Volt-VAr changes the reactive power output in response to grid voltage, following a programmable curve. It injects reactive power when voltage is below nominal and absorbs it when voltage is above nominal. IEEE 1547-2018 calls this the voltage-reactive power mode. One set of default settings requirements for that standard lists the function as OFF by default. The curve is set with four voltage points (V1 to V4), a reactive power value at each point (Q1 to Q4), and a response time constant for reaching 95% of the requested reactive power. In the Tesla commercial controls manuals, Volt-VAr is an open-loop response to voltage measured at the point of interconnection meter. Its output is added to any direct reactive power command, and the curve can be written over Modbus or DNP3. On Solis inverters using the EN50549 grid standard, you turn Q(U) on from the inverter screen under Working Mode, Mode 2. It can deliver up to 60% reactive power, and P lock-in and lock-out levels switch the mode on and off. With the SMA Data Manager M, Q(U) needs exactly one meter at the point of interconnection, and that meter must measure both voltage and current. Splitting the voltage and current measurements across two meters produces faulty power values.

<!-- review notes

Claims

part_of

c1 drafted · lead IEEE 1547-2018 proposed

Specified as one of the voltage and reactive power control functions for Category A and B DER.

Voltage-reactive power mode may also be commonly referred to as "volt-var" mode.
— IEEE 1547-2018 §5.1, Table 6 note a. Quoted with attribution; the text remains the publisher's copyright.

review note: support check: partial - Passages show voltage-reactive power (volt-var) mode in Table 6 for Category A and B DER, but the table's contents aren't shown; the 'one of the functions' framing is only implied.

default_value

c2 drafted · lead nominal 213 V

Conditions: Solis inverter, Volt-Var curve voltage point 1, EN50549 grid standard

review note: possible conflict with c4 (same source; check the conditions); possible conflict with c6 (same source; check the conditions); possible conflict with c8 (same source; check the conditions)

c4 drafted · lead nominal 223 V

Conditions: Solis inverter, Volt-Var curve voltage point 2, EN50549 grid standard

review note: possible conflict with c2 (same source; check the conditions); possible conflict with c6 (same source; check the conditions); possible conflict with c8 (same source; check the conditions)

c6 drafted · lead nominal 236 V

Conditions: Solis inverter, Volt-Var curve voltage point 3, EN50549 grid standard

review note: possible conflict with c2 (same source; check the conditions); possible conflict with c4 (same source; check the conditions); possible conflict with c8 (same source; check the conditions)

c8 drafted · lead nominal 246 V

Conditions: Solis inverter, Volt-Var curve voltage point 4, EN50549 grid standard

review note: possible conflict with c2 (same source; check the conditions); possible conflict with c4 (same source; check the conditions); possible conflict with c6 (same source; check the conditions)

c10 drafted · lead nominal 48 PERCENT

Conditions: Solis inverter, leading reactive power level of the Volt-Var curve, EN50549 grid standard

review note: possible conflict with c12 (same source; check the conditions); possible conflict with c14 (same source; check the conditions); possible conflict with c15 (same source; check the conditions)

c12 drafted · lead nominal -48 PERCENT

Conditions: Solis inverter, lagging reactive power level of the Volt-Var curve, EN50549 grid standard

review note: possible conflict with c10 (same source; check the conditions); possible conflict with c14 (same source; check the conditions); possible conflict with c15 (same source; check the conditions)

c14 drafted · lead nominal 20 PERCENT

Conditions: Solis inverter, P lock-in active power level that turns Q(U) on, EN50549 grid standard

review note: possible conflict with c10 (same source; check the conditions); possible conflict with c12 (same source; check the conditions); possible conflict with c15 (same source; check the conditions)

c15 verified · fact nominal 5 PERCENT

Conditions: Solis inverter, P lock-out active power level that turns Q(U) off, EN50549 grid standard

verified by: review-workflowverified on: 2026-10-24review note: possible conflict with c10 (same source; check the conditions); possible conflict with c12 (same source; check the conditions); possible conflict with c14 (same source; check the conditions)

setting_range

c3 drafted · lead 210–230 V

Conditions: Solis inverter, Volt-Var curve voltage point 1, EN50549 grid standard

review note: possible conflict with c9 (same source; check the conditions)

c5 drafted · lead 210–230 V

Conditions: Solis inverter, Volt-Var curve voltage point 2, EN50549 grid standard

review note: possible conflict with c9 (same source; check the conditions)

c7 verified · fact 230–255 V

Conditions: Solis inverter, Volt-Var curve voltage point 3, EN50549 grid standard

verified by: review-workflowverified on: 2026-10-24

c9 drafted · lead 240–265 V

Conditions: Solis inverter, Volt-Var curve voltage point 4, EN50549 grid standard

review note: possible conflict with c3 (same source; check the conditions); possible conflict with c5 (same source; check the conditions)

c11 drafted · lead 0–60 PERCENT

Conditions: Solis inverter, leading reactive power level of the Volt-Var curve, EN50549 grid standard

c13 verified · fact -60–0 PERCENT

Conditions: Solis inverter, lagging reactive power level of the Volt-Var curve, EN50549 grid standard