ABB / FIMER fault codes

FIMER PVS-166/175-TL-US

CodeShown asClassProductionClearsReportsPage
E001Input OC fault DC overcurrent 139
E002Input OV fault stops DC overvoltage 139
E003No pars (DSP) fault after a manual reset Internal communication failure 139
E004Bulk OV fault stops by itself DC bus overvoltage 139
E005Internal error fault after a manual reset Internal communication failure 140
E006Output OC fault after a manual reset AC overcurrent 140
E007IGBT Sat fault stops by itself Power switch saturation 140
E009Internal error fault after a manual reset Internal device fault 140
E010Bulk UV fault DC bus undervoltage 140
E011Ramp Fault fault after a manual reset Boost converter startup timeout 140
E012Internal error fault after a manual reset Internal device fault 140
E014Over temp. fault by itself Inverter overtemperature 140
E015Cap. Fault fault after a manual reset 140
E016Internal error fault after a manual reset 140
E017Internal error fault Inverter startup timeout, Insufficient DC input power 141
E018Leak fault fault High leakage current, Ground fault alarm or trip 141
E019Internal error fault stops after a manual reset Self-test failure 141
E020Internal error fault stops after a manual reset Self-test failure 141
E021Internal error fault stops after a manual reset Self-test failure 141
E022Internal error fault after a manual reset Self-test failure 141
E023DC injection fault by itself High DC injection 141
E024Internal error fault after a manual reset Internal device fault 142
E025Riso Low fault stops Low insulation resistance 142
E026Internal error fault after a manual reset Reference voltage out of tolerance 142
E027Internal error fault after a manual reset AC voltage measurement mismatch 142
E028Internal error fault after a manual reset Grid frequency measurement error 142
E029Mid Bulk OV fault after a manual reset DC bus overvoltage 142
E030Internal error fault after a manual reset Leakage current measurement error 142
E031Internal error fault after a manual reset Relay voltage mismatch 142
E032Internal error fault after a manual reset Phase imbalance 142
E033Undertemper. fault by itself Inverter undertemperature 142
E034IGBT not ready fault after a manual reset Internal device fault 143
E035Remote Off fault stops after a manual reset Remote shutdown 143
E036Internal error fault reduced Grid overvoltage, High grid impedance 143
E037Riso Low fault Low insulation resistance 143
E046Str. test failed fault after a manual reset Reverse polarity 143
E049Internal error fault after a manual reset Internal device fault 143
E050AFDD Activated fault stops after a manual reset Arc fault detected 143
E051Safety mem. Fault fault after a manual reset Internal memory error 143
E053AFDD Fault fault after a manual reset Self-test failure 143
E054AFDD comm. Fault fault after a manual reset Internal communication failure 144
E055AFDD wrong conf. fault after a manual reset Configuration error 144
E057Vbulk reading fault DC overvoltage 144
E058Internal error fault after a manual reset AC DC power deviation 144
E074Internal error fault after a manual reset Internal communication failure 144
E077Internal Error fault after a manual reset Configuration error 144
E078Riso Test fail fault after a manual reset Self-test failure 144
E079Wrong Sequence fault Incorrect phase sequence 144
E084BackFeed OC fault after a manual reset String reverse current 144
W001Sun Low warning Insufficient solar irradiance, DC undervoltage 136
W002Input UV warning Insufficient solar irradiance, DC undervoltage 136
W003Grid Fail warning Grid parameters out of range, Grid instability 137
W004Grid OV warning Grid overvoltage 137
W005Grid UV warning Grid undervoltage 137
W006Grid OF warning Grid overfrequency 137
W007Grid UF warning Grid underfrequency 137
W011Bulk UV warning DC bus undervoltage 137
W012Batt. Low warning Clock backup battery low 138
W013Clock Fail warning Inaccurate clock time 138
W015Island Detect. warning stops after a manual reset Islanding detected 138
W018DC SPD tripped warning needs service Surge protector alarm 138
W019AC SPD tripped warning needs service Surge protector alarm 138
W021P-reduction Star t warning reduced Inverter power derating 138
