Function

Voltage ride-through

ID
func:voltage-ride-through
IRI
https://solarlattice.org/kb/func/voltage-ride-through
Status
active
Also known as
LVRT/HVRT, fault ride-through, FRT, DVRT
Category
Grid support
Function kind
grid-support

Voltage ride-through lets an inverter stay online and keep delivering output current while grid voltage is briefly outside the normal deadband. A dip below the low threshold is low-voltage ride-through (LVRT), and a rise above the high threshold is high-voltage ride-through (HVRT). Utilities publish their own shall-trip and ride-through settings. In the PPL EU tables the ride-through curve and the trip curve are the same line. On SMA inverters, FRT_MODE selects one of six current feed-in modes, FRT_ULOW and FRT_UUP set the deadband, and FRT_U_BLK with FRT_T_BLK can set a blocking zone where generation stops.

<!-- review notes

Parts

Claims

trip_threshold

c1 drafted · lead nominal 0.88 UNITLESS

Scope: valid from 2023-11-30

Conditions: PPL EU UV1 shall-trip setting, in per unit of nominal voltage; ride-through and trip curves overlap

review note: possible conflict with c3 (same source; check the conditions); possible conflict with c5 (same source; check the conditions); possible conflict with c7 (same source; check the conditions)

c3 verified · fact nominal 0.5 UNITLESS

Scope: valid from 2023-11-30

Conditions: PPL EU UV2 shall-trip setting, in per unit of nominal voltage

verified by: review-workflowverified on: 2026-10-24review note: possible conflict with c1 (same source; check the conditions); possible conflict with c5 (same source; check the conditions); possible conflict with c7 (same source; check the conditions)

c5 verified · fact nominal 1.1 UNITLESS

Scope: valid from 2023-11-30

Conditions: PPL EU OV1 shall-trip setting, in per unit of nominal voltage; ride-through and trip curves overlap

verified by: review-workflowverified on: 2026-10-24review note: possible conflict with c1 (same source; check the conditions); possible conflict with c3 (same source; check the conditions); possible conflict with c7 (same source; check the conditions)

c7 drafted · lead nominal 1.2 UNITLESS

Scope: valid from 2023-11-30

Conditions: PPL EU OV2 shall-trip setting, in per unit of nominal voltage

review note: possible conflict with c1 (same source; check the conditions); possible conflict with c3 (same source; check the conditions); possible conflict with c5 (same source; check the conditions)

trip_time

c2 verified · fact nominal 2.1 SEC

Scope: valid from 2023-11-30

Conditions: PPL EU UV1 shall-trip time at 0.88 p.u.

verified by: review-workflowverified on: 2026-10-24review note: possible conflict with c4 (same source; check the conditions); possible conflict with c8 (same source; check the conditions)

c4 drafted · lead nominal 0.6 SEC

Scope: valid from 2023-11-30

Conditions: PPL EU UV2 shall-trip time at 0.5 p.u.

review note: possible conflict with c2 (same source; check the conditions); possible conflict with c6 (same source; check the conditions); possible conflict with c8 (same source; check the conditions)

c6 drafted · lead nominal 2.1 SEC

Scope: valid from 2023-11-30

Conditions: PPL EU OV1 shall-trip time at 1.1 p.u.

review note: possible conflict with c4 (same source; check the conditions); possible conflict with c8 (same source; check the conditions)

c8 drafted · lead nominal 0.16 SEC

Scope: valid from 2023-11-30

Conditions: PPL EU OV2 shall-trip time at 1.2 p.u.

review note: possible conflict with c2 (same source; check the conditions); possible conflict with c4 (same source; check the conditions); possible conflict with c6 (same source; check the conditions)

default_value

c9 verified · fact nominal 10 MIN

Conditions: SMA parameter FRT_T_U_AVG, the time window used to average pre-fault voltage

verified by: review-workflowverified on: 2026-10-24

c10 drafted · lead nominal 0 UNITLESS

Conditions: SMA parameter FRT_IQ_MODE; mode 0 selects the BDEW Iq(V) characteristic