Fault codes › Solis

Solis fault codes

Solis-1P(3.6-10)K-4G-US

CodeShown asClassProductionClearsReportsPage
AFCI Check FAULT fault after a manual reset Self-test failure 63
ARC-FAULT after a manual reset Arc fault detected 63
GRID-INTFGrid unstable Grid instability, AC overcurrent 62
INI-FAULTIni aliza on Protec on fault after a manual reset Internal device fault 62
NO-GRID Grid loss 61
OV-BUSDC BUS voltage is too high DC bus overvoltage 62
OV-DCDC voltage is too high DC overvoltage 61
OV-G-FOver Grid Frequency Grid overfrequency 61
OV-G-VOver Grid Voltage Grid overvoltage 60
OV-TEMTemperature Protec on fault Inverter overtemperature, High ambient temperature 62
UN-BUSDC BUS voltage is too low fault DC bus undervoltage 62
UN-G-FUnder Grid Frequency Grid underfrequency 61
UN-G-VUnder Grid Voltage Grid undervoltage 61
PV ISO-PRO 01/02Ground Protec on fault Low insulation resistance 62

Solis-3P(125-255)K-EHV-5G-US

CodeShown asClassProductionClearsReportsPage
12Power-FAULT12V power supply fault fault after a manual reset Auxiliary supply undervoltage 67
DCInj-FaultHigh DC injection current fault after a manual reset High DC injection 67
DC-INTFDC input overcurrent after a manual reset DC overcurrent 66
DSP-B-FaultComm. failure between main and slave DSP fault after a manual reset Internal communication failure 67
G-IMPHigh grid impedance High grid impedance 66
IG-ADGrid current sampling fail fault after a manual reset Measurement signal error 66
IGBT-OV-IOver IGBT current fault after a manual reset Inverter overcurrent 66
IGFOL-FGrid current tracking fail after a manual reset Grid current tracking failure 66
INI-FAULTInitialization system fault fault after a manual reset Internal device fault 67
NO-GRIDNo grid voltage Grid loss 66
OV-BUSOver DC bus voltage DC bus overvoltage 66
OV-DCA-IDC input overcurrent fault after a manual reset DC overcurrent 66
OV-G-IOver grid current after a manual reset AC overcurrent 66
OV-TEMOver Temperature fault Inverter overtemperature, High ambient temperature 66
RelayChk-FailRelay check fail fault after a manual reset 67
Reve-DCOne of the DC string is reversely connected Reverse polarity, Unbalanced MPPT string connection 67
GRID-INTF01/02Grid interference after a manual reset Grid instability 66
ILeak-PRO 01/02/03/04Leakage current protection High leakage current 67
OV-DC01/02/03/04Over DC voltage DC overvoltage 66
OV-G-F01/02Over grid frequency Grid overfrequency 66
OV-G-V01/02/03/04Over grid voltage Grid overvoltage 66
PV ISO-PRO 01/02PV isolation protection fault Low insulation resistance 67
UN-BUS01/02Under DC bus voltage fault DC bus undervoltage 66
UN-G-F01/02Under grid frequency fault Grid underfrequency 66
UN-G-V01/02Under grid voltage fault Grid undervoltage 66