W022Q-mode Change warning unaffected Reactive power mode change 138
W023Date/time mod. warning unaffected Clock time changed 138
W024Energy data rst warning unaffected Energy counter reset 138
W025P-reduction End warning unaffected Power limitation ended 138
W026AFDD user reset warning unaffected Arc fault alarm reset 138
W046Grid conn. fault warning stops by itself Grid connection failure 139
W047Update Incomplete warning Firmware update failure 139
W048Periodic GridOff warning stops by itself Scheduled periodic grid disconnection 139
W049Global-Settings Event warning unaffected Grid standard changed 139
W058System Frozen warning stops Operation inhibited 139

FIMER PVS-60-TL-US

CodeShown asClassProductionClearsReportsPage
CODE:00 reduced User-set power limitation 160
CODE:01 reduced Grid overfrequency 160
CODE:02 warning reduced Grid overvoltage 160
CODE:03 warning reduced Islanding detected 160
CODE:04 warning reduced Grid undervoltage 160
CODE:05 warning reduced by itself Inverter overtemperature 161
CODE:06 warning reduced DC overvoltage 161
E001Input OC fault DC overcurrent 154
E002Input OV fault stops DC overvoltage 154
E003No Parameters fault after a manual reset Internal communication failure 155
E004Bulk OV fault stops by itself DC bus overvoltage 155
E005Comm.Error fault after a manual reset Internal communication failure 155
E006Output OC fault after a manual reset AC overcurrent 155
E007IGBT Sat fault stops by itself Power switch saturation 155
E009Internal error fault after a manual reset Internal device fault 155
E010Bulk Low fault DC bus undervoltage 155
E011Ramp Fail fault after a manual reset Boost converter startup timeout 155
E012DcDc Fail fault after a manual reset Internal device fault 155
E013Wrong Mode fault Configuration error 155
E014Over Temp. fault by itself Inverter overtemperature 156
E015Bulk Cap Fail fault after a manual reset 156
E016Inverter Fail fault after a manual reset 156
E017Start Timeout fault Inverter startup timeout, Insufficient DC input power 156
E018Ground Fault fault High leakage current, Ground fault alarm or trip 156
E019Ileak sense.fail fault stops after a manual reset Self-test failure 156
E020Self Test Error 1 fault stops after a manual reset Self-test failure 156
E021Self Test Error 2 fault stops after a manual reset Self-test failure 156
E022Self Test Error 4 fault after a manual reset Self-test failure 156
E023DC in error fault by itself High DC injection 157
E024Internal error fault after a manual reset Internal device fault 157
E025Riso Low fault stops Low insulation resistance 157
E026Vref Error fault after a manual reset Reference voltage out of tolerance 157
E027Error Meas V fault after a manual reset AC voltage measurement mismatch 157
E028Error Meas F fault after a manual reset Grid frequency measurement error 157
E029Mid Bulk OV fault after a manual reset DC bus overvoltage 157
E030Error Meas Ileak fault after a manual reset Leakage current measurement error 157
E031Error Read V fault after a manual reset Relay voltage mismatch 157
E032Error Read I fault after a manual reset Phase imbalance 157
E033UTH fault by itself Inverter undertemperature 158
E034Interlock fail fault after a manual reset Internal device fault 158
E035Remote Off fault stops after a manual reset Remote shutdown 158
E036Vout Avg error fault reduced Grid overvoltage, High grid impedance 158
E037Riso Low fault Low insulation resistance 158
E046String self test fail fault after a manual reset Reverse polarity 158
E049AC FF Error fault after a manual reset Internal device fault 158
E050AFDD Activated fault stops after a manual reset Arc fault detected 158
E051Safety mem. Fault fault after a manual reset Internal memory error 158
E053AFDD Fault fault after a manual reset Self-test failure 158
E054AFDD comm. Fault fault after a manual reset Internal communication failure 158
E055AFDD wrong conf. fault after a manual reset Configuration error 158
E056Over Temp. (from external box) fault by itself Inverter overtemperature 159
E057Vbulk reading error fault DC overvoltage 159
E058Pin vs Pout check error fault after a manual reset AC DC power deviation 159
