Grid frequency out of range

ID
symptom:grid-frequency-out-of-range
IRI
https://solarlattice.org/kb/symptom/grid-frequency-out-of-range
Status
active
Also known as
GridF.OutLim, Grid incident

The inverter has found that the grid frequency is outside its allowed protection range, or it cannot detect the grid at all, so it trips off the grid. In the data, AC output stops and the measured grid frequency sits above the upper limit or below the lower limit. On CPS units at their IEEE1547-2018 defaults, the level 1 limits are 61.2 Hz on the high side and 58.5 Hz on the low side. The usual causes are a real frequency problem on the utility grid or a poor or loose AC connection between the inverter and the grid. First, watch the inverter for about 10 minutes to see if the alarm clears by itself. Inverters normally reconnect once the grid is back to normal. Next, read the measured frequency on the LCD. If it is within the limits, restart the inverter. If not, check that the AC wiring and the cable to the grid are secure and not damaged. If the actual grid frequency is outside the set range, contact the local utility. Also check that the frequency protection settings are set correctly. If an independent measurement shows a normal frequency but the inverter still reports it out of range, the inverter's measurement circuit may be faulty. Contact manufacturer service if the alarm keeps coming back.

<!-- review notes

Claims

observed_as

c1 verified · fact Grid frequency outside limits

The CPS manuals say to compare the frequency shown on the inverter LCD with the limits. Solis notes that a bad LCD reading can come from a faulty measurement circuit, so check it against a test-point measurement.

verified by: review-workflowverified on: 2026-10-20

c2 drafted · lead Zero power with irradiance

The inverter disconnects or cannot connect to the grid while frequency is out of range. The same alarm can also be raised when no grid is detected.