Solar Lattice

Function

High-frequency ride-through

ID
func:high-frequency-ride-through
IRI
https://solarlattice.org/kb/func/high-frequency-ride-through
Status
active
Also known as
HFRT, DHFT
Category
Grid support
Function kind
grid-support

High-frequency ride-through keeps a DER connected and in sync with the grid during a temporary over-frequency disturbance, so it does not trip right away. On the Yaskawa SGI XTM, you set up HFRT over Modbus: control, trigger and status bits, an ordered-pair count, and up to 10 frequency and time points that define the must-ride-through curve. When HFRT is enabled on the SGI XTM, it overrides the UL1741/IEEE1547 over-frequency protection setpoints. It can be enabled separately from LFRT. The inverter keeps exporting power while it is inside the time window. It stops producing only if frequency stays past the setpoint for longer than the set time. Above 70 Hz it goes into momentary cessation and risks damage. PPL EU over-frequency settings use OF1 at 61.2 Hz with a 301 s clearing time and OF2 at 62 Hz with a 0.2 s clearing time.

<!-- review notes

Claims

part_of

c1 drafted · lead Frequency ride-through

The Yaskawa frequency ride-through function covers both low (LFRT) and high (HFRT) frequency conditions, and each can be enabled on its own.

trip_threshold

c2 drafted · lead nominal 61.2 HZ

Conditions: PPL EU required over-frequency setting OF1 (shall trip)

review note: possible conflict with c4 (same source; check the conditions)

c4 drafted · lead nominal 62 HZ

Conditions: PPL EU required over-frequency setting OF2 (shall trip)

review note: possible conflict with c2 (same source; check the conditions)

trip_time

c3 drafted · lead nominal 301 SEC

Conditions: PPL EU over-frequency setting OF1 clearing time at 61.2 Hz

review note: possible conflict with c5 (same source; check the conditions)

c5 drafted · lead nominal 0.2 SEC

Conditions: PPL EU over-frequency setting OF2 clearing time at 62 Hz

review note: possible conflict with c3 (same source; check the conditions)

c7 drafted · lead ≥ 1 SEC

Scope: products Solectria SGI 500/750XTM

Conditions: Minimum time to trip on abnormal frequency, firmware D002

c8 drafted · lead ≥ 0.5 SEC

Scope: products Solectria SGI 500/750XTM

Conditions: Minimum time to trip on abnormal frequency, firmware D003

setting_range

c6 drafted · lead ≤ 10 NUM

Scope: products Solectria SGI 500/750XTM

Conditions: Number of [%Frequency, Time] ordered pairs that define the HFRT must-ride-through curve

response_time

c9 drafted · lead ≤ 500 MilliSEC

Scope: products Solectria SGI 500/750XTM

Conditions: Recovery after a frequency event when the inverter was not required to trip

c10 drafted · lead ≤ 2 SEC

Scope: products Solectria SGI 500/750XTM

Conditions: Time to reach full output power after momentary cessation, firmware D003

Data