Product
CPS SCA25KTL-DO/US-208
- ID
prod:chint-sca-25ktl-208
- IRI
https://solarlattice.org/kb/prod/chint-sca-25ktl-208
- Status
- active
- Also known as
- SCA 25 KTL DO US 208, SCA25KTL-DO/US-208
- Category
- Inverters
- Make
- chint
- Product level
- family
- Model number
- SCA25KTL-DO/US-208
The CPS SCA25KTL-DO/US-208 is a transformerless three-phase string inverter from CHINT Power Systems, built for 208 VAC grid connections. It takes up to 1000 VDC at the input, runs over a DC operating range of 200-950 VDC and starts at 330 V and 80 W. Its MPPTs can run independently or be combined in parallel. It delivers up to 69.5 A at 208 VAC and 60 Hz, with current THD below 3% and a maximum efficiency of 97%. Its listed smart-grid functions are voltage and frequency ride-through, ramp-rate control, specified power factor, Volt-VAr, Freq-Watt and Volt-Watt. You can select the IEEE 1547a2014, CA Rule 21, ISO-NE or HECO grid standard. It has DC arc-fault protection on an arc board. If you see Arcboard Err or ARC Protect, check that the logic connector to the arc board is secure and run the Arc Fault Test from the Settings menu. It communicates over RS485, and you load firmware upgrades through a USB port.
<!-- review notes
- sentence 1: support check: partial - Transformerless and 208VAC are supported, but 'three-phase', 'string inverter' and the full CHINT name are not stated.
- sentence 6: support check: partial - RS485 is supported; the USB port caption for firmware upgrades supports the USB firmware loading, but only as a figure caption.
- sentence 1: review: partial - The passages support transformerless and 208 VAC, but they never say three-phase, string inverter or CHINT Power Systems.
-->
Claims
manufactured_by
c1 drafted · lead
CHINT POWER SYSTEMS
review note: support check: partial - Model name and 'CPS' appear, but the passages do not state the full manufacturer name CHINT POWER SYSTEMS.
instance_of
c2 drafted · lead
Inverter
Transformerless topology
review note: support check: partial - Transformerless topology is stated, but the passages do not say the device is an inverter explicitly (implied by efficiency spec).
max_input_voltage
c3 drafted · lead
nominal 1000 V
Conditions: Maximum DC input voltage
nominal_voltage
c4 verified · fact
nominal 208 V
Conditions: Rated AC output voltage
verified by: review-workflowverified on: 2026-10-24
rated_output_current
c5 verified · fact
nominal 69.5 A
Conditions: Maximum AC output current at 208 VAC
verified by: review-workflowverified on: 2026-10-24
frequency
c6 verified · fact
nominal 60 HZ
Conditions: Rated output frequency
verified by: review-workflowverified on: 2026-10-24
efficiency
c7 drafted · lead
nominal 97 PERCENT
Conditions: Maximum efficiency, transformerless topology
certified_to
c8 drafted · lead
UL 1741 SA proposed
Listed as UL1741-SA Ed. 2
c9 drafted · lead
UL 1699B proposed
c10 drafted · lead
UL 1998 proposed
c11 drafted · lead
IEEE 1547 proposed
c12 drafted · lead
FCC Part 15 proposed
implements
c13 drafted · lead
Voltage ride-through
c14 verified · fact
Frequency ride-through
verified by: review-workflowverified on: 2026-10-24
c15 drafted · lead
Ramp rate control
c16 drafted · lead
Constant power factor mode
Listed as Specified-PF
c17 drafted · lead
Volt-VAr
c18 drafted · lead
Frequency-Watt
c19 drafted · lead
Volt-Watt
c20 drafted · lead
DC arc-fault protection
Arc board with Arc Fault Test available from Settings menu
uses_protocol
c21 drafted · lead
RS-485