Arc fault alarm reset

ID
symptom:arc-fault-reset
IRI
https://solarlattice.org/kb/symptom/arc-fault-reset
Status
active
Also known as
AFDD user reset, Reset AFD

This warning records that a customer or installer manually cleared an arc fault error. The manufacturer says it is not an error in itself. It does not light any LED and is kept only in the inverter's event history, so look for it in the event log rather than on the front panel. Depending on the model, the reset is done with a button on the DC wiring box, the internal webserver, the display menu or the configuration software. Each reset means an arc fault came before it. That fault showed as the red GFI and ALARM LEDs on, with POWER off and the inverter disconnected from the grid. If the inverter reconnects normally after the reset, the arc was probably temporary or intermittent. Arcs are more likely in damp conditions and point to insulation breakdown, so still have the PV plant inspected. If the self-test fails again after the reset, or the inverter will not reconnect, the DC arc fault is still present. Lock out the AC and DC disconnects and get service to repair the array. Repeated reset entries in the log are a reason to check DC cables, connectors and module junction boxes for a recurring arc.

<!-- review notes

Claims

observed_as

c1 verified · fact Arc fault reset event entry

Code W026 (AFDD user reset) is written only to the inverter's event history. No LED shows it, and on some UNO-DM models it does not appear on the display. The reset is done by the customer or installer, through the webserver, the display or the configuration software.

verified by: review-workflowverified on: 2026-10-23review note: support check: partial - W026 is only in event history with no LED and may not show on display, and reset is via webserver/display/software, but the 'UNO-DM' model reference and the event-log measurement mapping are not stated in passages.

c2 drafted · lead AFCI self-test fault result

On UNO-DM models, Reset AFD clears E050 and runs the self-test again. If the DC arc is still present, the self-test ends with E053 instead of reconnecting.

c3 verified · fact Zero inverter AC output

If the inverter does not reconnect after the arc fault is reset, the fault in the PV array is still there and needs service.

verified by: review-workflowverified on: 2026-10-23review note: support check: partial - Passages say that if the inverter does not reconnect, service is needed to repair the array fault, but say nothing about AC output staying at zero with irradiance.

c4 drafted · lead Arc fault alarm

A reset follows an arc fault. Before the reset the red GFI LED and the ALARM LED are on and the POWER LED is off (Arc Fault pending).