DC arc-fault protection
DC arc-fault protection watches the DC side of the inverter for electrical noise that points to a series arc, then stops the inverter when it finds one. Fronius Arc Guard uses an electronic circuit to check the DC current and voltage for contact errors and shuts the circuit down. This lowers the risk of overheating and fire at poor contact points. The function is required by NEC Article 690.11. Fronius also cites CSA C22.1 Art. 64-216. The CPS and Solectria inverters state compliance with UL 1699B. On the CSI 23/28KTL-CT, an arc trip shows ARC Protect on the LCD and must be cleared by hand. You can run an AFCI Test from the System Setting OtherCmd menu, which ends with TestFinish or AFCI Fault. The ABB UNO-DM inverters self-test the arc detection circuit at every power-up. After an arc trip they stay off the grid until someone presses the reset button on the DC wiring box. Check the DC cables and panels first to find the source of the arc. For the CPS ARC Protect or Arcboard Err alarms, check that the logic connector to the arc board is secure and run the Arc Fault Test. If the alarm comes back, call CPS Service to replace the arc board or the wiring box.
<!-- review notes
- sentence 3: support check: partial - NEC 690.11, CSA 64-216 and UL 1699B compliance are stated, but the passages don't name Solectria, and CPS isn't named either; 'required by NEC' is stated only for the NFPA 70 case, and Fronius brand isn't explicit.
- sentence 5: support check: partial - Self-test at power-up, manual reset, and checking DC cables/panels first are stated, but the passage says the reset button is on the left side and doesn't name ABB UNO-DM (the statement mentions only the DC wiring box, fine); the model name isn't in the passage. -->
Parts
Referenced by
- Series and parallel arc faults
related_toc4 - UNO-DM-3.3/3.8/4.6/5.0-TL-PLUS-US string inverter
implementsc5 - APsmart RSD rapid shutdown system
lacksc10 - CSI 23/28KTL-CT/US-480
implementsc6 - CSI-25/30/36/40K-T480GL01-UB
implementsc4 - CSI-50/60/66K-T480GL01-UB
implementsc4 - CPS SCA25KTL-DO/US-208
implementsc20 - CPS SCA50-60KTL-DO/US-480
implementsc8 - CPS SCH200K-T-US-480 / SCH250K-T-US-600
implementsc6 - Fronius Galvo 208-240
implementsc2 - Fronius Primo GEN24
implementsc1 - Generac PV Link
implementsc5 - Huawei SUN2000-25KTL-US / SUN2000-30KTL-US
implementsc16 - Huawei SUN2000-45KTL-US-HV-D0
implementsc15 - Sunny Tripower CORE1-US
implementsc3 - Sunny Tripower X (international)
implementsc10 - Solis-1P(3.6-10)K-4G-US
implementsc2 - Solis RHI-1P(5-10)K-HVES-5G-US
implementsc14 - Solis S6-EH1P(3.8-11.4)K-H-US
implementsc3 - Solis S6-EH2P(9.6-16)K-SV-YD-L-US
implementsc8 - Solis S6-EH3P(30-60)K-NV-YD-H-US
implementsc3 - Solis S6-EH3P(75-150)K10-NV-YD-H-US
implementsc2 - Solis S6-GU(250-350)K-EHV-US
implementsc2 - Sungrow SG200HX-US
implementsc27 - Solectria PVI 14-20TL
implementsc3 - Solectria PVI 3800-7600TL
implementsc12 - Operation inhibition after arc fault
part_ofc1