Symptom
AC disconnect open
- ID
symptom:ac-disconnect-open
- IRI
https://solarlattice.org/kb/symptom/ac-disconnect-open
- Status
- active
- Also known as
- AC disconnection unit is open, AC service disconnect switch
This symptom means the AC disconnection unit between the inverter and the grid is open, either because it was opened or because it tripped. On SMA Sunny Central CP XT inverters it is reported as error 7706, and the manual's corrective measure is to contact the SMA Service Line. Check the central switch indicator first: position B means the unit tripped and is open, and position C means the switch is in the off position. On the display, an open-switch symbol between the inverter data and AC side symbols means the AC contactor is open, while the same symbol on the DC side means the DC switchgear is open. Before treating it as a fault, confirm the disconnect was not left open on purpose after lockout and tagout for service or inspection. If the inverter enclosure is not level, the mechanism of an optional AC disconnect or breaker can be damaged, so check that the doors line up.
<!-- review notes
- sentence 1: support check: partial - Open or tripped is stated, but 'between the inverter and the grid' location is not in the passages.
- sentence 3: support check: partial - Positions B and C meanings are stated, but 'check first' ordering is not, and C is described as the AC disconnection unit open, which matches off-position.
- sentence 5: support check: partial - Passages show lockout/tagout procedures with AC disconnect opened for service, but do not state to confirm the disconnect wasn't left open on purpose before treating as a fault.
- sentence 1: review: partial - The passages say the AC disconnection unit is open or tripped, but none of them places it between the inverter and the grid.
-->
Claims
observed_as
c1 drafted · lead
AC disconnect open position
On the Sunny Central CP XT, the central switch indicator shows position B when the AC disconnection unit tripped and is open, and position C (switch off) when it is open.
c2 verified · fact
Inverter fault code display
SMA Sunny Central CP XT reports error 7706 when the AC disconnection unit is open or has tripped. The corrective measure is to contact the SMA Service Line.
verified by: review-workflowverified on: 2026-10-23