IEEE 1547 performance categories

ID
concept:ieee-1547-performance-categories
IRI
https://solarlattice.org/kb/concept/ieee-1547-performance-categories
Status
active
Also known as
Category I, Category II, Category III, Category A, Category B, abnormal performance category, abnormal performance categories, normal performance categories, disturbance performance categories
Category
Grid
Concept kind
technology

IEEE 1547-2018 groups DER requirements into performance categories, so that each DER type and application can be held to a performance level suited to it. Categories A and B cover voltage regulation and reactive power capability under Clause 5. These are called the normal performance categories. Categories I, II and III cover disturbance ride-through under Clause 6, meaning the voltage and frequency ride-through requirements. These are called the abnormal performance categories. The categories exist because some desirable DER technologies, such as synchronous generators or an engine running on landfill gas, cannot meet the full reactive power or ride-through requirements. The authority governing interconnection requirements (AGIR) decides which category each DER type and application must meet. It may use technical criteria such as DER type, capacity and expected penetration, as well as nontechnical criteria. The Clause 5 and Clause 6 categories are not tied to each other. Even so, the standard strongly recommends pairing Category I with Category A, and pairing Categories II and III with Category B. To protect the security of the bulk power system, most DER should have Category II ride-through. Category I or III is used only in notable exceptions.

<!-- review notes

Claims

part_of

c1 drafted · lead IEEE 1547-2018 proposed

Annex B gives guidance on how categories are assigned.

Categories I, II, and III for disturbance ride-through requirements (Clause 6)
— IEEE 1547-2018 Annex B.3. Quoted with attribution; the text remains the publisher's copyright.

related_to

c2 drafted · lead Voltage ride-through

c3 drafted · lead Frequency ride-through

c4 drafted · lead Distributed energy resource