The Modbus protocol reference guide lists RTU mode as a transmission mode of the Modbus protocol.
- Modbus Protocol Ref Guide - PI MBUS 300
tbl=1.r7h=5c8284ccc5ff
verified by: review-workflowverified on: 2026-10-24
Modbus RTU is the RTU transmission mode of the Modbus protocol. It runs over a serial link, for example a two-wire RS-485 bus with D- and D+ data terminals on the Fronius Symo. The FIMER PVS-60-TL-US and PVS-166/175-TL-US string inverters list Modbus RTU/TCP as their communication protocol and state that it is SunSpec compliant. The UNO-DM-PLUS-US inverters list ModBus RTU (SunSpec) next to the Aurora Protocol, and some variants also list ModBus TCP. On the Fronius Datamanager 2.0, the RS485 port carries either SunSpec Modbus RTU or a meter connection. Third-party systems can use it to read inverter data while the system also reports to Fronius Solar.web. The Huawei SmartLogger can connect to one environmental monitoring instrument that supports standard Modbus-RTU. Other third-party Modbus-RTU devices need a .cfg protocol file from Huawei imported into the logger, and you must add them manually. On the Elkor WattsOn Mark II W2-M2, wire the Modbus RTU master to the X. Bus terminal and set the serial format to 115200,N,8,1. The meter answers on any address, and address 1 is recommended.
subclass_ofThe Modbus protocol reference guide lists RTU mode as a transmission mode of the Modbus protocol.
tbl=1.r7 h=5c8284ccc5ffverified by: review-workflowverified on: 2026-10-24