Solar Lattice

Symptom

Grid overvoltage

ID
symptom:grid-overvoltage
IRI
https://solarlattice.org/kb/symptom/grid-overvoltage
Status
active
Also known as
AC overvoltage, Over Grid Voltage, OV-G-V, 10-minute grid overvoltage, Grid transient overvoltage, Grid Uncompliant

Grid overvoltage means the inverter measures AC voltage above its protection setpoint and disconnects from the grid. It normally reconnects once the grid is back to normal. In monitoring data it often repeats as a cycle: the inverter trips, voltage drops, the inverter reconnects after the set delay, and voltage climbs until the next trip, which may come seconds or minutes later. Some inverters report a separate fault when the ten-minute average voltage stays too high, and another for short transient overvoltage spikes. The cause can be a weak grid, where high distribution-grid resistance meets a lot of local PV capacity. It can also be local, from AC cables between the inverter and the grid connection that are too small or too resistive. Check first: with the DC switch off, measure AC voltage at the inverter. If it is already high, the grid is the cause and the utility should be contacted. If voltage is only high at full power, compare the inverter display with your test-point readings and review the cable ampacity, voltage-drop calculation and cable cross-section. Also confirm that the overvoltage protection parameters are set correctly. Change them only with the utility operator's consent.

<!-- review notes

Claims

observed_as

c1 verified · fact Grid voltage outside limits

The inverter or storage unit sees AC grid voltage above its protection setpoint and disconnects. It usually reconnects once the grid returns to normal.

verified by: review-workflowverified on: 2026-10-20review note: support check: partial - Passages show grid overvoltage faults where voltage exceeds the set protection value and the inverter reconnects after normalization, but the specific signal behaviors (power falling to zero while disconnected, voltage rising before the trip) are not stated.

c2 drafted · lead Ten-minute average overvoltage

The ten-minute average of grid voltage stays above the permitted range, which points to grid voltage or grid impedance at the connection point being too high.

c3 drafted · lead Repeated trip-reconnect cycling

The inverter disconnects, voltage falls, it reconnects after the reconnection delay, and voltage climbs again. The next trip can follow after seconds, minutes or longer as the wires heat up again.

c4 drafted · lead Transient grid overvoltage event

A short voltage spike above the standard value, reported under a separate fault code from sustained overvoltage.

c5 drafted · lead Volt-watt power derating

With volt-watt derating set up, active power is reduced as grid voltage rises between a start voltage and an end voltage. These voltages are configurable settings.

review note: support check: partial - The derating table gives the V1 start and V2 end voltage settings, which are configurable, but it does not explicitly state that power is reduced between them (only start/end power points) or describe the monitoring signals.