E074Internal error fault after a manual reset Internal communication failure 159
E077Internal Error fault after a manual reset Configuration error 159
E078Riso Test fail fault after a manual reset Self-test failure 159
E079Wrong Sequence fault Incorrect phase sequence 159
E081Internal Error fault after a manual reset Internal device fault 159
E084BackFeed OC fault after a manual reset String reverse current 159
E103RSD self-test fault fault after a manual reset Rapid shutdown failure, Self-test failure 159
W001Sun Low warning Insufficient solar irradiance, DC undervoltage 151
W002Input UV warning Insufficient solar irradiance, DC undervoltage 151
W003Grid Fail warning Grid parameters out of range, Grid instability 152
W004Grid OV warning Grid overvoltage 152
W005Grid UV warning Grid undervoltage 152
W006Grid OF warning Grid overfrequency 152
W007Grid UF warning Grid underfrequency 152
W010Fan Fail warning needs service Fan fault alarm 152
W011Bulk UV warning DC bus undervoltage 152
W012Batt. Low warning Clock backup battery low 153
W013Clock Fail warning Inaccurate clock time 153
W015Island Detect. warning stops after a manual reset Islanding detected 153
W017String Err. warning String current measurement error 153
W018SPD DC Err warning needs service Surge protector alarm 153
W019SPD AC Err warning needs service Surge protector alarm 153
W021P-reductionStart warning reduced Inverter power derating 153
W022Reactive power mode changed warning unaffected Reactive power mode change 153
W023date/time changed warning unaffected Clock time changed 153
W024Energy data reset warning unaffected Energy counter reset 153
W025P-reductionEnd warning unaffected Power limitation ended 154
W026AFDD user reset warning unaffected Arc fault alarm reset 154
W027Latch-Manual reset warning unaffected Latched alarm reset 154
W030Energy Meter ER- ROR warning Communication loss 154
W045Sys disconnected warning stops Low battery state of charge 154
W046Grid conn. fault warning stops by itself Grid connection failure 154
W047Update Incomplete warning Firmware update failure 154
W048Periodic GridOff warning stops by itself Scheduled periodic grid disconnection 154
W049Global-Settings Event warning unaffected Grid standard changed 154
W058System Frozen warning stops Operation inhibited 154

TRIO-20.0/27.6-TL-OUTD(-US)

CodeShown asClassProductionClearsReportsPage
CODE:00 reduced User-set power limitation 114
CODE:01 reduced Grid overfrequency 114
CODE:02 warning reduced Grid overvoltage 114
CODE:03 warning reduced Islanding detected 115
CODE:04 warning reduced Grid undervoltage 115
CODE:05 warning reduced by itself Inverter overtemperature 115
CODE:06 warning reduced DC overvoltage 115
E001Input OC fault DC overcurrent 110
E002Input OV fault stops DC overvoltage 110
E003No Parameters fault after a manual reset Internal communication failure 110
E004Bulk OV fault stops by itself DC bus overvoltage 110
E005Comm.Error fault after a manual reset Internal communication failure 110
E006Output OC fault after a manual reset AC overcurrent 110
E007IGBT Sat fault stops by itself Power switch saturation 110
E009Internal error fault after a manual reset Internal device fault 110
E010Bulk Low fault DC bus undervoltage 110
E011Ramp Fail fault after a manual reset Boost converter startup timeout 110
E012DcDc Fail fault after a manual reset Internal device fault 110
E013Wrong Mode fault Configuration error 111
E014Over Temp. fault by itself Inverter overtemperature 111
E015Bulk Cap Fail fault after a manual reset 111
E016Inverter Fail fault after a manual reset 111
E017Start Timeout fault Inverter startup timeout, Insufficient DC input power 111
E018Ground Fault fault High leakage current, Ground fault alarm or trip 111
E019Ileak sense.fail fault stops after a manual reset Self-test failure 111
E020Self Test Error 1 fault stops after a manual reset Self-test failure 111
E021Self Test Error 2 fault stops after a manual reset Self-test failure 112
E022Self Test Error 4 fault after a manual reset Self-test failure 112
E023DC in error fault by itself High DC injection 112
E024Internal error fault after a manual reset Internal device fault 112
E025Riso Low fault stops Low insulation resistance 112
