Parameter setting failed event
The inverter writes an event to its log saying a parameter could not be set, and the displayed parameter keeps its previous value. Events 10101 and 10103 mean the requested value was rejected; check that the value is within the parameter's allowed thresholds, then enter the change again. Event 10121 means the device has to be stopped before the parameter can be changed. Event 10122 means the installation assistant must be started before the setting can be applied. Event 7105 is logged when parameters could not be loaded from the memory card; for grid-relevant parameters, make sure the SMA Grid Guard code is available. A successful change is logged as event 27103, which confirms the new value was adopted, so use it to check that a retry worked.