Function
Frequency-Watt
- ID
func:frequency-watt
- IRI
https://solarlattice.org/kb/func/frequency-watt
- Status
- active
- Also known as
- frequency droop, frequency-power, P(f), Freq-Watt, over-frequency power reduction, DHFW, DLFW, Frequency-droop mode, Set F Derating, Frequency-Watt Control
- Category
- Grid support
- Function kind
- grid-support
Frequency-Watt changes the inverter's active power output when grid frequency moves away from nominal, which supports grid frequency. When frequency rises, output power goes down. IEEE 1547-2018 sets frequency droop parameters, including an overfrequency droop value kOF. A default settings document for IEEE 1547-2018 lists frequency-droop mode (Freq-Watt) as ON by default. Tesla controllers set up frequency droop with an enable flag, upper and lower deadbands around the reference frequency, upper and lower proportional gains, and a low-pass filter time response. A read-only register reports the resulting power command. On CSI inverters the Freq-Watt menu uses a start frequency, a power reduction gradient, a stop frequency and a hysteresis option. It applies only when a Rule 21 standard is selected, and it is meant for maintenance personnel only. Change these parameters only when the grid operator asks for it.
<!-- review notes
- sentence 2: support check: partial - Table 38 title and overfrequency droop kOF are given and the default ON is listed, but the passages don't say IEEE 1547-2018 sets these or that the document is a default settings document, though it is implied.
-->
Claims
requires
c1 drafted · lead
Grid Guard code holder
Scope: products Sunny Island 4.4M / 6.0H / 8.0H
Sunny Island: the P(f) overfrequency active power reduction mode is an expert parameter protected by SMA Grid Guard.
default_value
c2 drafted · lead
nominal 0.036 HZ
Scope: products CPS SCA25KTL-DO/US-208
Conditions: Overfrequency droop deadband (FreqDroop_DbOf) in the grid setting table
c3 drafted · lead
nominal 0.036 HZ
Scope: products CPS SCA25KTL-DO/US-208
Conditions: Underfrequency droop deadband (FreqDroop_DbUf) in the grid setting table
setting_range
c4 drafted · lead
0–1800 SEC
Scope: products Solectria SGI 500/750XTM
Conditions: Freq Watt Time Window Modbus register 40381; default 0
c5 verified · fact
0–64800 SEC
Scope: products Solectria SGI 500/750XTM
Conditions: Freq Watt Timeout Window Modbus register 40382; default 0
verified by: review-workflowverified on: 2026-10-24
c6 drafted · lead
0–600 SEC
Scope: products Solectria SGI 500/750XTM
Conditions: Freq Watt Ramp Time Modbus register 40383; default 0
c7 verified · fact
2–10 NUM
Scope: products Solectria SGI 500/750XTM
Conditions: Number of points on the frequency-watt curve, Modbus register 40384
verified by: review-workflowverified on: 2026-10-24
c8 drafted · lead
2–10 NUM
Scope: products Solectria XGI 1500
Conditions: Active points on the Freq-Watt curve; at least 2 required