A signal processor reset is reported by SMA Sunny Island battery inverters when the device detects that a digital signal processor (DSP) has restarted. If the reset happens in the device at L1 (the master), it is logged as error F702 (RsDsp) at level 5. If it happens in a slave device, it is logged as a level 1 warning: W791 for slave 1, W792 for slave 2 and W793 for slave 3. Check the code first to see which device in the cluster reset, the master or a particular slave. A separate warning, W705, means the watchdog of the master's signal processor has tripped. Check whether it was logged too. The manual's only corrective action for these events is to contact SMA Service.