KACO new energy fault codes
KACO blueplanet 87.0-165 TL3
| Code | Shown as | Class | Production | Clears | Reports | Page |
|---|---|---|---|---|---|---|
| 2 | Insufficient generator voltage / insufficient battery voltage! | DC undervoltage | 100 | |||
| 4 | Feed in at max. MPP | informational | unaffected | 100 | ||
| 8 | Self-test in progress | informational | 100 | |||
| 9 | Test mode | informational | 100 | |||
| 10 | Temperature in device too high | Inverter overtemperature | 101 | |||
| 11 | Power limitation | reduced | Inverter power derating, Inverter overtemperature | 101 | ||
| 17 | HMI1: "Powador-protect dis-connection" HMI2: "External grid protection shutdown" | stops | Grid parameters out of range | 101 | ||
| 18 | Resid. current shutdown (AFI) | stops | High leakage current | 101 | ||
| 20 | Power rampup active | informational | reduced | by itself | Inverter power derating | 101 |
| 31 | AFI module fault | Internal device fault | 101 | |||
| 33 | DC feed-in error | by itself | High DC injection | 101 | ||
| 34 | Internal communication er-ror | Internal communication failure | 102 | |||
| 35 | Protect. shutdown SW | fault | stops | Grid overvoltage, DC bus overvoltage | 102 | |
| 36 | Protection shutdown HW | stops | by itself | AC overcurrent | 102 | |
| 38 | Generator voltage too high / fault: Battery overvoltage | DC overvoltage | 102 | |||
| 41 | Grid failure undervoltage L1 | stops | Grid undervoltage | 102 | ||
| 42 | Grid failure overvoltage L1 | stops | Grid overvoltage | 102 | ||
| 43 | Grid failure undervoltage L2 | stops | Grid undervoltage | 102 | ||
| 44 | Grid failure overvoltage L2 | stops | Grid overvoltage | 102 | ||
| 45 | Grid failure undervoltage L3 | Grid undervoltage | 103 | |||
| 46 | Grid failure overvoltage L3 | Grid overvoltage | 103 | |||
| 47 | Grid failure phase-to-phase voltage | Grid voltage out of range | 103 | |||
| 48 | Grid failure underfrequency | Grid underfrequency | 103 | |||
| 49 | Grid failure overfrequency | Grid overfrequency | 103 | |||
| 50 | Grid failure average voltage | fault | Grid overvoltage | 104 | ||
| 57 | Waiting for reconnect | by itself | 104 | |||
| 58 | Control board overtemp. | stops | Inverter overtemperature | 104 | ||
| 59 | Self test error | fault | needs service | Self-test failure | 104 | |
| 60 | Excessive generator voltage / excessive battery voltage | stops | by itself | DC overvoltage | 104 | |
| 61 | External limit | informational | reduced | Remote power limit | 104 | |
| 62 | Standalone mode | 105 | ||||
| 63 | Frequency-dependent power reduction | reduced | 105 | |||
| 64 | Output current limitation | reduced | Inverter power derating | 105 | ||
| 67 | Fehler Leistungsteil 1 | fault | 105 | |||
| 70 | Fault in fan 1 | reduced to 50 % of rated power | Fan fault alarm | 105 | ||
| 71 | Fault in fan 2 | unaffected | Fan fault alarm | 105 | ||
| 72 | Fault in fan 3 | unaffected | Fan fault alarm | 105 | ||
| 73 | Standalone grid error | fault | stops | Grid loss | 105 | |
| 75 | Self test in progress | informational | 105 | |||
| 78 | Resid. current shutdown (AFI) | fault | stops | High leakage current | 105 | |
| 79 | Insulation measurement | informational | 105 | |||
| 80 | Insulation meas. not pos-sible | fault | PV voltage fluctuation | 106 | ||
| 81 | Protection shutdown grid voltage L1 | fault | stops | Grid overvoltage | 106 | |
| 82 | Protection shutdown grid voltage L2 | fault | stops | Grid overvoltage | 106 | |
| 83 | Protection shutdown grid voltage L3 | fault | stops | Grid overvoltage | 106 | |
| 84 | Protection shutdown DC link undervoltage | fault | stops | DC bus undervoltage | 106 | |
| 85 | Protection shutdown DC link overvoltage | fault | stops | DC bus overvoltage | 106 | |
| 86 | Protect. shutdown unbal. DC link | fault | stops | Neutral point voltage imbalance | 106 | |
| 87 | Protection shutdown over-current L1 | fault | stops | AC overcurrent | 106 | |
| 88 | Protection shutdown over-current L2 | fault | stops | AC overcurrent | 106 | |
| 89 | Protection shutdown over-current L3 | fault | stops | AC overcurrent | 106 | |
| 91 | Protective shutdown drop 2.5 V | fault | stops | 106 | ||
| 97 | Protection shutdown over-current HW | fault | stops | needs service | Inverter overcurrent | 106 |
| 100 | Protection shutdown HW overtemperature | fault | stops | after a manual reset | Inverter overtemperature | 106 |
| 101 | Temperature plausibility er-ror | fault | needs service | Abnormal temperature reading | 107 | |
| 102 | Plausibility fault efficiency | fault | needs service | AC DC power deviation | 107 | |
| 105 | Relay plausibility error | fault | after a manual reset | Relay voltage mismatch | 107 | |
