Solar Lattice

DetectionMethod

Grid frequency measurement

ID
method:grid-frequency-measurement
IRI
https://solarlattice.org/kb/method/grid-frequency-measurement
Status
active

Grid frequency measurement means measuring the real grid frequency when an inverter reports a grid over-frequency, under-frequency or grid abnormal fault, and comparing it with the inverter's set protection range. On Solis inverters, turn the DC switch off, then check the frequency at the inverter test points and compare it with the LCD reading, because a faulty measurement circuit can give a false reading. At commissioning, measure the frequency of each phase to ground if your meter can do it, and confirm each value is within local grid standards and the inverter specifications. The inverter display also shows the grid frequency value for a quick comparison. Sungrow SG250HX-US and SG36CX-US/SG60CX-US inverters list a nominal grid frequency of 60 Hz and a grid frequency range of 55 to 65 Hz. If the measured frequency is outside the set range, contact the local utility; on Solis units, raise the upper limit only with the utility's permission. Also check that the protection parameters are set correctly in the app or on the LCD. If the fault continues after these causes are ruled out, contact the manufacturer's service team or replace the inverter.

<!-- review notes

Claims

produces

c1 verified · fact Grid frequency outside limits

Used to confirm grid over-frequency, under-frequency and grid abnormal faults. On Solis units, a reading that differs from the LCD value may point to a faulty inverter measurement circuit rather than the grid.

verified by: review-workflowverified on: 2026-10-23