E026Vref Error fault after a manual reset Reference voltage out of tolerance 112
E027Error Meas V fault after a manual reset AC voltage measurement mismatch 112
E028Error Meas F fault after a manual reset Grid frequency measurement error 112
E029Mid Bulk OV fault after a manual reset DC bus overvoltage 112
E030Error Meas Ileak fault after a manual reset Leakage current measurement error 113
E031Error Read V fault after a manual reset Relay voltage mismatch 113
E032Error Read I fault after a manual reset Phase imbalance 113
E033UTH fault by itself Inverter undertemperature 113
E034Interlock fail fault after a manual reset Internal device fault 113
E035Remote Off fault stops after a manual reset Remote shutdown 113
E036Vout Avg error fault reduced Grid overvoltage, High grid impedance 113
E037Riso Low fault Low insulation resistance 113
E046String self test fail fault after a manual reset Reverse polarity 113
E049AC FF Error fault after a manual reset Internal device fault 113
E056Over Temp. external box) fault by itself Inverter overtemperature 114
E057Vbulk reading error fault DC overvoltage 114
E058Pin vs Pout check error fault after a manual reset AC DC power deviation 114
W001Sun Low warning Insufficient solar irradiance, DC undervoltage 108
W002Input UV warning Insufficient solar irradiance, DC undervoltage 108
W003Grid Fail warning Grid parameters out of range, Grid instability 108
W009Empty Table warning needs service Configuration error 108
W010Fan broken! warning needs service Fan fault alarm 109
W011Bulk UV warning DC bus undervoltage 109
W012Batt. Flat warning Clock backup battery low 109
W013Clock broken warning Inaccurate clock time 109
W017String Err. warning String current measurement error 109
W018SPD DC Err warning needs service Surge protector alarm 109
W019SPD AC Err warning needs service Surge protector alarm 109
W022 warning unaffected Reactive power mode change 109
W023date/time changed warning unaffected Clock time changed 109
W024 warning unaffected Energy counter reset 109

UNO-DM-3.3/3.8/4.6/5.0-TL-PLUS-US

CodeShown asClassProductionClearsReportsPage
CODE:00 reduced User-set power limitation 143
CODE:01 reduced Grid overfrequency 143
CODE:02 warning reduced Grid overvoltage 143
CODE:03 warning reduced Islanding detected 143
CODE:04 warning reduced Grid undervoltage 143
CODE:05 warning reduced by itself Inverter overtemperature 144
CODE:06 warning reduced DC overvoltage 144
E001Input OC fault DC overcurrent 128
E002Input OV fault stops DC overvoltage 128
E003No Parameters fault after a manual reset Internal communication failure 128
E004Bulk OV fault stops by itself DC bus overvoltage 128
E005Comm.Error fault after a manual reset Internal communication failure 128
E006Output OC fault after a manual reset AC overcurrent 128
E007IGBT Sat fault stops by itself Power switch saturation 129
E009Internal error fault after a manual reset Internal device fault 129
E010Bulk Low fault DC bus undervoltage 129
E011Ramp Fail fault after a manual reset Boost converter startup timeout 129
E012DcDc Fail fault after a manual reset Internal device fault 129
E013Wrong Mode fault Configuration error 129
E014Over Temp. fault by itself Inverter overtemperature 129
E015Bulk Cap Fail fault after a manual reset 129
E016Inverter Fail fault after a manual reset 129
E017Start Timeout fault Inverter startup timeout, Insufficient DC input power 129
E018Ground Fault fault High leakage current, Ground fault alarm or trip 129
E019Ileak sense.fail fault stops after a manual reset Self-test failure 130
E020Self Test Error 1 fault stops after a manual reset Self-test failure 130
E021Self Test Error 2 fault stops after a manual reset Self-test failure 130
E022Self Test Error 4 fault after a manual reset Self-test failure 130
E023DC in error fault by itself High DC injection 130
E024Internal error fault after a manual reset Internal device fault 130
E025Riso Low fault stops Low insulation resistance 130
E026Vref Error fault after a manual reset Reference voltage out of tolerance 130
E027Error Meas V fault after a manual reset AC voltage measurement mismatch 130
E028Error Meas F fault after a manual reset Grid frequency measurement error 131
