The CSI 23/28KTL-CT/US-480 is a Canadian Solar transformerless three-phase string inverter family. It comes in a 23 kW model and a 28 kW model. Both models accept up to 1000 Vdc and have two MPP trackers with four DC inputs each. A load-rated DC switch handles DC disconnection. The MPPT range is 480-800 Vdc on the 23 kW model and 500-800 Vdc on the 28 kW model. Maximum input current per MPPT is 25 A and 29 A. The AC output is 480 Vac, 60 Hz, three-phase with neutral and PE. Maximum output current is 27.7 A on the 23 kW model and 33.7 A on the 28 kW model. Peak efficiency is 98.6 percent and CEC efficiency is 98.0 percent. Power factor can be adjusted, and output derates at high temperature. For communication the inverter uses Modbus over RS485. Firmware can be upgraded from a USB disk through the communication board's USB port. An Arcboard provides arc fault detection. An Arcboard Err fault points to poor contact or damage on that board. Clear it with ARCFaultClear after checking the board.

<!-- review notes

Claims

manufactured_by

c1 drafted · lead Canadian Solar

review note: support check: partial - Evidence is only the bare string 'CanadianSolar', which suggests but does not state the manufacturer relation.

instance_of

c2 drafted · lead Inverter

uses_protocol

c3 drafted · lead Modbus

c4 drafted · lead RS-485

RS485 cable: UTP CAT-5e or 3x #22-18 AWG communication cable, e.g. Belden 3106A.

implements

c5 drafted · lead Maximum power point tracking

Two MPP trackers per model, with four DC inputs on each MPPT.

c6 drafted · lead DC arc-fault protection

Uses an Arcboard; arc faults are cleared with the ARCFaultClear command.

review note: support check: partial - The Arcboard error and ARCFaultClear are in the passage, but it never states that the inverter provides DC arc-fault protection.

c7 drafted · lead Constant power factor mode

Power factor above 0.99, adjustable to plus or minus 0.8.

review note: support check: partial - The table gives a power factor of >0.99 and ±0.8 adjustable, but it does not name a constant power factor mode.; review: partial - The table gives power factor >0.99 and adjustable to ±0.8, which matches the note, but it never names a constant power factor mode.

rated_power

c8 drafted · lead nominal 23 KiloW

Conditions: CSI 23KTL-CT/US-480, rated AC output power

review note: possible conflict with c9 (same source; check the conditions)

c9 drafted · lead nominal 28 KiloW

Conditions: CSI 28KTL-CT/US-480, rated AC output power

review note: possible conflict with c8 (same source; check the conditions)

max_input_voltage

c10 drafted · lead nominal 1000 V

Conditions: Both models, maximum DC input voltage

mppt_voltage_range

c11 drafted · lead 480–800 V

Conditions: CSI 23KTL-CT/US-480

c12 verified · fact 500–800 V

Conditions: CSI 28KTL-CT/US-480

verified by: review-workflowverified on: 2026-10-24

max_input_current

c13 drafted · lead nominal 25 A

Conditions: CSI 23KTL-CT/US-480, per MPPT (Imp); total 50 A

review note: possible conflict with c14 (same source; check the conditions)

c14 drafted · lead nominal 29 A

Conditions: CSI 28KTL-CT/US-480, per MPPT (Imp); total 58 A

review note: possible conflict with c13 (same source; check the conditions)

rated_output_current

c15 drafted · lead nominal 27.7 A

Conditions: CSI 23KTL-CT/US-480, maximum AC output current

review note: possible conflict with c16 (same source; check the conditions)

c16 drafted · lead nominal 33.7 A

Conditions: CSI 28KTL-CT/US-480, maximum AC output current

review note: possible conflict with c15 (same source; check the conditions)

nominal_voltage

c17 drafted · lead nominal 480 V

Conditions: Rated AC output voltage, three-phase with N and PE; output voltage range 422-528 Vac

frequency

c18 drafted · lead nominal 60 HZ

Conditions: Rated output frequency

c19 drafted · lead 59.3–60.5 HZ

Conditions: Output frequency range

efficiency

c20 verified · fact nominal 98.6 PERCENT

Conditions: Maximum (peak) efficiency

verified by: review-workflowverified on: 2026-10-24review note: possible conflict with c21 (same source; check the conditions)

c21 drafted · lead nominal 98 PERCENT

Conditions: CEC weighted efficiency

review note: possible conflict with c20 (same source; check the conditions)