Also known as
10-minute grid overvoltage

This signature appears when the inverter's ten-minute average of grid voltage moves outside the permitted range. One manufacturer reports it as fault code 014, meaning the grid voltage has stayed above the inverter's preset AC voltage for a long time. The usual cause is grid voltage or grid impedance that is too high at the connection point. The voltage can rise because the distribution grid has high resistance compared with the PV capacity nearby, or because the wiring between the inverter and the grid connection has too much resistance. To protect power quality, the inverter disconnects from the utility grid when this happens. After a disconnection the voltage falls and the inverter reconnects. The voltage can then climb again, so the trips may repeat after seconds, minutes or longer. On some inverters the moving-average voltage limits can be configured. The default upper limit is 110 percent, and the default trip time on the low-voltage side is 600 seconds. Wait for the inverter to return to normal. If the fault keeps coming back, contact the manufacturer.

<!-- review notes

Signals

Monitoring channels where this signature appears, named by SunSpec model point.

PointUnitPattern
model_103.PhVphAVRolling ten-minute average of the phase voltage stays above the allowed upper limit