Volt-watt power derating

ID
meas:overvoltage-power-derating
IRI
https://solarlattice.org/kb/meas/overvoltage-power-derating
Status
active
Also known as
Grid Over Voltage Derating, Volt-Watt, grid overvoltage derating

Volt-watt derating is an open-loop limit on real power that responds when the grid voltage goes too high. Grid voltage is measured at the point of interconnection meter. A programmable curve sets how far output is limited as the voltage rises. The derating takes effect over a set open-loop response time, which defaults to 10 seconds under IEEE1547-2018 and 5 seconds under Rule21. In the Tesla controls, the first real power limit is fixed at 1 per unit. A read-only register reports the power limit worked out from the Volt-Watt curve, so trend that register alongside grid voltage. On Solis inverters Volt-watt is one of several working modes and can run together with Volt-var. The working mode display shows which of the two takes priority.

<!-- review notes

Signals

Monitoring channels where this signature appears, named by SunSpec model point.

PointUnitPattern
model_103.WWAC power falls below available power as AC voltage rises above the derating start voltage
model_103.PhVphAVAC voltage elevated into the volt-watt derating band