Solar Lattice

Symptom

Grid frequency measurement error

ID
symptom:grid-frequency-measurement-error
IRI
https://solarlattice.org/kb/symptom/grid-frequency-measurement-error
Status
active
Also known as
Error Meas F, Internal error

The inverter reports code E028 on its display, shown as Error Meas F or Internal error, together with the yellow LED or the alarm LED. The code means the inverter's own grid frequency measurement failed. Regulations require two separate circuits to measure frequency for redundancy, and the error is tied to this check. The manuals say this is an error inside the inverter that cannot be checked from outside. The cause is in the inverter's measurement electronics, not in the grid itself. Do not confuse it with a grid over-frequency alarm. There, the grid frequency itself goes above the limit set by the operator, and you can check it both on the inverter and at the supply. For other brands' frequency alarms, the manuals say to measure frequency at the inverter test points and compare it with the display reading. A display reading that differs from the measurement may point to a bad measurement circuit. First, switch the inverter off and back on. If E028 comes back, contact customer assistance. A matching code, E027 (Error Meas V), covers the same redundant-measurement fault for grid voltage.

<!-- review notes

Claims

observed_as

c1 verified · fact Inverter fault code display

ABB/FIMER inverters show code E028 on the display, labelled Error Meas F or Internal error.

verified by: review-workflowverified on: 2026-10-23