Fault codes › SMA › Sunny Tripower CORE1-US (STP 33/50/62-US-41)
Reports communication loss; do: network load reduction.
Failure modes that present as the reported condition, and the tests that tell them apart.
| Tell apart | By | How |
|---|---|---|
| Device firmware defect vs Monitoring network configuration fault drafted · lead | Communication test proposed | Switch the Modbus TCP server parameter off and back on. If communication returns, the problem is limited to Modbus TCP. If it stays down, check the network cabling and RJ45 connections. |
sec=h296 h=c86593bb9e0csec=h297 h=059ce03933b4sec=h213 h=c86593bb9e0csec=h214 h=059ce03933b4sec=h298 h=c86593bb9e0csec=h299 h=059ce03933b4The manufacturer's own cause and corrective text is not reproduced here.