E029Mid Bulk OV fault after a manual reset DC bus overvoltage 131
E030Error Meas Ileak fault after a manual reset Leakage current measurement error 131
E031Error Read V fault after a manual reset Relay voltage mismatch 131
E032Error Read I fault after a manual reset Phase imbalance 131
E033UTH fault by itself Inverter undertemperature 131
E034Interlock fail fault after a manual reset Internal device fault 131
E035Remote Off fault stops after a manual reset Remote shutdown 131
E036Vout Avg error fault reduced Grid overvoltage, High grid impedance 131
E046String self test fail fault after a manual reset Reverse polarity 131
E049AC FF Error fault after a manual reset Internal device fault 131
E050AFDD Activated fault stops after a manual reset Arc fault detected 131
E053AFDD Fault fault after a manual reset Self-test failure 131
E054AFDD comm. Fault fault after a manual reset Internal communication failure 131
E055AFDD wrong conf. fault after a manual reset Configuration error 132
E056Over Temp. (from external box) fault by itself Inverter overtemperature 132
E057Vbulk reading error fault DC overvoltage 132
E058Pin vs Pout check error fault after a manual reset AC DC power deviation 132
E077Internal Error fault after a manual reset Configuration error 132
E078Riso Test fail fault after a manual reset Self-test failure 132
E079Wrong Sequence fault Incorrect phase sequence 132
E081Internal Error fault after a manual reset Internal device fault 142
E084BackFeed OC fault after a manual reset String reverse current 132
E089Wrong Wiring fault 142
W001Sun Low warning Insufficient solar irradiance, DC undervoltage 125
W002Input UV warning Insufficient solar irradiance, DC undervoltage 125
W003Grid Fail warning Grid parameters out of range, Grid instability 126
W004Grid OV warning Grid overvoltage 126
W005Grid UV warning Grid undervoltage 126
W006Grid OF warning Grid overfrequency 126
W007Grid UF warning Grid underfrequency 126
W010Fan Fail warning needs service Fan fault alarm 126
W011Bulk UV warning DC bus undervoltage 127
W012Batt. Low warning Clock backup battery low 127
W013Clock Fail warning Inaccurate clock time 127
W015Island Detect. warning stops after a manual reset Islanding detected 127
W017String Err. warning String current measurement error 127
W018SPD DC Err warning needs service Surge protector alarm 127
W019SPD AC Err warning needs service Surge protector alarm 127
W022Reactive power mode changed warning unaffected Reactive power mode change 127
W023date/time changed warning unaffected Clock time changed 127
W024Energy data reset warning unaffected Energy counter reset 127
W026AFDD user reset warning unaffected Arc fault alarm reset 127
W027Latch-Manual reset warning unaffected Latched alarm reset 128
W046Grid conn. fault warning stops by itself Grid connection failure 128
W047Update Incomplete warning Firmware update failure 128
W048Periodic GridOff warning stops by itself Scheduled periodic grid disconnection 128
W049Global-Settings Event warning unaffected Grid standard changed 128
W058System Frozen warning stops Operation inhibited 128

UNO-DM-6.0-TL-PLUS-US

CodeShown asClassProductionClearsReportsPage
CODE:00 reduced User-set power limitation 142
CODE:01 reduced Grid overfrequency 142
CODE:02 warning reduced Grid overvoltage 142
CODE:03 warning reduced Islanding detected 142
CODE:04 warning reduced Grid undervoltage 142
CODE:05 warning reduced by itself Inverter overtemperature 143
CODE:06 warning reduced DC overvoltage 143
E001Input OC fault DC overcurrent 124
E002Input OV fault stops DC overvoltage 124
E003No Parameters fault after a manual reset Internal communication failure 124
E004Bulk OV fault stops by itself DC bus overvoltage 124
E005Comm.Error fault after a manual reset Internal communication failure 124
E006Output OC fault after a manual reset AC overcurrent 124
E007IGBT Sat fault stops by itself Power switch saturation 125
E009Internal error fault after a manual reset Internal device fault 125
E010Bulk Low fault DC bus undervoltage 125
E011Ramp Fail fault after a manual reset Boost converter startup timeout 125
E012DcDc Fail fault after a manual reset Internal device fault 125
