This event occurs in multi-device Sunny Island setups where a slave unit does not receive the synchronization pulse it needs. The display shows F783 when the sync pulse is missing at the master on L1, and W784, W785 or W786 when slave 1, 2 or 3 misses it. F783 is a level 2 event, while the slave messages W784 to W786 are level 1 warnings. The event names (CANCom, CANComSlv1, CANComSlv2) point to the internal communication link between the devices. Check first that the communication cables are undamaged CAT5e and plugged in correctly. Then confirm that the communication bus has a terminator at both ends. Yaskawa Solectria SGI XTM central inverters log similar faults when a follower loses CAN or fast-loop synchronization, or when a master/slave synchronization message fails.