ID
fm:insulation-loss
IRI
https://solarlattice.org/kb/fm/insulation-loss
Status
active
Also known as
insulation fault, Insulation failure, isolation fault, low insulation resistance, Electrical insulation fault

Loss of electrical insulation means current-carrying parts of the PV array are no longer properly isolated from ground or from people. It usually comes from damaged cables, faulty connectors, broken module glass or failed junction boxes. Moisture makes it worse, so the fault may only appear during rain or humid periods and can be intermittent. In the field it shows up as ground faults and inverter trips or shutdowns. Low insulation resistance on its own does not reduce output until the inverter faults. If the leakage stays below the protection device thresholds, the fault can go undetected while still causing significant power losses. Confirm it with insulation resistance testing on isolated circuits. Treat it as a shock hazard: exposed parts can carry dangerous voltages, and in the worst case damaged cables or connectors can arc and start a fire. Replace damaged cable runs or modules that can no longer guarantee insulation, then confirm insulation integrity after the repair.

Claims

caused_by

c1 drafted · lead Cable Defect

Damaged or undersized DC cables are named as a main source of insulation faults.

c2 verified · fact Connector Defect

verified by: joshuahamsaverified on: 2026-10-20

c3 drafted · lead Glass Breakage

Once the glass is broken, module insulation is no longer guaranteed, especially in wet conditions.

c4 verified · fact Junction Box Failure

verified by: joshuahamsaverified on: 2026-10-20

c5 drafted · lead Delamination

Delamination near the junction box or module edge can let water in, causing an insulation failure as a follow-up failure.

c6 drafted · lead Moisture exposure

The fault can come and go with humidity and is often worse on rainy days or in humid periods.

review note: support check: partial - The passages tie moisture to insulation faults that are intermittent and worse in wet or humid periods, but they don't present moisture exposure as a generic cause.

affects

c7 drafted · lead DC cable

c8 drafted · lead DC connector

c9 drafted · lead Junction box

presents_as

c10 drafted · lead Ground fault alarm or trip

May be intermittent, with lower insulation during rain.

c11 drafted · lead Inverter shutdown

Low insulation resistance causes no loss by itself until the inverter faults or switches off.

leads_to

c12 drafted · lead Arc fault

In the worst case, damaged cables or connectors may arc and start a fire.

detected_by

c13 drafted · lead Insulation resistance testing

mitigated_by

c14 drafted · lead Module replacement

Replace modules that can no longer guarantee electrical safety or insulation resistance.

c15 drafted · lead Cable replacement

c16 drafted · lead Post-repair verification

Confirm insulation integrity after the repair.