by: review-workflowverified on: 2026-10-20

c6 drafted · lead PV array

mitigated_by

c7 drafted · lead DC wiring check

review note: support check: partial - Passages say physically check cables, which is roughly a DC cable check, but don't say DC wiring specifically.

c8 drafted · lead Inverter restart

c9 drafted · lead Inverter replacement

has_event_class

c10 verified · fact Fault (device stops or needs intervention)

verified by: review-workflowverified on: 2026-10-20

indicates

c11 verified · fact Loss of electrical insulation

verified by: review-workflowverified on: 2026-10-20

has_recovery

c12 verified · fact Manual reset (operator restarts or acknowledges)

Reset after inspection; replace inverter if insulation checks normal and fault persists.

verified by: review-workflowverified on: 2026-10-20review note: support check: partial - Solution includes reset inverter and replace inverter, but the passage doesn't say reset is required to clear it or that…

applies_to

c13 drafted · lead Solis S5-GC(75-125)K-US

Data