Cease to energize is a DER state in which the unit delivers no active power at its point of connection, whether conditions are steady or transient. During this state the DER may still import power and exchange reactive power, but only to keep its housekeeping and auxiliary loads supplied, and any reactive exchange must come solely from passive devices. The requirement can also be met by disconnecting the Local EPS, or the part of it that holds the DER, from the Area EPS, and the DER may keep supplying that isolated part. Momentary cessation is a related ride-through behavior: for Category III DER, when voltage falls into the momentary cessation region, the DER ceases to energize without tripping and then restores its output. Setting Permit service to disabled directs a DER to cease to energize and trip, and an energy storage system that has ceased to energize may keep charging. In the field, the function is verified by operating a load interrupting device, confirming that the output terminals are de-energized and do not reconnect before the required delay, and repeating this on each phase.
<!-- review notes
sentence 2: support check: partial - Import of active power and reactive exchange is permitted only for housekeeping and auxiliary loads, and reactive exchange must result from passive devices, but the passages do not limit the passive-only requirement to those loads; they also set the 10%/3% limits.
-->
Cease to energize may alternatively be met by disconnecting the Local EPS from the Area EPS; the Area EPS operator may request the remaining reactive susceptance.
review note: support check: partial - The test content matches, but the passages do not show it belongs to IEEE 1547-2003; the references (4.1.4, 4.2.x, 4.4.1) are not tied to the edition in the passages.