Solis RHI-1P(5-10)K-HVES-5G-US

CodeShown asClassProductionClearsReportsPage
12Power-FAULT12V power supply fault fault after a manual reset Auxiliary supply undervoltage 35
AFCI Check FAULTAFCI module self check fault fault after a manual reset Self-test failure 34
ARC-FAULTARC detected in DC circuit after a manual reset Arc fault detected 34
DCInj-FaultHigh DC injection current fault after a manual reset High DC injection 34
DC-INTFDC input overcurrent after a manual reset DC overcurrent 34
DSP-B-FaultComm. failure between main and slave DSP fault after a manual reset Internal communication failure 34
G-IMPHigh grid impedance High grid impedance 34
IG-ADGrid current sampling fail fault after a manual reset Measurement signal error 34
IGBT-OV-IOver IGBT current fault after a manual reset Inverter overcurrent 34
IGFOL-FGrid current tracking fail after a manual reset Grid current tracking failure 34
INI-FAULTInitialization system fault fault after a manual reset Internal device fault 34
NO-BatteryUnconnected battery Battery disconnected 34
NO-GRIDNo grid voltage Grid loss 34
OV-BUSOver DC bus voltage DC bus overvoltage 34
OV-DCA-IDC input overcurrent fault after a manual reset DC overcurrent 35
Over-LoadBackup overload fault after a manual reset Inverter overload 35
OV-G-IOver grid current after a manual reset AC overcurrent 35
OV-IgTrAC side transient overcurrent fault after a manual reset AC overcurrent 35
OV-ILLCLLC hardware overcurrent after a manual reset Internal overcurrent or overvoltage 35
OV-TEMOver Temperature fault Inverter overtemperature, High ambient temperature 35
OV-VBackupBackup overvoltage fault after a manual reset Backup output AC overvoltage 35
OV-Vbatt-HBattery overvoltage hardware fault after a manual reset Battery overvoltage 35
RelayChk-FailRelay check fail fault after a manual reset 35
GRID-INTF01/02Grid interference after a manual reset Grid instability 34
ILeak-PRO 01/02/03/04leakage current protection High leakage current 34
OV-DC01/02/03/04Over DC voltage DC overvoltage 35
OV-G-F01/02Over grid frequency Grid overfrequency 35
OV-G-V01/02/03/04/05Over grid voltage Grid overvoltage 35
OV-Vbatt1The detection of battery overvol tage after a manual reset Battery overvoltage 35
PV ISO-PRO 01/02PV isolation protection fault Low insulation resistance 35
UN-BUS01/02Under DC bus voltage fault DC bus undervoltage 35
UN-G-F01/02Under grid frequency fault Grid underfrequency 35
UN-G-V01/02Under grid voltage fault Grid undervoltage 35

Solis S5-GC(75-125)K-US

CodeShown asClassProductionClearsReportsPage
ARC-FAULT fault after a manual reset Arc fault detected 71
GRID-INTFGrid unstable Grid instability, AC overcurrent 70
INI-FAULTInitialization Protect ion fault after a manual reset Internal device fault 71
NO-GRID Grid loss 70
OV-BUSDC BUS voltage is too high DC bus overvoltage 70
OV-DCDC voltage is too high DC overvoltage 70
OV-G-FOver Grid Frequency Grid overfrequency 70
OV-G-VOver Grid Voltage Grid overvoltage 69
OV-TEMTemperature Protect ion fault Inverter overtemperature, High ambient temperature 71
Reve-DC Reverse polarity, Unbalanced MPPT string connection 71
UN-BUSDC BUS voltage is too low fault needs service DC bus undervoltage 69
UN-G-VUnder Grid Voltage Grid undervoltage 69
PV ISO-PRO 01/02Ground Protect ion fault after a manual reset Low insulation resistance 71