E013Wrong Mode fault Configuration error 125
E014Over Temp. fault by itself Inverter overtemperature 125
E015Bulk Cap Fail fault after a manual reset 125
E016Inverter Fail fault after a manual reset 125
E017Start Timeout fault Inverter startup timeout, Insufficient DC input power 125
E018Ground Fault fault High leakage current, Ground fault alarm or trip 125
E019Ileak sense.fail fault stops after a manual reset Self-test failure 126
E020Self Test Error 1 fault stops after a manual reset Self-test failure 126
E021Self Test Error 2 fault stops after a manual reset Self-test failure 126
E022Self Test Error 4 fault after a manual reset Self-test failure 126
E023DC in error fault by itself High DC injection 126
E024Internal error fault after a manual reset Internal device fault 126
E025Riso Low fault stops Low insulation resistance 126
E026Vref Error fault after a manual reset Reference voltage out of tolerance 126
E027Error Meas V fault after a manual reset AC voltage measurement mismatch 126
E028Error Meas F fault after a manual reset Grid frequency measurement error 127
E029Mid Bulk OV fault after a manual reset DC bus overvoltage 127
E030Error Meas Ileak fault after a manual reset Leakage current measurement error 127
E031Error Read V fault after a manual reset Relay voltage mismatch 127
E032Error Read I fault after a manual reset Phase imbalance 127
E033UTH fault by itself Inverter undertemperature 127
E034Interlock fail fault after a manual reset Internal device fault 127
E035Remote Off fault stops after a manual reset Remote shutdown 127
E036Vout Avg error fault reduced Grid overvoltage, High grid impedance 127
E046String self test fail fault after a manual reset Reverse polarity 127
E049AC FF Error fault after a manual reset Internal device fault 127
E050AFDD Activated fault stops after a manual reset Arc fault detected 127
E053AFDD Fault fault after a manual reset Self-test failure 127
E054AFDD comm. Fault fault after a manual reset Internal communication failure 127
E055AFDD wrong conf. fault after a manual reset Configuration error 128
E056Over Temp. (from external box) fault by itself Inverter overtemperature 128
E057Vbulk reading error fault DC overvoltage 128
E058Pin vs Pout check error fault after a manual reset AC DC power deviation 128
E077Internal Error fault after a manual reset Configuration error 128
E078Riso Test fail fault after a manual reset Self-test failure 128
E079Wrong Sequence fault Incorrect phase sequence 128
E081Internal Error fault after a manual reset Internal device fault 141
E084BackFeed OC fault after a manual reset String reverse current 128
E089Wrong Wiring fault 141
W001Sun Low warning Insufficient solar irradiance, DC undervoltage 121
W002Input UV warning Insufficient solar irradiance, DC undervoltage 121
W003Grid Fail warning Grid parameters out of range, Grid instability 122
W004Grid OV warning Grid overvoltage 122
W005Grid UV warning Grid undervoltage 122
W006Grid OF warning Grid overfrequency 122
W007Grid UF warning Grid underfrequency 122
W010Fan Fail warning needs service Fan fault alarm 122
W011Bulk UV warning DC bus undervoltage 123
W012Batt. Low warning Clock backup battery low 123
W013Clock Fail warning Inaccurate clock time 123
W015Island Detect. warning stops after a manual reset Islanding detected 123
W017String Err. warning String current measurement error 123
W018SPD DC Err warning needs service Surge protector alarm 123
W019SPD AC Err warning needs service Surge protector alarm 123
W022Reactive power mode changed warning unaffected Reactive power mode change 123
W023date/time changed warning unaffected Clock time changed 123
W024Energy data reset warning unaffected Energy counter reset 123
W026AFDD user reset warning unaffected Arc fault alarm reset 123
W027Latch-Manual reset warning unaffected Latched alarm reset 124
W046Grid conn. fault warning stops by itself Grid connection failure 124
W047Update Incomplete warning Firmware update failure 124
W048Periodic GridOff warning stops by itself Scheduled periodic grid disconnection 124
W049Global-Settings Event warning unaffected Grid standard changed 124
W058System Frozen warning stops Operation inhibited 124