Rate-of-change-of-frequency ride-through

ID
func:rocof-ride-through
IRI
https://solarlattice.org/kb/func/rocof-ride-through
Status
active
Also known as
ROCOF ride-through, PFRC, ROCOF
Category
Grid support
Function kind
grid-support

ROCOF ride-through means the DER stays connected and does not trip while grid frequency is changing quickly, as long as the rate of change stays within the limit for its performance category. The ride-through limits are 0.5 Hz/s for Category I, 2.0 Hz/s for Category II and 3.0 Hz/s for Category III. When compliance at the PCC is shown by the DER system itself, a type test is required. Evaluation and commissioning tests are not required in that case. Composite installations do need a DER evaluation and commissioning tests. One utility's default settings document accepts UL 1741 SB certification as enough proof of ROCOF ride-through for an individual inverter. That same document does not allow relays, controllers or any other site equipment outside the certified inverter to trip on ROCOF or to have ROCOF enabled.

<!-- review notes

Claims

subclass_of

c1 verified · fact Frequency ride-through

ROCOF ride-through applies within the continuous operation region and the low- and high-frequency ride-through regions.

verified by: review-workflowverified on: 2026-10-24review note: support check: partial - Passage states ROCOF ride-through applies within continuous operation and the low/high-frequency ride-through regions, but does not state that it is a kind of frequency ride-through (taxonomy relation is implied only by context).