Solar Lattice

Function

Frequency-Watt

ID
func:frequency-watt
IRI
https://solarlattice.org/kb/func/frequency-watt
Status
active
Also known as
frequency droop, frequency-power, P(f), Freq-Watt, over-frequency power reduction, DHFW, DLFW, Frequency-droop mode, Set F Derating, Frequency-Watt Control
Category
Grid support
Function kind
grid-support

Frequency-Watt changes the inverter's active power output when grid frequency moves away from nominal, which supports grid frequency. When frequency rises, output power goes down. IEEE 1547-2018 sets frequency droop parameters, including an overfrequency droop value kOF. A default settings document for IEEE 1547-2018 lists frequency-droop mode (Freq-Watt) as ON by default. Tesla controllers set up frequency droop with an enable flag, upper and lower deadbands around the reference frequency, upper and lower proportional gains, and a low-pass filter time response. A read-only register reports the resulting power command. On CSI inverters the Freq-Watt menu uses a start frequency, a power reduction gradient, a stop frequency and a hysteresis option. It applies only when a Rule 21 standard is selected, and it is meant for maintenance personnel only. Change these parameters only when the grid operator asks for it.

<!-- review notes

Claims

requires

c1 drafted · lead Grid Guard code holder

Scope: products Sunny Island 4.4M / 6.0H / 8.0H

Sunny Island: the P(f) overfrequency active power reduction mode is an expert parameter protected by SMA Grid Guard.

default_value

c2 drafted · lead nominal 0.036 HZ

Scope: products CPS SCA25KTL-DO/US-208

Conditions: Overfrequency droop deadband (FreqDroop_DbOf) in the grid setting table

c3 drafted · lead nominal 0.036 HZ

Scope: products CPS SCA25KTL-DO/US-208

Conditions: Underfrequency droop deadband (FreqDroop_DbUf) in the grid setting table

setting_range

c4 drafted · lead 0–1800 SEC

Scope: products Solectria SGI 500/750XTM

Conditions: Freq Watt Time Window Modbus register 40381; default 0

c5 verified · fact 0–64800 SEC

Scope: products Solectria SGI 500/750XTM

Conditions: Freq Watt Timeout Window Modbus register 40382; default 0

verified by: review-workflowverified on: 2026-10-24

c6 drafted · lead 0–600 SEC

Scope: products Solectria SGI 500/750XTM

Conditions: Freq Watt Ramp Time Modbus register 40383; default 0

c7 verified · fact 2–10 NUM

Scope: products Solectria SGI 500/750XTM

Conditions: Number of points on the frequency-watt curve, Modbus register 40384

verified by: review-workflowverified on: 2026-10-24

c8 drafted · lead 2–10 NUM

Scope: products Solectria XGI 1500

Conditions: Active points on the Freq-Watt curve; at least 2 required