Function
Frequency ride-through
- ID
func:frequency-ride-through
- IRI
https://solarlattice.org/kb/func/frequency-ride-through
- Status
- active
- Also known as
- LFRT/HFRT, LFRT, HFRT, Low/High Frequency Ride-Through, FRT_US
- Category
- Grid support
- Function kind
- grid-support
Frequency ride-through lets an inverter keep running through abnormally low or high grid frequency for a set time, and disconnect only if the excursion lasts longer than that delay. PPL EU publishes shall-trip settings for frequency ride-through: UF1 at 58.5 Hz and OF1 at 61.2 Hz, each with 301 s clearing, plus UF2 at 56.5 Hz and OF2 at 62 Hz, each with 0.2 s clearing. On the Solectria SGI XTM, LFRT and HFRT are set over Modbus with up to 10 ordered pairs of frequency percent and time. Each can be enabled on its own, and once enabled it overrides the UL1741/IEEE1547 frequency protection setpoints.
<!-- review notes
- sentence 3: support check: partial - Ordered pairs (up to 10), separate enabling and override of UL1741/IEEE1547 setpoints are stated, and registers are Modbus-style offsets, but Modbus is never explicitly named.
-->
Parts
Claims
trip_threshold
c1 drafted · lead
nominal 58.5 HZ
Conditions: PPL EU required under-frequency shall-trip setting UF1
review note: possible conflict with c3 (same source; check the conditions); possible conflict with c5 (same source; check the conditions); possible conflict with c7 (same source; check the conditions)
c3 verified · fact
nominal 56.5 HZ
Conditions: PPL EU required under-frequency shall-trip setting UF2
verified by: review-workflowverified on: 2026-10-24review note: possible conflict with c1 (same source; check the conditions); possible conflict with c5 (same source; check the conditions); possible conflict with c7 (same source; check the conditions)
c5 drafted · lead
nominal 61.2 HZ
Conditions: PPL EU required over-frequency shall-trip setting OF1
review note: possible conflict with c1 (same source; check the conditions); possible conflict with c3 (same source; check the conditions); possible conflict with c7 (same source; check the conditions)
c7 drafted · lead
nominal 62 HZ
Conditions: PPL EU required over-frequency shall-trip setting OF2
review note: possible conflict with c1 (same source; check the conditions); possible conflict with c3 (same source; check the conditions); possible conflict with c5 (same source; check the conditions)
trip_time
c2 drafted · lead
nominal 301 SEC
Conditions: PPL EU UF1 clearing time at 58.5 Hz
review note: possible conflict with c4 (same source; check the conditions); possible conflict with c8 (same source; check the conditions)
c4 verified · fact
nominal 0.2 SEC
Conditions: PPL EU UF2 clearing time at 56.5 Hz
verified by: review-workflowverified on: 2026-10-24review note: possible conflict with c2 (same source; check the conditions); possible conflict with c6 (same source; check the conditions)
c6 drafted · lead
nominal 301 SEC
Conditions: PPL EU OF1 clearing time at 61.2 Hz
review note: possible conflict with c4 (same source; check the conditions); possible conflict with c8 (same source; check the conditions)
c8 drafted · lead
nominal 0.2 SEC
Conditions: PPL EU OF2 clearing time at 62 Hz
review note: possible conflict with c2 (same source; check the conditions); possible conflict with c6 (same source; check the conditions)
c11 drafted · lead
≥ 1 SEC
Scope: products Solectria SGI 500/750XTM
Conditions: Minimum time required to trip on abnormal frequency, firmware D002
c12 drafted · lead
≥ 0.5 SEC
Scope: products Solectria SGI 500/750XTM
Conditions: Minimum time required to trip on abnormal frequency, firmware D003
setting_range
c9 drafted · lead
0–10 NUM
Scope: products Solectria SGI 500/750XTM
Conditions: Number of LFRT or HFRT ordered pairs (registers offset 426 and 467)
default_value
c10 drafted · lead
nominal 2 NUM
Scope: products Solectria SGI 500/750XTM
Conditions: Factory default number of LFRT and of HFRT ordered pairs
response_time
c13 drafted · lead
≤ 500 MilliSEC
Scope: products Solectria SGI 500/750XTM
Conditions: Recovery after a frequency event when the inverter was not required to trip
c14 drafted · lead
≤ 2 SEC
Scope: products Solectria SGI 500/750XTM
Conditions: Time to reach full output power after momentary cessation, firmware D003
Referenced by
Data