Solar Lattice

Fault codes › SMA › Sunny Highpower PEAK3 (SHP 125-172-US)

SMA PEAK3-US 3701

Code
3701
Shown as
Residual current too high > Check generator
Page
63
ID
fc:sma-shp-peak3-3701
IRI
https://solarlattice.org/kb/fc/sma-shp-peak3-3701
Status
active
Also known as
3701, SMA 3701, Residual current too high > Check generator
Category
Inverters
Class fault drafted · lead
Production stops drafted · lead
Clears by itself drafted · lead

Decoded

Reports ground fault alarm or trip; look at PV array; confirm with insulation resistance testing, open-circuit voltage measurement, grid voltage measurement, visual inspection, infrared thermography; do: grounding conductor check, DC wiring check.

What can be behind Ground fault alarm or trip

Failure modes that present as the reported condition, and the tests that tell them apart.

Defined in

The manufacturer's own cause and corrective text is not reproduced here.

Same condition on other equipment

ABB / FIMER
ABB / FIMER PVS-166-175-TL E018, ABB / FIMER PVS-60-TL E018, ABB / FIMER TRIO-20.0-27.6-TL E018, ABB / FIMER UNO-DM-3.3-5.0-PLUS E018, ABB / FIMER UNO-DM-6.0-PLUS E018
CPS
CPS SCA50-100K-T PFault0040, CPS SCA50-100K-T Protect0200
Enphase
Enphase M215-M250 GFI Tripped
Fronius
Fronius Galvo 475, Fronius Primo 475, Fronius Symo 475
Huawei
Huawei SUN2000-100KTL-USH0 2031
SMA
SMA SB-US-40 3501, SMA SB-US-40 3601, SMA SB-US-40 3701, SMA SB-US-41 3501, SMA SB-US-41 3601, SMA SB-US-41 3701, SMA SBSE-US-50 3501, SMA SBSE-US-50 3601, SMA SBSE-US-50 3701, SMA PEAK3-US 3501, SMA PEAK3-US 3601, SMA CORE1-US 3501, SMA CORE1-US 3701, SMA STP-TL-US 3501, SMA STP-TL-US 3601, SMA STP-TL-US 3701, SMA STP-X-US 3501, SMA STP-X-US 3601, SMA STP-X-US 3701, SMA SC-CP-XT 3501, SMA SC-CP-XT 3502, SMA SC-CP-XT 3507, SMA SC-CP-XT 3512, SMA SC-CP-XT 3515, SMA SC-CP-XT 3601, SMA SC-CP-XT 6487
Schneider Electric
Schneider Electric CL125 033
Solis
Solis S6-EH2P PV ISO-PRO01, Solis S6-EH2P PV ISO-PRO02, Solis S6-EH3P30-60K PV ISO-PRO01, Solis S6-EH3P30-60K PV ISO-PRO02, Solis S6-EH3P75-150K PV ISO-PRO01, Solis S6-EH3P75-150K PV ISO-PRO02
Sungrow
Sungrow SG200HX 1600-1615, Sungrow SG200HX 1632-1655, Sungrow SG250HX 1600-1615, Sungrow SG250HX 1632-1655, Sungrow SG350HX 1600-1615, Sungrow SG350HX 1632-1655
Yaskawa Solectria
Yaskawa Solectria SGI-XTM DC GND Fault, Yaskawa Solectria SGI-XTM RCM Fault, Yaskawa Solectria XGI-1500-1MW CRIT-7, Yaskawa Solectria XGI-1500 CRIT-7, Yaskawa Solectria XGI-1500-DCG CRIT-7

Same code in other families

Claims

defined_in

c1 drafted · lead SHPxxx-US-21-BE-en-11

reports

c2 drafted · lead Ground fault alarm or trip

affects

c3 drafted · lead PV array

detected_by

c4 drafted · lead Insulation resistance testing

c5 drafted · lead Open-circuit voltage measurement

c6 verified · fact Grid voltage measurement

verified by: review-workflowverified on: 2026-10-23

c7 drafted · lead Visual inspection

c8 drafted · lead Infrared thermography

review note: support check: partial - IR camera is mentioned only as a tip for support, not as a definite detection method.

mitigated_by

c9 drafted · lead Grounding conductor check

c10 drafted · lead DC wiring check

has_event_class

c11 drafted · lead Fault (device stops or needs intervention)

review note: support check: partial - Describes an insulation error with auto reconnect; fault class is only loosely implied, not stated.

has_production_effect

c12 drafted · lead Trip (production stops)

Momentary insulation error; inverter disconnects and reconnects.

review note: support check: partial - The inverter reconnects implying it disconnected, but disconnecting is not explicitly stated.

has_recovery

c13 drafted · lead Auto-reset (clears by itself)

Reconnects once values return to permissible range.

applies_to

c14 drafted · lead Sunny Highpower PEAK3

Data