Grid parameters out of range

ID
symptom:grid-parameters-out-of-range
IRI
https://solarlattice.org/kb/symptom/grid-parameters-out-of-range
Status
active
Also known as
Grid Fail, W003

The inverter reports a grid warning, for example W003 Grid Fail with a yellow LED, when grid voltage or frequency goes beyond the limits set by the operator during normal operation. Possible triggers are an absent grid voltage, after which the inverter shows Missing Grid, an unstable voltage that is too low or too high, or an unstable grid frequency. The alarm relay switches while W003 to W007 are present and resets when the signal ends, because checking the grid is normal operation and not an alarm state. Check the grid voltage first at the inverter and then at the supply point. If it is absent at both, the problem is on the grid side. If the voltage rises only while the inverter is exporting, or is high at the supply, the line or grid impedance is high. Ask the utility to adjust the voltage, and change inverter limits only with their approval and with customer assistance. If the voltage at the supply point is much lower than at the inverter, the line between the inverter and the contactor needs attention. If voltage stays high, the inverter may first reduce output power and later disconnect if a 10-minute average stays out of range. Check whether the protection settings suit the selected grid standard.

<!-- review notes

Claims

observed_as

c1 verified · fact Grid voltage outside limits

W003 is raised when, during normal operation, grid voltage goes beyond operator-set limits, including unstable voltage that is too low or too high.

verified by: review-workflowverified on: 2026-10-23

c2 verified · fact Grid frequency outside limits

An unstable grid frequency is one trigger for W003. Other vendors report a separate fault for abnormal grid frequency.

verified by: review-workflowverified on: 2026-10-23

c3 drafted · lead Zero AC grid voltage

When grid voltage is absent, the inverter changes to Missing Grid. While Missing Grid is shown, the alarm contact stays at rest.

c4 drafted · lead Grid voltage rise with power

If the voltage rises while the inverter is connected, the line or grid impedance is high.

c5 verified · fact Ten-minute average overvoltage

This is the related E036 condition: grid voltage averaged over 10 minutes is outside the permitted range. The inverter limits power first and disconnects if the voltage does not settle.

verified by: review-workflowverified on: 2026-10-23

c6 verified · fact Volt-watt power derating

The inverter reduces output automatically when grid voltage is too high or too low.

verified by: review-workflowverified on: 2026-10-23