Solar Lattice

Symptom

String reverse current

ID
symptom:string-reverse-current
IRI
https://solarlattice.org/kb/symptom/string-reverse-current
Status
active
Also known as
String Current Reflux, Reve-DC

Sungrow lists four things to check: a string with fewer modules than the others, shading on the string, an abnormal open-circuit voltage or wiring fault, and modules facing the wrong way. Solis gives two causes for its matching reverse DC alarm: a string connected with reversed polarity, or string inputs with different numbers of modules. Find reverse polarity first. With a meter, a reversed string shows a negative voltage. In a combiner box, a reversed string reads about twice the system voltage between string positives where good strings read near zero. If polarity is correct, count the modules in each string and compare. Then look for shading or modules mounted at the wrong orientation. Only open the DC switch to fix wiring or configuration once the string current has fallen below 0.5 A, for example at night or when irradiance is low. The SG250HX monitors current on each string, so the affected input can be found by comparing it against the other strings in the monitoring data.