Symptom
Grid parameters out of range
- ID
symptom:grid-parameters-out-of-range
- IRI
https://solarlattice.org/kb/symptom/grid-parameters-out-of-range
- Status
- active
- Also known as
- Grid Fail, W003
The inverter reports a grid warning, for example W003 Grid Fail with a yellow LED, when grid voltage or frequency goes beyond the limits set by the operator during normal operation. Possible triggers are an absent grid voltage, after which the inverter shows Missing Grid, an unstable voltage that is too low or too high, or an unstable grid frequency. The alarm relay switches while W003 to W007 are present and resets when the signal ends, because checking the grid is normal operation and not an alarm state. Check the grid voltage first at the inverter and then at the supply point. If it is absent at both, the problem is on the grid side. If the voltage rises only while the inverter is exporting, or is high at the supply, the line or grid impedance is high. Ask the utility to adjust the voltage, and change inverter limits only with their approval and with customer assistance. If the voltage at the supply point is much lower than at the inverter, the line between the inverter and the contactor needs attention. If voltage stays high, the inverter may first reduce output power and later disconnect if a 10-minute average stays out of range. Check whether the protection settings suit the selected grid standard.
<!-- review notes
- sentence 4: support check: partial - The passages say to check at the inverter and then at the supply point if absent, but they do not say that absence at both means the problem is on the grid side.
- sentence 5: support check: partial - High impedance and asking the operator to adjust voltage are stated, but 'utility' is not named, and 'only while exporting' is a stronger reading than 'tends to rise when connected'.
- sentence 7: support check: partial - Power limiting then disconnection on a 10-minute average is stated, but checking protection settings against the grid standard is only loosely supported (the standard-dependent U< and U> values, and the Sungrow protection-parameter check for underfrequency).
- sentence 4: review: partial - The order of checks (inverter first, then the supply point) is stated, but the conclusion that absence at both means a grid-side problem is not.
- sentence 7: review: partial - Power limiting followed by disconnection on an out-of-range 10-minute voltage average is stated; checking protection settings against the selected grid standard is only loosely supported (U</U> values depend on the country standard; Sungrow says to check that protection parameters are…
-->
Claims
observed_as
c1 verified · fact
Grid voltage outside limits
W003 is raised when, during normal operation, grid voltage goes beyond operator-set limits, including unstable voltage that is too low or too high.
verified by: review-workflowverified on: 2026-10-23
c2 verified · fact
Grid frequency outside limits
An unstable grid frequency is one trigger for W003. Other vendors report a separate fault for abnormal grid frequency.
verified by: review-workflowverified on: 2026-10-23
c3 drafted · lead
Zero AC grid voltage
When grid voltage is absent, the inverter changes to Missing Grid. While Missing Grid is shown, the alarm contact stays at rest.
c4 drafted · lead
Grid voltage rise with power
If the voltage rises while the inverter is connected, the line or grid impedance is high.
c5 verified · fact
Ten-minute average overvoltage
This is the related E036 condition: grid voltage averaged over 10 minutes is outside the permitted range. The inverter limits power first and disconnects if the voltage does not settle.
verified by: review-workflowverified on: 2026-10-23
c6 verified · fact
Volt-watt power derating
The inverter reduces output automatically when grid voltage is too high or too low.
verified by: review-workflowverified on: 2026-10-23