Solis S6-EH1P(3.8-11.4)K-H-US

CodeShown asClassProductionClearsReportsPage
12Power-FAULT12V power supply fault fault after a manual reset Auxiliary supply undervoltage 74
AFCI Check FAULTAFCI module self check fault fault after a manual reset Self-test failure 72
ARC-FAULTARC detected in DC circuit after a manual reset Arc fault detected 72
DCInj-FaultHigh DC injection current fault after a manual reset High DC injection 72
DC-INTFDC input overcurrent after a manual reset DC overcurrent 72
DSP-B-FaultComm. failure between main and slave DSP fault after a manual reset Internal communication failure 72
G-IMPHigh grid impedance High grid impedance 72
IG-ADGrid current sampling fail fault after a manual reset Measurement signal error 72
IGBT-OV-IOver IGBT current fault after a manual reset Inverter overcurrent 72
IGFOL-FGrid current tracking fail after a manual reset Grid current tracking failure 72
INI-FAULTInitialization system fault fault after a manual reset Internal device fault 72
NO-BatteryUnconnected battery Battery disconnected 72
NO-GRIDNo grid voltage Grid loss 72
OV-BUSOver DC bus voltage DC bus overvoltage 72
OV-DCA-IDC input overcurrent fault after a manual reset DC overcurrent 73
Over-LoadBackup overload fault after a manual reset Inverter overload 73
OV-G-IOver grid current after a manual reset AC overcurrent 73
OV-IgTrAC side transient overcurrent fault after a manual reset AC overcurrent 73
OV-ILLCLLC hardware overcurrent after a manual reset Internal overcurrent or overvoltage 73
OV-TEMOver Temperature fault Inverter overtemperature, High ambient temperature 73
OV-VBackupBackup overvoltage fault after a manual reset Backup output AC overvoltage 73
OV-Vbatt-HBattery overvoltage hardware fault after a manual reset Battery overvoltage 73
RelayChk-FailRelay check fail fault after a manual reset 73
GRID-INTF01/02Grid interference after a manual reset Grid instability 72
ILeak-PRO 01/02/03/04leakage current protection High leakage current 72
OV-DC01/02/03/04Over DC voltage DC overvoltage 73
OV-G-F01/02Over grid frequency Grid overfrequency 73
OV-G-V01/02/03/04/05Over grid voltage Grid overvoltage 73
OV-Vbatt1The detection of battery overvol tage after a manual reset Battery overvoltage 73
PV ISO-PRO 01/02PV isolation protection fault Low insulation resistance 73
UN-BUS01/02Under DC bus voltage fault DC bus undervoltage 74
UN-G-F01/02Under grid frequency fault Grid underfrequency 74
UN-G-V01/02Under grid voltage fault Grid undervoltage 74

