Function
Volt-Watt
- ID
func:volt-watt
- IRI
https://solarlattice.org/kb/func/volt-watt
- Status
- active
- Also known as
- voltage-active power mode, P(U), P(V), DVWC
- Category
- Grid support
- Function kind
- grid-support
Volt-Watt lowers the active power output of an inverter or battery system as grid voltage rises, following a programmable voltage versus power curve. On the Tesla commercial controls the response is open-loop, based on overvoltage measured at the POI meter. The curve is set with an enable flag, high voltage setpoints V1 and V2, a power limit P2 and a response time constant, and the resulting power limit can be read back over Modbus. Tesla project engineers can program the curve during commissioning, or it can be changed in real time over Modbus or DNP3 points. IEEE 1547-2018 defines a voltage-active power mode that can be switched on or off. Category A DER do not have to provide it, and the default settings guidance leaves it off. Volt-Watt is listed as a feature of the CPS SCA25KTL-DO/US-208 and SCA36KTL, the Solectria PVI series and Generac PWRmicro equipment. On the CPS SCA25KTL it is enabled for IEEE 1547-2018 and Rule 21 and disabled for ISO-NE.
<!-- review notes
- sentence 1: support check: partial - Passages say active power changes with voltage and Tesla limits via programmable curve against overvoltage, but 'inverter or battery' lowering as voltage rises is mostly implied; generally supported though not explicit about lowering for inverters (P3/P4 0%).
- sentence 5: support check: partial - Volt-Watt listed for SCA36KTL, PVI series, and the enabled/disabled settings are shown, but SCA25KTL-DO/US-208 listing and Generac PWRmicro are not clearly shown, and the settings table isn't tied to SCA25KTL.
-->
Claims
setting_range
c1 verified · fact
240–288 V
Scope: products Solis RHI-1P(5-10)K-HVES-5G-US; standard CA Rule 21 proposed
Conditions: Volt-Watt V2 (Vstart), Rule 21 settings, 240 V rated grid
verified by: review-workflowverified on: 2026-10-24
c3 verified · fact
240–288 V
Scope: products Solis RHI-1P(5-10)K-HVES-5G-US; standard CA Rule 21 proposed
Conditions: Volt-Watt V3 (Vstop), Rule 21 settings, 240 V rated grid
verified by: review-workflowverified on: 2026-10-24
c5 verified · fact
221–304 V
Scope: products CSI-25/30/36/40K-T480GL01-UB; standard CA Rule 21 proposed
Conditions: Volt-Watt V2 (Vstart), Rule 21 settings, 480 V rated grid
verified by: review-workflowverified on: 2026-10-24
c7 drafted · lead
277–332 V
Scope: products CSI-25/30/36/40K-T480GL01-UB; standard CA Rule 21 proposed
Conditions: Volt-Watt V3 (Vstop), Rule 21 settings, 480 V rated grid
default_value
c2 drafted · lead
nominal 254 V
Scope: products Solis RHI-1P(5-10)K-HVES-5G-US; standard CA Rule 21 proposed
Conditions: Volt-Watt V2 (Vstart), Rule 21 default, 240 V rated grid
review note: possible conflict with c4 (same source; check the conditions)
c4 verified · fact
nominal 264 V
Scope: products Solis RHI-1P(5-10)K-HVES-5G-US; standard CA Rule 21 proposed
Conditions: Volt-Watt V3 (Vstop), Rule 21 default, 240 V rated grid
verified by: review-workflowverified on: 2026-10-24review note: possible conflict with c2 (same source; check the conditions)
c6 drafted · lead
nominal 293 V
Scope: products CSI-25/30/36/40K-T480GL01-UB; standard CA Rule 21 proposed
Conditions: Volt-Watt V2 (Vstart), Rule 21 default, 480 V rated grid
review note: possible conflict with c8 (same source; check the conditions)
c8 drafted · lead
nominal 304 V
Scope: products CSI-25/30/36/40K-T480GL01-UB; standard CA Rule 21 proposed
Conditions: Volt-Watt V3 (Vstop), Rule 21 default, 480 V rated grid
review note: possible conflict with c6 (same source; check the conditions)