KACO new energy fault codes

KACO blueplanet 87.0-165 TL3

CodeShown asClassProductionClearsReportsPage
2Insufficient generator voltage / insufficient battery voltage! DC undervoltage 100
4Feed in at max. MPP informational unaffected 100
8Self-test in progress informational 100
9Test mode informational 100
10Temperature in device too high Inverter overtemperature 101
11Power limitation reduced Inverter power derating, Inverter overtemperature 101
17HMI1: "Powador-protect dis-connection" HMI2: "External grid protection shutdown" stops Grid parameters out of range 101
18Resid. current shutdown (AFI) stops High leakage current 101
20Power rampup active informational reduced by itself Inverter power derating 101
31AFI module fault Internal device fault 101
33DC feed-in error by itself High DC injection 101
34Internal communication er-ror Internal communication failure 102
35Protect. shutdown SW fault stops Grid overvoltage, DC bus overvoltage 102
36Protection shutdown HW stops by itself AC overcurrent 102
38Generator voltage too high / fault: Battery overvoltage DC overvoltage 102
41Grid failure undervoltage L1 stops Grid undervoltage 102
42Grid failure overvoltage L1 stops Grid overvoltage 102
43Grid failure undervoltage L2 stops Grid undervoltage 102
44Grid failure overvoltage L2 stops Grid overvoltage 102
45Grid failure undervoltage L3 Grid undervoltage 103
46Grid failure overvoltage L3 Grid overvoltage 103
47Grid failure phase-to-phase voltage Grid voltage out of range 103
48Grid failure underfrequency Grid underfrequency 103
49Grid failure overfrequency Grid overfrequency 103
50Grid failure average voltage fault Grid overvoltage 104
57Waiting for reconnect by itself 104
58Control board overtemp. stops Inverter overtemperature 104
59Self test error fault needs service Self-test failure 104
60Excessive generator voltage / excessive battery voltage stops by itself DC overvoltage 104
61External limit informational reduced Remote power limit 104
62Standalone mode 105
63Frequency-dependent power reduction reduced 105
64Output current limitation reduced Inverter power derating 105
67Fehler Leistungsteil 1 fault 105
70Fault in fan 1 reduced to 50 % of rated power Fan fault alarm 105
71Fault in fan 2 unaffected Fan fault alarm 105
72Fault in fan 3 unaffected Fan fault alarm 105
73Standalone grid error fault stops Grid loss 105
75Self test in progress informational 105
78Resid. current shutdown (AFI) fault stops High leakage current 105
79Insulation measurement informational 105
80Insulation meas. not pos-sible fault PV voltage fluctuation 106
81Protection shutdown grid voltage L1 fault stops Grid overvoltage 106
82Protection shutdown grid voltage L2 fault stops Grid overvoltage 106
83Protection shutdown grid voltage L3 fault stops Grid overvoltage 106
84Protection shutdown DC link undervoltage fault stops DC bus undervoltage 106
85Protection shutdown DC link overvoltage fault stops DC bus overvoltage 106
86Protect. shutdown unbal. DC link fault stops Neutral point voltage imbalance 106
87Protection shutdown over-current L1 fault stops AC overcurrent 106
88Protection shutdown over-current L2 fault stops AC overcurrent 106
89Protection shutdown over-current L3 fault stops AC overcurrent 106
91Protective shutdown drop 2.5 V fault stops 106
97Protection shutdown over-current HW fault stops needs service Inverter overcurrent 106
100Protection shutdown HW overtemperature fault stops after a manual reset Inverter overtemperature 106
101Temperature plausibility er-ror fault needs service Abnormal temperature reading 107
102Plausibility fault efficiency fault needs service AC DC power deviation 107
105Relay plausibility error fault after a manual reset Relay voltage mismatch 107
107Check surge protection device warning unaffected needs service Surge protector alarm 107
108Grid failure overvoltage L1 fault stops Grid overvoltage 107
109Grid failure overvoltage L2 Grid overvoltage 107
110Grid failure overvoltage L3 Grid overvoltage 107
111Grid failure undervoltage L1 fault stops Grid undervoltage 107
112Grid failure undervoltage L2 fault stops Grid undervoltage 107
113Grid failure undervoltage L3 fault stops Grid undervoltage 107
118DC overvoltage 1 DC overvoltage 107
119DC overvoltage 2 DC overvoltage 108
125Relay control fault fault stops needs service Switching device status fault 108
128Internal memory error 1 fault stops after a manual reset Internal memory error 108
129Voltage-dependent power reduction Inverter power derating 108
148External memory error 1 after a manual reset Internal memory error 108
150Protective shutdown drop reference ADC fault stops after a manual reset Reference voltage out of tolerance 108
158Power limitation warning reduced Inverter overtemperature 108
159Waiting for fault acknow-ledgement Configuration error 108
160Error: Grid relay L1 fault Self-test failure 108
161Error: Grid relay L2 fault Self-test failure 108
162Error: Grid relay L3 fault Self-test failure 108
164Error: Filter relay L1 fault Self-test failure 108
165Error: Filter relay L2 fault Self-test failure 108
166Error: Filter relay L3 Self-test failure 108
169Error: AFI sensor fault 108
180Pre-synchronisation not pos-sible fault stops after a manual reset Grid synchronization failure 108
181Insulation error, centre fault Low insulation resistance 109
182Insulation error, minus Low insulation resistance 109
183Insulation error, plus Low insulation resistance 109
184Protective shutdown over-current L1 int. stops Inverter overcurrent 109
185Protective shutdown over-current L2 int. stops Inverter overcurrent 109
186Protective shutdown over-current L3 int. stops Inverter overcurrent 109
187Fault in fan 4 warning unaffected Fan fault alarm 109
188Semiconductor test not pos-sible fault after a manual reset Self-test failure 109
189Semiconductor module 1 in channel A defective fault after a manual reset 109
190Semiconductor module 2 in channel A defective 109
191Semiconductor module 3 in channel A defective 109
192Semiconductor module 1 in channel B defective 109
193Semiconductor module 2 in channel B defective 109
194Semiconductor module 3 in channel B defective 109
195DESAT error Internal overcurrent or overvoltage, Driver supply undervoltage 109
203Protection shutdown grid voltage (effective value) L1 fault stops Grid overvoltage 110
204Protection shutdown grid voltage (effective value) L2 fault stops Grid overvoltage 110
205Protection shutdown grid voltage (effective value) L3 fault stops Grid overvoltage 110
206Protection shutdown over-current HW fault stops Inverter overcurrent 110
207Detection of hardware de-tection failed: Control card fault after a manual reset Internal memory error 110
208Detection of hardware de-tection failed: AC power board fault after a manual reset Internal memory error 110
209Detection of hardware de-tection failed: AC relay board fault after a manual reset Internal memory error 110
216Protect. shutdown HW - overvoltage DC link halves fault stops after a manual reset DC bus overvoltage 110
217Protect. shutdown HW - 24V supply voltage fault stops after a manual reset Invalid internal supply voltage 110
224External limitation informational reduced Remote power limit 110
226The inverter is disconnected from the grid manually informational stops after a manual reset Manual grid disconnection 110
227Protective shutdown current Schutzabschaltung, die bei (hochohmigen) stops Phase imbalance 111

Codes are sorted by vendor prefix and number. Each row links to the code's record; concepts link to their reading rule.