Solis S6-EH2P(9.6-16)K-SV-YD-L-US

CodeShown asClassProductionClearsReportsPage
12Power-FAULT12V undervoltage failure fault after a manual reset Auxiliary supply undervoltage 96
AFCI-CheckAFCI self-test failure fault after a manual reset Self-test failure 98
ARC-FAULTAFCI failure after a manual reset Arc fault detected 98
BatName-FAILWrong battery brand selection Configuration error 94
CAN FailCAN Fail Communication loss 94
DCInj-FaultThe current DC component exceeds the limit fault after a manual reset High DC injection 96
DC-INTFDC hardware overcurrent (1, 2, 3, 4) after a manual reset DC overcurrent 94
DSP-B-FaultThe master-slave DSP communication is abnormal fault after a manual reset Internal communication failure 98
Fan AlarmFan alarm Fan fault alarm 94
G-F-GLUGrid voltage frequency f luctuat ion fault Grid instability 97
G-PHASEUnbalanced grid voltage after a manual reset Phase imbalance 97
GRID-INTFAC hardware overcurrent (abc phase) Grid instability, AC overcurrent 94
GridToLoadGrid to load informational unaffected 95
IGBT-OV-IIGBT overcurrent fault after a manual reset Inverter overcurrent 96
IGFOL-FGrid current tracking failure after a manual reset Grid current tracking failure 97
ILeak-CheckLeakage current sensor fai lure fault after a manual reset Self-test failure 96
INI-FAULTAD zero drift overlink fault after a manual reset Internal device fault 98
LmtByDRMDRM Function ON reduced Remote power limit 95
LmtByEPMThe device's output is under cont rol led reduced Remote power limit 95
LmtByFreqFrequency power limited reduced by itself Grid frequency out of range 95
LmtByTempOver temperature power l imi ted reduced by itself Inverter overtemperature 95
LmtByUnFrUnder frequency limit reduced Grid underfrequency 95
LmtByVar Grid overvoltage 95
LmtByVgThe device is in the Volt-Watt mode Grid overvoltage 95
NO-BatteryBattery is not connected Battery disconnected 97
NO-GRIDNo grid Grid loss 97
OV-BUSDC bus overvoltage DC bus overvoltage 94
OV-BUS-HBattery overvoltage hardware failure / VBUS fault Battery overvoltage, DC bus overvoltage 96
OV-DCA-IDC 1 average overcurrent fault after a manual reset DC overcurrent 94
OV-DCB-IDC 2 average overcurrent fault after a manual reset DC overcurrent 94
Over-LoadLoad overload fault after a manual reset Inverter overload 97
OV-G-IA phase RMS value overcurrent after a manual reset AC overcurrent 94
OV-ILLCLLC hardware overcurrent after a manual reset Internal overcurrent or overvoltage 98
OV-TEMModule over temperature fault Inverter overtemperature, High ambient temperature 96
OV-VBackupInverting overvoltage after a manual reset Backup output AC overvoltage 97
OV-VbattBattery undervoltage detected Battery voltage out of range 94
OV-Vbatt-HBattery overvoltage hardware failure / VBUS after a manual reset Battery overvoltage 96
RelayChk-FailRelay failure fault after a manual reset 96
StandbySynochOff grid status to On grid status informational 95
Surge AlarmOn-site grid surge fault after a manual reset Grid surge 97
UNB-BUSDC bus unbalanced voltage fault after a manual reset Neutral point voltage imbalance 94
UN-TEMLow temperature protection fault after a manual reset Inverter undertemperature 96
UN-VbattBattery overvoltage detected after a manual reset Battery voltage out of range 94
GRID-INTF02Power grid disturbance 02 fault Grid instability 96
ILeak-PRO01Leakage current failure 01 (30mA) fault High leakage current 96
ILeak-PRO02Leakage current failure 02 (60mA) fault High leakage current 96
ILeak-PRO03Leakage current failure 03 (150mA) fault High leakage current 96
ILeak-PRO04Leakage current failure 04 fault High leakage current 96
OV-DC01DC 1 input overvoltage after a manual reset DC overvoltage 94
OV-DC02DC 2 input overvoltage fault after a manual reset DC overvoltage 94
OV-G-F01Grid frequency exceeds the upper frequency range fault Grid overfrequency 97
OV-G-F02Grid frequency exceeds the upper frequency range fault Grid overfrequency 97
OV-G-V01Grid voltage exceeds the upper voltage range fault Grid overvoltage 97
OV-G-V02Grid transient overvoltage fault Grid overvoltage 97
OV-G-V03Grid transient overvoltage fault after a manual reset Grid overvoltage 97
OV-G-V04Grid voltage exceeds the upper voltage range fault Grid overvoltage 97
OV-G-V05Grid voltage RMS instanta-neous overvoltage fault fault Grid overvoltage 97
PV ISO-PRO01PV negative ground fault fault Ground fault alarm or trip 96
PV ISO-PRO02PV positive ground fault fault Ground fault alarm or trip 96
UN-BUS01DC bus undervoltage fault after a manual reset DC bus undervoltage 94
UN-BUS02Abnormal detection of DC bus voltage fault after a manual reset DC bus voltage detection error 94
UN-G-F01Grid frequency exceeds the lower frequency range fault Grid underfrequency 97
UN-G-F02Grid frequency exceeds the lower frequency range fault Grid underfrequency 97
UN-G-V01Grid voltage exceeds the lower voltage range fault Grid undervoltage 97
UN-G-V02Grid voltage exceeds the lower voltage range fault Grid undervoltage 97

