Effective grounding

ID
concept:effective-grounding
IRI
https://solarlattice.org/kb/concept/effective-grounding
Status
active
Also known as
effectively grounded, grounding transformer, grounding bank
Category
Grid
Concept kind
electrical

A system is effectively grounded when its ground connection has low enough impedance that a ground fault cannot raise voltages above the limits set for the connected equipment. The IEEE definition uses sequence impedances: the ratio X0/X1 must be positive and below 3, and R0/X1 must be positive and below 1. Under these conditions the coefficient of grounding stays at or below 80%. If a phase faults to ground and the system is not effectively grounded, equipment on the healthy phases can see up to 173% of nominal voltage. Effective grounding keeps this to roughly 125% to 138%, depending on the utility system. Utilities expect distributed generation and storage sites to match their level of grounding, so the site does not weaken the utility's grounding. Some utilities therefore require AC-side grounding of PV inverters. Effective grounding can be provided in two ways. One is a grounding reactor in the transformer neutral. The other is a grounding bank, built from a zig-zag or wye-delta transformer, which passes zero-sequence current easily but blocks positive-sequence current. A single grounding bank at the point of common coupling can effectively ground a whole multi-inverter plant, so the inverters can be connected without a neutral. Grounding banks are usually rated only for short-term duty and need overcurrent protection. The inverters should be interlocked so they shut off when the grounding bank breaker opens. Effective grounding also gives fault current a low-impedance return path, so utility ground-fault protection can operate faster. Related topics are symmetrical components, transformer winding configuration and protection coordination.

Claims

related_to

c1 drafted · lead IEEE 142-2007 (Green Book) proposed

The IEEE Green Book defines effective grounding through zero-sequence to positive-sequence impedance ratios and suggests two grounding schemes.

c2 drafted · lead IEEE 1547 proposed

PV plants must meet IEEE 1547 and local utility interface rules. Some utilities also require AC-side grounding of the inverters to match their own grounding scheme.

c3 drafted · lead Symmetrical components

Effective grounding is stated as ratios of zero-sequence to positive-sequence impedance. Grounding banks give a low-impedance path to zero-sequence voltage.

c4 drafted · lead Transformer winding configuration

Whether a transformer configuration provides effective grounding is judged case by case by each utility.

c5 drafted · lead Protection coordination

Solid grounding can let large fault currents flow, which can desensitize overcurrent coordination. Effective grounding speeds up utility ground-fault protection.

c6 drafted · lead Transient grid overvoltage event

Systems that are not effectively grounded can see temporary overvoltage. One mitigation is a local 3V0 relay scheme.

c7 drafted · lead Medium voltage transformer

A grounding reactor in the transformer neutral, or a grounding bank on the primary side of the MV transformer, can provide effective grounding.

review note: support check: partial - Grounding reactor in neutral and grounding bank on the MV transformer primary side are supported, but the reactor is described for a transformer neutral generally, not specifically the MV transformer.

c8 verified · fact Solectria Effective Grounding Design Tool proposed

Used to calculate the grounding bank impedance and current ratings.

verified by: review-workflowverified on: 2026-10-24