FailureMode
Arc fault nuisance trip
- ID
fm:afci-nuisance-trip
- IRI
https://solarlattice.org/kb/fm/afci-nuisance-trip
- Status
- active
- Also known as
- false AFCI event, nuisance trips, AFCI events with Rapid Shutdown devices, RSD humming noise during MPPT sweep, false trips, AFCI events
An arc fault nuisance trip happens when the inverter's arc detector reports an arc but no real arc is present in the DC circuit. It can be caused by fast current changes from changing light. At sites with rapid shutdown devices, those devices can also hum during the inverter's MPPT sweep, and the inverter may read that noise as an arc. The inverter logs an arc event, stops feeding the grid, and may stay locked out until someone resets it manually. Never assume a trip is false. Inspect the array before every reset and look for discolored or melted wiring, burned junction boxes, and loose or badly crimped connectors. Where the array cannot be reached, test the cabling with a megohm meter. This finds a fault but does not show where it is. If random arc events affect several inverters at a site with rapid shutdown devices, turning off the ShadeFix sweep can stop the nuisance trips. A firmware update was planned to fix this. If arc events keep recurring, investigate right away. If the cause cannot be found, take the inverter out of service.
Claims
caused_by
c1 drafted · lead
MLPE electronic noise proposed
During the inverter's periodic MPPT sweep (ShadeFix), a rapid shutdown device can be pulled below its threshold voltage and its electronics may hum; the inverter can read this noise as an arc.
c2 drafted · lead
Inverter parameter settings
Reported when the ShadeFix MPPT sweep parameter is ON, which is the default on most current SMA models.
c3 verified · fact
Rapid irradiance changes proposed
Fast current changes caused by changing light, combined with a sensitive arc detection circuit, can trip the detector when no arc is present.
verified by: review-workflowverified on: 2026-10-24
affects
c4 drafted · lead
Arc fault detection board
review note: support check: partial - u2 mentions the arc detection circuit being triggered falsely, but no passage names a detection board as the affected component; this is only implied.
c5 drafted · lead
Inverter
c6 drafted · lead
Module-level rapid shutdown device
review note: support check: partial - u1 involves RSD devices as the noise source, but being 'affected' by the nuisance trip is not stated.
presents_as
c7 drafted · lead
Arc fault detected
SMA event IDs 4301/4302/8204/8206/8210 are reported, sometimes at random across several inverters.
c8 drafted · lead
Spurious fault event
c9 drafted · lead
Inverter shutdown
c10 drafted · lead
Operation inhibited
When AFCI is set with permanent operation inhibition, the inverter waits for a manual reset.
c11 drafted · lead
Inverter audible noise
The humming comes from the rapid shutdown device electronics during the MPPT sweep, not from the inverter.
review note: support check: partial - u1 says the RSD electronics hum during the sweep and the inverter reads it as an AFCI event, but it never lists inverter audible noise as a symptom, and the note that the hum is not from the inverter is only implied.
detected_by
c12 verified · fact
Visual inspection
verified by: review-workflowverified on: 2026-10-24
c13 drafted · lead
Tactile inspection
Gently tug DC cables at connectors and in the combiner box to find loose terminations or bad crimps.
review note: support check: partial - u2 describes gently tugging DC cables to find loose or badly crimped connections, but this finds real faults, not the nuisance trip itself.
c14 drafted · lead
Insulation resistance testing
Used on cabling where a hands-on inspection is not possible, such as residential rooftops. It does not pinpoint the fault location.
review note: support check: partial - u2 recommends a megohm meter where hands-on inspection is not possible and says it does not pinpoint the fault, but it frames this as finding a cabling failure, not detecting a nuisance trip.
distinguished_from
c15 drafted · lead
Arc fault — told apart by Visual inspection
A real arc leaves evidence such as discolored wiring or racking, melted connectors or insulation, and burned junction boxes. A false trip leaves no such damage and no loose or badly crimped connections.
review note: support check: partial - u2 says arcing leaves evidence that a visual inspection finds, but it does not state that a false trip leaves none.
mitigated_by
c16 drafted · lead
Inverter parameter adjustment
Set ShadeFix to 'NO' when random AFCI events appear across several inverters at sites with rapid shutdown devices.
c17 drafted · lead
Firmware update
The manufacturer said a future firmware release would address the condition.
c18 drafted · lead
Contact system installer
c19 drafted · lead
Manual reset of latched operation inhibition
Reset only after the array has been inspected.
review note: support check: partial - u9, u13 and u24 support a manual reset of operation inhibition, and u2 requires inspecting the site before resetting, but only u2 links reset to nuisance trips and it is not in the cited passages for this statement.
c20 drafted · lead
Close monitoring
Investigate recurring AFCI events at once. If no cause is found, take the inverter out of service.