Solis S6-EH3P(30-60)K-NV-YD-H-US

CodeShown asClassProductionClearsReportsPage
12Power-FAULT12V undervoltage failure fault after a manual reset Auxiliary supply undervoltage 94
AFCI-CheckAFCI self-test failure fault after a manual reset Self-test failure 95
ARC-FAULTAFCI failure after a manual reset Arc fault detected 95
BatName-FAILWrong battery brand selection Configuration error 93
CAN FailCAN Fail Communication loss 93
DCInj-FaultThe current DC component exceeds the limit fault after a manual reset High DC injection 94
DC-INTFDC hardware overcurrent (1, 2, 3, 4) after a manual reset DC overcurrent 93
DSP-B-FaultThe master-slave DSP communication is abnormal fault after a manual reset Internal communication failure 95
Fan AlarmFan alarm Fan fault alarm 93
G-F-GLUGrid voltage frequency f luctuat ion fault Grid instability 92
G-PHASEUnbalanced grid voltage after a manual reset Phase imbalance 92
GRID-INTFAC hardware overcurrent (abc phase) Grid instability, AC overcurrent 93
GridToLoadGrid to load informational unaffected 91
IGBT-OV-IIGBT overcurrent fault after a manual reset Inverter overcurrent 94
IGFOL-FGrid current tracking failure after a manual reset Grid current tracking failure 92
ILeak-CheckLeakage current sensor fai lure fault after a manual reset Self-test failure 94
INI-FAULTAD zero drift overlink fault after a manual reset Internal device fault 95
LmtByDRMDRM Function ON reduced Remote power limit 91
LmtByEPMThe device's output is under cont rol led reduced Remote power limit 91
LmtByFreqFrequency power limited reduced by itself Grid frequency out of range 91
LmtByTempOver temperature power l imi ted reduced by itself Inverter overtemperature 91
LmtByUnFrUnder frequency limit reduced Grid underfrequency 91
LmtByVar Grid overvoltage 91
LmtByVgThe device is in the Volt-Watt mode Grid overvoltage 91
NO-BatteryBattery is not connected Battery disconnected 92
NO-GRIDNo grid Grid loss 92
OV-BUSDC bus overvoltage DC bus overvoltage 93
OV-BUS-HBattery overvoltage hardware failure / VBUS fault Battery overvoltage, DC bus overvoltage 94
OV-DCA-IDC 1 average overcurrent fault after a manual reset DC overcurrent 93
OV-DCB-IDC 2 average overcurrent fault after a manual reset DC overcurrent 93
Over-LoadLoad overload fault after a manual reset Inverter overload 92
OV-G-IA phase RMS value overcurrent after a manual reset AC overcurrent 93
OV-ILLCLLC hardware overcurrent after a manual reset Internal overcurrent or overvoltage 94
OV-TEMModule over temperature fault Inverter overtemperature, High ambient temperature 94
OV-VBackupInverting overvoltage after a manual reset Backup output AC overvoltage 92
OV-VbattBattery undervoltage detected Battery voltage out of range 93
OV-Vbatt-HBattery overvoltage hardware failure / VBUS after a manual reset Battery overvoltage 94
RelayChk-FailRelay failure fault after a manual reset 94
StandbySynochOff grid status to On grid status informational 91
Surge AlarmOn-site grid surge fault after a manual reset Grid surge 92
UNB-BUSDC bus unbalanced voltage fault after a manual reset Neutral point voltage imbalance 93
UN-TEMLow temperature protection fault after a manual reset Inverter undertemperature 94
UN-VbattBattery overvoltage detected after a manual reset Battery voltage out of range 93
GRID-INTF02Power grid disturbance 02 fault Grid instability 94
ILeak-PRO01Leakage current failure 01 (30mA) fault High leakage current 94
ILeak-PRO02Leakage current failure 02 (60mA) fault High leakage current 94
ILeak-PRO03Leakage current failure 03 (150mA) fault High leakage current 94
ILeak-PRO04Leakage current failure 04 fault High leakage current 94
OV-DC01DC 1 input overvoltage after a manual reset DC overvoltage 93
OV-DC02DC 2 input overvoltage fault after a manual reset DC overvoltage 93
OV-G-F01Grid frequency exceeds the upper frequency range fault Grid overfrequency 92
OV-G-F02Grid frequency exceeds the upper frequency range fault Grid overfrequency 92
OV-G-V01Grid voltage exceeds the upper voltage range fault Grid overvoltage 92
OV-G-V02Grid transient overvoltage fault Grid overvoltage 92
OV-G-V03Grid transient overvoltage fault after a manual reset Grid overvoltage 92
OV-G-V04Grid voltage exceeds the upper voltage range fault Grid overvoltage 92
OV-G-V05Grid voltage RMS instanta-neous overvoltage fault fault Grid overvoltage 92
PV ISO-PRO01PV negative ground fault fault Ground fault alarm or trip 94
PV ISO-PRO02PV positive ground fault fault Ground fault alarm or trip 94
UN-BUS01DC bus undervoltage fault after a manual reset DC bus undervoltage 93
UN-BUS02Abnormal detection of DC bus voltage fault after a manual reset DC bus voltage detection error 93
UN-G-F01Grid frequency exceeds the lower frequency range fault Grid underfrequency 92
UN-G-F02Grid frequency exceeds the lower frequency range fault Grid underfrequency 92
UN-G-V01Grid voltage exceeds the lower voltage range fault Grid undervoltage 92
UN-G-V02Grid voltage exceeds the lower voltage range fault Grid undervoltage 92

