Voltage ride-through lets an inverter stay online and keep delivering output current while grid voltage is briefly outside the normal deadband. A dip below the low threshold is low-voltage ride-through (LVRT), and a rise above the high threshold is high-voltage ride-through (HVRT). Utilities publish their own shall-trip and ride-through settings. In the PPL EU tables the ride-through curve and the trip curve are the same line. On SMA inverters, FRT_MODE selects one of six current feed-in modes, FRT_ULOW and FRT_UUP set the deadband, and FRT_U_BLK with FRT_T_BLK can set a blocking zone where generation stops.
<!-- review notes
- sentence 2: support check: partial - The passages support that the PPL EU ride-through and trip curves are identical. They do not state that utilities in general publish their own settings.
-->
Parts
Claims
trip_threshold
c1 drafted · lead
nominal 0.88 UNITLESS
Scope: valid from 2023-11-30
Conditions: PPL EU UV1 shall-trip setting, in per unit of nominal voltage; ride-through and trip curves overlap
review note: possible conflict with c3 (same source; check the conditions); possible conflict with c5 (same source; check the conditions); possible conflict with c7 (same source; check the conditions)
c3 verified · fact
nominal 0.5 UNITLESS
Scope: valid from 2023-11-30
Conditions: PPL EU UV2 shall-trip setting, in per unit of nominal voltage
verified by: review-workflowverified on: 2026-10-24review note: possible conflict with c1 (same source; check the conditions); possible conflict with c5 (same source; check the conditions); possible conflict with c7 (same source; check the conditions)
c5 verified · fact
nominal 1.1 UNITLESS
Scope: valid from 2023-11-30
Conditions: PPL EU OV1 shall-trip setting, in per unit of nominal voltage; ride-through and trip curves overlap
verified by: review-workflowverified on: 2026-10-24review note: possible conflict with c1 (same source; check the conditions); possible conflict with c3 (same source; check the conditions); possible conflict with c7 (same source; check the conditions)
c7 drafted · lead
nominal 1.2 UNITLESS
Scope: valid from 2023-11-30
Conditions: PPL EU OV2 shall-trip setting, in per unit of nominal voltage
review note: possible conflict with c1 (same source; check the conditions); possible conflict with c3 (same source; check the conditions); possible conflict with c5 (same source; check the conditions)
trip_time
c2 verified · fact
nominal 2.1 SEC
Scope: valid from 2023-11-30
Conditions: PPL EU UV1 shall-trip time at 0.88 p.u.
verified by: review-workflowverified on: 2026-10-24review note: possible conflict with c4 (same source; check the conditions); possible conflict with c8 (same source; check the conditions)
c4 drafted · lead
nominal 0.6 SEC
Scope: valid from 2023-11-30
Conditions: PPL EU UV2 shall-trip time at 0.5 p.u.
review note: possible conflict with c2 (same source; check the conditions); possible conflict with c6 (same source; check the conditions); possible conflict with c8 (same source; check the conditions)
c6 drafted · lead
nominal 2.1 SEC
Scope: valid from 2023-11-30
Conditions: PPL EU OV1 shall-trip time at 1.1 p.u.
review note: possible conflict with c4 (same source; check the conditions); possible conflict with c8 (same source; check the conditions)
c8 drafted · lead
nominal 0.16 SEC
Scope: valid from 2023-11-30
Conditions: PPL EU OV2 shall-trip time at 1.2 p.u.
review note: possible conflict with c2 (same source; check the conditions); possible conflict with c4 (same source; check the conditions); possible conflict with c6 (same source; check the conditions)
default_value
c9 verified · fact
nominal 10 MIN
Conditions: SMA parameter FRT_T_U_AVG, the time window used to average pre-fault voltage
verified by: review-workflowverified on: 2026-10-24
c10 drafted · lead
nominal 0 UNITLESS
Conditions: SMA parameter FRT_IQ_MODE; mode 0 selects the BDEW Iq(V) characteristic