Transformer winding configuration describes how the windings on each side of a transformer are connected, for example delta, wye or grounded wye. It is often written as an IEC vector group such as Dd0 or Dy1. The configuration matters because it affects ground fault detection, whether the system has a voltage reference, and how harmonics are filtered. Some configurations give effective grounding, such as grounded wye on both sides, sometimes with a grounding bank or a neutral grounding reactor. The utility decides this case by case. Inverter makers publish compatibility tables, and only some windings are allowed. For example, some CPS models accept wye floating, wye grounded and delta floating windings, but not delta grounded. Solis S6-GU EHV inverters accept Y(n)y(n), Dy(n) and Dd windings, but not Y(n)d. The Solectria XGI 1500 is compatible with grounded wye on the inverter side and delta on the utility side. Check the transformer against the inverter or storage manual before connecting. Manuals list prohibited configurations, and battery systems like Megapack show which configurations to use for grid-following operation.
<!-- review notes
- sentence 1: support check: partial - Delta/wye/grounded wye and IEC vector groups Dd0, Dy1 appear, but the definition and 'often written as' are only implied.
- sentence 6: support check: partial - Prohibited configurations and grid-following figures are present, but the instruction to check against the manual before connecting and Megapack naming are not stated.
-->
Claims
related_to
c1 drafted · lead
Effective grounding
Grounded wye-wye, wye-wye with a grounding bank, and wye-delta with a neutral grounding reactor are shown as grounding configurations. Utilities decide case by case which configurations count as effectively grounded.
c2 drafted · lead
Harmonic distortion
The winding configuration matters for filtering harmonics from the transmission system.
c3 verified · fact
Grid-following inverter
Megapack manuals show transformer configurations for on-grid, grid-following operation.
verified by: review-workflowverified on: 2026-10-24
c4 drafted · lead
Transformer winding compatibility check proposed
Inverter vendors publish tables of compatible transformer windings.
c5 drafted · lead
Solis S6-GU(250-350)K-EHV-US
Listed as compatible with Y(n)y(n), Dy(n) and Dd windings, and not compatible with Y(n)d.
c6 drafted · lead
Solectria XGI 1500
Compatible with a grounded-wye winding on the inverter side, neutral bonded to ground, and delta on the utility side. The manual also lists prohibited configurations.
c7 drafted · lead
CPS SCA25KTL-DO/US-208
For the 25 kW 208 V inverter: wye floating, wye grounded and delta floating are allowed. Delta grounded is not. Neutral connection is optional.