Also known as
Undervoltage, grid under-voltage

A grid undervoltage fault means the inverter measured an AC grid voltage below its set protection value and disconnected from the grid. Inverters and storage systems report it as a fault code or a status flag when the measured voltage falls outside the protection trip thresholds. Usually the inverter reconnects by itself once the grid voltage is normal again, so a single event needs no action. If the fault keeps coming back, first measure the actual grid voltage. If it really is below the setpoint, the cause is on the utility side and the local power company should be contacted. If the grid voltage is normal, check in the app or on the LCD that the undervoltage protection parameters are set correctly for the local grid code. Next, check that the AC cable is firmly seated in its terminals. If none of these checks finds the cause, contact the inverter manufacturer's service.