Solis S6-EH3P(75-150)K10-NV-YD-H-US

CodeShown asClassProductionClearsReportsPage
12Power-FAULT12V undervoltage failure fault after a manual reset Auxiliary supply undervoltage 118
AFCI-CheckAFCI self-test failure fault after a manual reset Self-test failure 118
ARC-FAULTAFCI failure after a manual reset Arc fault detected 118
BatName-FAILWrong battery brand selection Configuration error 117
CAN FailCAN Fail Communication loss 117
DCInj-FaultThe current DC component exceeds the limit fault after a manual reset High DC injection 117
DC-INTFDC hardware overcurrent (1, 2, 3, 4) after a manual reset DC overcurrent 117
DSP-B-FaultThe primary-secondary DSP communication is abnormal fault after a manual reset Internal communication failure 118
Fan AlarmFan alarm Fan fault alarm 117
G-F-GLUGrid voltage frequency f luctuat ion fault Grid instability 116
G-PHASEUnbalanced grid voltage after a manual reset Phase imbalance 116
GRID-INTFAC hardware overcurrent (abc phase) Grid instability, AC overcurrent 117
GridToLoadGrid to load informational unaffected 115
IGBT-OV-IIGBT overcurrent fault after a manual reset Inverter overcurrent 118
IGFOL-FGrid current tracking failure after a manual reset Grid current tracking failure 116
ILeak-CheckLeakage current sensor fai lure fault after a manual reset Self-test failure 118
INI-FAULTAD zero drift overlink fault after a manual reset Internal device fault 118
LmtByDRMDRM Function ON reduced Remote power limit 115
LmtByEPMThe device's output is under cont rol led reduced Remote power limit 115
LmtByFreqFrequency power limited reduced by itself Grid frequency out of range 115
LmtByTempOver temperature power l imi ted reduced by itself Inverter overtemperature 115
LmtByUnFrUnder frequency limit reduced Grid underfrequency 115
LmtByVar Grid overvoltage 115
LmtByVgThe device is in the Volt-Watt mode Grid overvoltage 115
NO-BatteryBattery is not connected Battery disconnected 116
NO-GRIDNo grid Grid loss 116
OV-BUSDC bus overvoltage DC bus overvoltage 117
OV-BUS-HBattery overvoltage hardware failure / VBUS fault Battery overvoltage, DC bus overvoltage 118
OV-DCA-IDC 1 average overcurrent fault after a manual reset DC overcurrent 117
OV-DCB-IDC 2 average overcurrent fault after a manual reset DC overcurrent 117
Over-LoadLoad overload fault after a manual reset Inverter overload 116
OV-G-IA phase RMS value overcurrent after a manual reset AC overcurrent 117
OV-ILLCLLC hardware overcurrent after a manual reset Internal overcurrent or overvoltage 118
OV-TEMModule over temperature fault Inverter overtemperature, High ambient temperature 118
OV-VBackupInverting overvoltage after a manual reset Backup output AC overvoltage 116
OV-VbattBattery overvoltage detected Battery voltage out of range 117
OV-Vbatt-HBattery overvoltage hardware failure / VBUS after a manual reset Battery overvoltage 118
RelayChk-FailRelay failure fault after a manual reset 118
StandbySynochOff grid status to On grid status informational 115
Surge AlarmOn-site grid surge fault after a manual reset Grid surge 116
UNB-BUSDC bus unbalanced voltage fault after a manual reset Neutral point voltage imbalance 117
UN-TEMLow temperature protection fault after a manual reset Inverter undertemperature 118
UN-VbattBattery undervoltage detected after a manual reset Battery voltage out of range 117
GRID-INTF02Power grid disturbance 02 fault Grid instability 118
ILeak-PRO01Leakage current failure 01 (30mA) fault High leakage current 118
ILeak-PRO02Leakage current failure 02 (60mA) fault High leakage current 118
ILeak-PRO03Leakage current failure 03 (150mA) fault High leakage current 118
ILeak-PRO04Leakage current failure 04 fault High leakage current 118
OV-DC01DC 1 input overvoltage after a manual reset DC overvoltage 117
OV-DC02DC 2 input overvoltage fault after a manual reset DC overvoltage 117
OV-G-F01Grid frequency exceeds the upper frequency range fault Grid overfrequency 116
OV-G-F02Grid frequency exceeds the upper frequency range fault Grid overfrequency 116
OV-G-V01Grid voltage exceeds the upper voltage range fault Grid overvoltage 116
OV-G-V02Grid transient overvoltage fault Grid overvoltage 116
OV-G-V03Grid transient overvoltage fault after a manual reset Grid overvoltage 116
OV-G-V04Grid voltage exceeds the upper voltage range fault Grid overvoltage 116
OV-G-V05Grid voltage RMS instanta-neous overvoltage fault fault Grid overvoltage 116
PV ISO-PRO01PV negative ground fault fault Ground fault alarm or trip 118
PV ISO-PRO02PV positive ground fault fault Ground fault alarm or trip 118
UN-BUS01DC bus undervoltage fault after a manual reset DC bus undervoltage 117
UN-BUS02Abnormal detection of DC bus voltage fault after a manual reset DC bus voltage detection error 117
UN-G-F01Grid frequency exceeds the lower frequency range fault Grid underfrequency 116
UN-G-F02Grid frequency exceeds the lower frequency range fault Grid underfrequency 116
UN-G-V01Grid voltage exceeds the lower voltage range fault Grid undervoltage 116
UN-G-V02Grid voltage exceeds the lower voltage range fault Grid undervoltage 116

