Cease to energize is a DER state in which the unit delivers no active power at its point of connection, whether conditions are steady or transient. During this state the DER may still import power and exchange reactive power, but only to keep its housekeeping and auxiliary loads supplied, and any reactive exchange must come solely from passive devices. The requirement can also be met by disconnecting the Local EPS, or the part of it that holds the DER, from the Area EPS, and the DER may keep supplying that isolated part. Momentary cessation is a related ride-through behavior: for Category III DER, when voltage falls into the momentary cessation region, the DER ceases to energize without tripping and then restores its output. Setting Permit service to disabled directs a DER to cease to energize and trip, and an energy storage system that has ceased to energize may keep charging. In the field, the function is verified by operating a load interrupting device, confirming that the output terminals are de-energized and do not reconnect before the required delay, and repeating this on each phase.

<!-- review notes

Claims

related_to

c1 drafted · lead IEEE 1547-2018 4.5 Cease to energize performance requirement proposed

Scope: standard IEEE 1547-2018 proposed

In the cease to energize state, the DER shall not deliver active power during steady-state or transient conditions.
— IEEE 1547-2018 §4.5. Quoted with attribution; the text remains the publisher's copyright.

c2 drafted · lead IEEE 1547-2018 proposed

Defines the cease to energize state and the optional momentary cessation parameters.

c3 verified · fact Permit service / cease to energize

Scope: standard IEEE 1547-2018 proposed

Setting Permit service to disabled directs the DER to cease to energize and trip.

verified by: review-workflowverified on: 2026-10-24

c4 verified · fact Voltage ride-through

Scope: standard IEEE 1547-2018 proposed

For Category III DER, voltage inside the momentary cessation region requires ceasing to energize without tripping, then restoring output.

verified by: review-workflowverified on: 2026-10-24

c5 verified · fact IEEE 1547 performance categories

Momentary cessation behavior is specified for Category III DER.

verified by: review-workflowverified on: 2026-10-24

c6 drafted · lead Area electric power system

Cease to energize may alternatively be met by disconnecting the Local EPS from the Area EPS; the Area EPS operator may request the remaining reactive susceptance.

c7 verified · fact Local electric power system proposed

Reactive exchange limits depend on aggregate DER rating of the Local EPS; the DER may keep supplying a disconnected portion of the Local EPS.

verified by: review-workflowverified on: 2026-10-24

c8 drafted · lead Cease to energize functionality test proposed

Scope: standard IEEE 1547-2003 proposed

Operate a load interrupting device, verify output terminals de-energize and do not reconnect for the required delay; test each phase individually.

review note: support check: partial - The test content matches, but the passages do not show it belongs to IEEE 1547-2003; the references (4.1.4, 4.2.x, 4.4.1) are not tied to the edition in the passages.

c9 drafted · lead Battery energy storage system

An energy storage system that ceases to energize may continue charging; some battery systems report a cease-to-energize status flag over Modbus.