Symptom

Parameter change rejected

ID
symptom:parameter-change-rejected
IRI
https://solarlattice.org/kb/symptom/parameter-change-rejected
Status
active
Also known as
Grid parameter unchanged, Grid parameters locked, Grid parameter locked, Parameter setting failed, Grid parameters unchanged

The inverter refuses a parameter change and logs an event saying the grid parameters cannot be changed or are locked, or that a parameter setting failed. On SMA string inverters this shows up as event 29004, 9003 or 9005 in the event log or user interface. Event 9005 can mean three things: the rotary switch position for the country setting is not programmed, the parameters are protected, or the DC input voltage is too low to run the main computer. Event 9003 means the grid parameters are now locked, so you must log in with the SMA Grid Guard code before you can change them. If the Grid Guard code you enter is wrong, the parameters stay protected and the change is still rejected. When a single parameter setting fails, check that the new value is within the allowed thresholds, then try the change again. Check first that the country data set is configured correctly, that the Grid Guard code has been entered, and that there is enough DC voltage, shown by the green LED glowing or flashing.

<!-- review notes

Claims

observed_as

c1 drafted · lead Inverter fault code display

SMA events 29004 (grid parameter unchanged), 9003 (grid parameters locked) and 9005 (grid parameters cannot be changed) appear in the inverter event log.

c2 drafted · lead Parameter setting failed event

SMA events 10101 and 10103 report that the displayed parameter was not changed. Event 7105 reports that parameters could not be set from the memory card.

Referenced by

Data