Solis S6-GC(25-60)K-US

CodeShown asClassProductionClearsReportsPage
AFCI-CheckAFCI self check protect ion fault after a manual reset Self-test failure 74
ARC-FAULT after a manual reset Arc fault detected 72
BoostFalDC Boost converter fault fault after a manual reset 75
DCInj-FaultExcessive DC component fault after a manual reset High DC injection 74
DC-INTFDC input disturbance after a manual reset DC overcurrent 73
DRM LINK FailDRM link failed fault after a manual reset Communication loss 75
DSP-B-FaultDSP-B internal protect ion fault after a manual reset Internal communication failure 74
DSP-SelfCheckDSP self-check is abnormal fault after a manual reset Self-test failure 75
G-F-FLUGrid frequency fluctuat ion after a manual reset Grid frequency out of range 73
G-PHASEUnbalanced Grid after a manual reset Phase imbalance 73
GRID-INTFGrid unstable Grid instability, AC overcurrent 71
IG-ADAbnormal grid current sampling fault after a manual reset Measurement signal error 75
IGBT-OV-IIGBT overcurrent fault after a manual reset Inverter overcurrent 74
IGFOL-FGrid current tracking is abnormal after a manual reset Grid current tracking failure 73
ILeak-CheckLeakage current self check protect ion fault after a manual reset Self-test failure 74
ILeak-PROLeakage current protect ion fault High leakage current 74
INI-FAULTInitialization Protect ion fault after a manual reset Internal device fault 72
NO-GRID Grid loss 71
OV-BUSDC BUS voltage is too high DC bus overvoltage 71
OV-DCDC voltage is too high DC overvoltage 71
OV-DCA-IDC1 average overcurrent fault after a manual reset DC overcurrent 75
OV-DCB-IDC1 average overcurrent fault after a manual reset DC overcurrent 75
OV-G-FOver Grid Frequency Grid overfrequency 71
OV-G-IGrid overcurrent after a manual reset AC overcurrent 73
OV-G-VOver Grid Voltage Grid overvoltage 70
OV-IgTrGrid current transient overcurrent fault after a manual reset AC overcurrent 75
OV-TEMTemperature Protect ion fault Inverter overtemperature, High ambient temperature 72
PHASE FAULTAbnormal phase of the grid fault after a manual reset Abnormal grid phase angle 75
PID RepairingInverter logic fault fault Internal device fault 73
RelayChk-FailRelay detection fai lure fault after a manual reset 74
Reve-DC Reverse polarity, Unbalanced MPPT string connection 72
UN-BUSDC BUS voltage is too low fault DC bus undervoltage 70
UN-G-FGrid under frequency Grid underfrequency 73
UN-G-VUnder Grid Voltage Grid undervoltage 70
UN-TEMUnder temperature protect ion fault after a manual reset Inverter undertemperature 74
PV ISO-PRO 01/02Ground Protect ion fault Low insulation resistance 72

