FailureMode
Arc fault
- ID
fm:arc-fault
- IRI
https://solarlattice.org/kb/fm/arc-fault
- Status
- active
- Also known as
- DC arc faults, DC series arc fault, electric arc, internal arcs, arcing
An arc fault is a sudden high-power discharge between two conductors. It can occur in series within a string or in parallel between strings. Arcs usually cause destructive fires, and they have likely started grass fires on site. Common origins are weak or badly crimped connectors, internal arcs in junction boxes, and broken cell interconnections where an open bypass diode cannot carry the current. Look for burnt connectors and burnt junction boxes, especially at the input leads. Arcs are transient and hard to catch. Detection relies on spectrum analysis of string current and voltage, which shows a high-frequency noise pattern. Arc fault circuit interrupters installed on individual strings protect the system. Where arcing or burn evidence is found, isolate the circuit safely first. Then replace the damaged connectors, modules or junction-box assemblies.
<!-- review notes
- sentence 3: support check: partial - Weak/badly crimped connectors, j-box internal arcs and broken interconnections are supported, but 'common origins' ranking is not stated and the diode condition is slightly off: the passages say the bypass diode fails to bypass or is open-circuited.
- sentence 4: support check: partial - Figures show a burned connector and a burnt junction box with an arc at the input lead, but no passage instructs inspecting for them, and 'especially at input leads' is only implied by one example.
-->
Claims
caused_by
c1 drafted · lead
Cell Interconnection Failure
If every solder bond or busbar of a cell breaks, string current is blocked. An arc can then form if the bypass diode cannot carry the current and the system runs at high voltage.
c2 drafted · lead
Bypass Diode Failure
An open-circuited bypass diode forces current through the failed cell string, which can lead to arcs and fire.
c3 drafted · lead
Connector Defect
Weak or poorly crimped connectors, or mismatched connector types, can arc. A significant share of PV fires start at quick connectors.
c4 drafted · lead
Junction Box Failure
Internal arcs can form inside the junction box, for example from bad solder contacts.
c5 drafted · lead
Mechanical stress
A junction box loosened by delamination puts mechanical stress on the diodes and connectors inside it, which can lead to arcs.
affects
c6 drafted · lead
Junction box
c7 drafted · lead
DC connector
presents_as
c8 drafted · lead
Deformed or burnt junction box
A junction box burnt by an arc at its input lead.
c9 drafted · lead
Fire damage
DC arcs usually cause destructive fires. Onsite grass fires have likely been triggered by arc faults.
c10 drafted · lead
High-frequency current noise
The arc's length and voltage fluctuate, which produces a high-frequency noise pattern.
detected_by
c11 drafted · lead
Waveform spectrum analysis
Spectrum analysis of the current and voltage waveforms. Detection is hard because arcs are transient.
c12 verified · fact
Machine-learning fault classification
Examples are DA-DCGAN on framed loop current and logistic regression on time- and frequency-domain features.
verified by: joshuahamsaverified on: 2026-10-20
mitigated_by
c13 verified · fact
Arc fault circuit interrupter
Installed on individual strings.
verified by: joshuahamsaverified on: 2026-10-20
c14 verified · fact
Safety isolation
Isolation is the priority when there is evidence of arcing or burning.
verified by: joshuahamsaverified on: 2026-10-20