| 107 | Check surge protection device | warning | unaffected | needs service | Surge protector alarm | 107 |
| 108 | Grid failure overvoltage L1 | fault | stops | Grid overvoltage | 107 | |
| 109 | Grid failure overvoltage L2 | Grid overvoltage | 107 | |||
| 110 | Grid failure overvoltage L3 | Grid overvoltage | 107 | |||
| 111 | Grid failure undervoltage L1 | fault | stops | Grid undervoltage | 107 | |
| 112 | Grid failure undervoltage L2 | fault | stops | Grid undervoltage | 107 | |
| 113 | Grid failure undervoltage L3 | fault | stops | Grid undervoltage | 107 | |
| 118 | DC overvoltage 1 | DC overvoltage | 107 | |||
| 119 | DC overvoltage 2 | DC overvoltage | 108 | |||
| 125 | Relay control fault | fault | stops | needs service | Switching device status fault | 108 |
| 128 | Internal memory error 1 | fault | stops | after a manual reset | Internal memory error | 108 |
| 129 | Voltage-dependent power reduction | Inverter power derating | 108 | |||
| 148 | External memory error 1 | after a manual reset | Internal memory error | 108 | ||
| 150 | Protective shutdown drop reference ADC | fault | stops | after a manual reset | Reference voltage out of tolerance | 108 |
| 158 | Power limitation | warning | reduced | Inverter overtemperature | 108 | |
| 159 | Waiting for fault acknow-ledgement | Configuration error | 108 | |||
| 160 | Error: Grid relay L1 | fault | Self-test failure | 108 | ||
| 161 | Error: Grid relay L2 | fault | Self-test failure | 108 | ||
| 162 | Error: Grid relay L3 | fault | Self-test failure | 108 | ||
| 164 | Error: Filter relay L1 | fault | Self-test failure | 108 | ||
| 165 | Error: Filter relay L2 | fault | Self-test failure | 108 | ||
| 166 | Error: Filter relay L3 | Self-test failure | 108 | |||
| 169 | Error: AFI sensor | fault | 108 | |||
| 180 | Pre-synchronisation not pos-sible | fault | stops | after a manual reset | Grid synchronization failure | 108 |
| 181 | Insulation error, centre | fault | Low insulation resistance | 109 | ||
| 182 | Insulation error, minus | Low insulation resistance | 109 | |||
| 183 | Insulation error, plus | Low insulation resistance | 109 | |||
| 184 | Protective shutdown over-current L1 int. | stops | Inverter overcurrent | 109 | ||
| 185 | Protective shutdown over-current L2 int. | stops | Inverter overcurrent | 109 | ||
| 186 | Protective shutdown over-current L3 int. | stops | Inverter overcurrent | 109 | ||
| 187 | Fault in fan 4 | warning | unaffected | Fan fault alarm | 109 | |
| 188 | Semiconductor test not pos-sible | fault | after a manual reset | Self-test failure | 109 | |
| 189 | Semiconductor module 1 in channel A defective | fault | after a manual reset | 109 | ||
| 190 | Semiconductor module 2 in channel A defective | 109 | ||||
| 191 | Semiconductor module 3 in channel A defective | 109 | ||||
| 192 | Semiconductor module 1 in channel B defective | 109 | ||||
| 193 | Semiconductor module 2 in channel B defective | 109 | ||||
| 194 | Semiconductor module 3 in channel B defective | 109 | ||||
| 195 | DESAT error | Internal overcurrent or overvoltage, Driver supply undervoltage | 109 | |||
| 203 | Protection shutdown grid voltage (effective value) L1 | fault | stops | Grid overvoltage | 110 | |
| 204 | Protection shutdown grid voltage (effective value) L2 | fault | stops | Grid overvoltage | 110 | |
| 205 | Protection shutdown grid voltage (effective value) L3 | fault | stops | Grid overvoltage | 110 | |
| 206 | Protection shutdown over-current HW | fault | stops | Inverter overcurrent | 110 | |
| 207 | Detection of hardware de-tection failed: Control card | fault | after a manual reset | Internal memory error | 110 | |
| 208 | Detection of hardware de-tection failed: AC power board | fault | after a manual reset | Internal memory error | 110 | |
| 209 | Detection of hardware de-tection failed: AC relay board | fault | after a manual reset | Internal memory error | 110 | |
| 216 | Protect. shutdown HW - overvoltage DC link halves | fault | stops | after a manual reset | DC bus overvoltage | 110 |
| 217 | Protect. shutdown HW - 24V supply voltage | fault | stops | after a manual reset | Invalid internal supply voltage | 110 |
| 224 | External limitation | informational | reduced | Remote power limit | 110 | |
| 226 | The inverter is disconnected from the grid manually | informational | stops | after a manual reset | Manual grid disconnection | 110 |
| 227 | Protective shutdown current Schutzabschaltung, die bei (hochohmigen) | stops | Phase imbalance | 111 |
Codes are sorted by vendor prefix and number. Each row links to the code's record; concepts link to their reading rule.