Solis S6-GU(250-350)K-EHV-US

CodeShown asClassProductionClearsReportsPage
AFCI-CheckAFCI self check protect ion fault after a manual reset Self-test failure 49
ARC-FAULT after a manual reset Arc fault detected 47
BoostFalDC Boost converter fault fault after a manual reset 50
DCInj-FaultExcessive DC component fault after a manual reset High DC injection 49
DC-INTFDC input disturbance after a manual reset DC overcurrent 48
DRM LINK FailDRM link failed fault after a manual reset Communication loss 50
DSP-B-FaultDSP-B internal protect ion fault after a manual reset Internal communication failure 49
DSP-SelfCheckDSP self-check is abnormal fault after a manual reset Self-test failure 50
G-F-FLUGrid frequency fluctuat ion after a manual reset Grid frequency out of range 48
G-PHASEUnbalanced Grid after a manual reset Phase imbalance 48
GRID-INTFGrid unstable Grid instability, AC overcurrent 46
IG-ADAbnormal grid current sampling fault after a manual reset Measurement signal error 50
IGBT-OV-IIGBT overcurrent fault after a manual reset Inverter overcurrent 49
IGFOL-FGrid current tracking is abnormal after a manual reset Grid current tracking failure 48
ILeak-CheckLeakage current self check protect ion fault after a manual reset Self-test failure 49
ILeak-PROLeakage current protect ion fault High leakage current 49
INI-FAULTInitialization Protect ion fault after a manual reset Internal device fault 47
NO-GRID Grid loss 46
OV-BUSDC BUS voltage is too high DC bus overvoltage 46
OV-DCDC voltage is too high DC overvoltage 46
OV-DCA-IDC1 average overcurrent fault after a manual reset DC overcurrent 50
OV-DCB-IDC1 average overcurrent fault after a manual reset DC overcurrent 50
OV-G-FOver Grid Frequency Grid overfrequency 46
OV-G-IGrid overcurrent after a manual reset AC overcurrent 48
OV-G-VOver Grid Voltage Grid overvoltage 45
OV-IgTrGrid current transient overcurrent fault after a manual reset AC overcurrent 50
OV-TEMTemperature Protect ion fault Inverter overtemperature, High ambient temperature 47
PHASE FAULTAbnormal phase of the grid fault after a manual reset Abnormal grid phase angle 50
PID RepairingInverter logic fault fault Internal device fault 48
RelayChk-FailRelay detection fai lure fault after a manual reset 49
Reve-DC Reverse polarity, Unbalanced MPPT string connection 47
UN-BUSDC BUS voltage is too low fault DC bus undervoltage 45
UN-G-FGrid under frequency Grid underfrequency 48
UN-G-VUnder Grid Voltage Grid undervoltage 45
UN-TEMUnder temperature protect ion fault after a manual reset Inverter undertemperature 49
PV ISO-PRO 01/02Ground Protect ion fault Low insulation resistance 47

Codes are sorted by vendor prefix and number. Each row links to the code's record; concepts link to their reading rule.