Frequency trip disconnects the inverter from the grid when grid frequency stays above an over-frequency limit or below an under-frequency limit for longer than its set clearing time. Settings normally come in two stages per direction, such as OF1/OF2 and UF1/UF2, each with its own frequency and clearing time; utilities like PPL EU and ISO New England publish their own required values. CPS string inverters expose GridFrqMax1-3, GridFrqMin1-3 and matching trip time parameters, with separate defaults for the IEEE 1547-2018, Rule 21 and ISO-NE profiles. The Fronius Galvo states a frequency trip accuracy of 0.05 Hz and has a settable tolerance time for frequency limit violations. On Solis hybrids running from a generator, the HF1/HF2 and LF1/LF2 trip points can be widened to stop nuisance trips, but only in backup or off-grid mode, and they must be set back when the grid returns.
<!-- review notes
- sentence 1: support check: partial - Passages say the inverter disconnects after a programmed delay, but the u36 text ties disconnect to abnormal voltage, and the clearing-time tables don't state the general mechanism fully.
- sentence 2: support check: partial - Two stages per direction and PPL EU/ISO-NE values are shown, but 'normally' and that utilities publish their own required values (ISO-NE settings are SolarEdge settings) aren't stated.
- sentence 3: support check: partial - Parameters and profile defaults shown, but a single product doesn't show all of GridFrqMin1-3 in u30, and some tables only have IEEE/Rule21; mostly supported across passages.
- sentence 1: review: partial - The IEEE trip tables give frequency limits with clearing times, and ABB says the inverter disconnects after a programmed delay, but no passage states the general rule that the inverter trips when frequency stays past the limit for longer than…
-->
Claims
default_value
c1 drafted · lead
nominal 56.5 HZ
Scope: standard IEEE 1547-2018 proposed
Conditions: UF2 shall-trip default frequency
review note: possible conflict with c4 (same source; check the conditions)
c3 drafted · lead
nominal 0.16 SEC
Scope: standard IEEE 1547-2018 proposed
Conditions: UF2 default clearing time
c4 verified · fact
nominal 62 HZ
Scope: standard IEEE 1547-2018 proposed
Conditions: OF2 shall-trip default frequency
verified by: review-workflowverified on: 2026-10-24review note: possible conflict with c1 (same source; check the conditions)
c6 drafted · lead
nominal 0.16 SEC
Scope: standard IEEE 1547-2018 proposed
Conditions: OF2 default clearing time
c31 drafted · lead
nominal 61.2 HZ
Scope: products CPS SCA25KTL-DO/US-208, CPS SCA36KTL-DO/US-480, CPS SCA50-60KTL-DO/US-480
Conditions: CPS GridFrqMax1, IEEE 1547-2018 and ISO-NE profiles
c32 drafted · lead
nominal 60.5 HZ
Scope: products CPS SCA25KTL-DO/US-208, CPS SCA36KTL-DO/US-480, CPS SCA50-60KTL-DO/US-480; standard CA Rule 21 proposed
Conditions: CPS GridFrqMax1, Rule 21 profile
review note: possible conflict with c35 (same source; check the conditions)
c35 verified · fact
nominal 57 HZ
Scope: products CPS SCA25KTL-DO/US-208, CPS SCA36KTL-DO/US-480, CPS SCA50-60KTL-DO/US-480; standard CA Rule 21 proposed
Conditions: CPS GridFrqMin2 and GridFrqMin3, Rule 21 profile (56.5 Hz for IEEE 1547-2018 and ISO-NE)
verified by: review-workflowverified on: 2026-10-24review note: possible conflict with c32 (same source; check the conditions)
setting_range
c2 verified · fact
50–57 HZ
Scope: standard IEEE 1547-2018 proposed
Conditions: UF2 allowable frequency setting range
verified by: review-workflowverified on: 2026-10-24review note: possible conflict with c5 (same source; check the conditions)
c5 drafted · lead
61.8–66 HZ
Scope: standard IEEE 1547-2018 proposed
Conditions: OF2 allowable frequency setting range
review note: possible conflict with c2 (same source; check the conditions)
c33 drafted · lead
60–66 HZ
Scope: products CPS SCA25KTL-DO/US-208, CPS SCA36KTL-DO/US-480, CPS SCA50-60KTL-DO/US-480
Conditions: CPS over-frequency thresholds GridFrqMax1-3, all profiles
c34 drafted · lead
48–60 HZ
Scope: products CPS SCA25KTL-DO/US-208, CPS SCA36KTL-DO/US-480, CPS SCA50-60KTL-DO/US-480
Conditions: CPS under-frequency thresholds GridFrqMin1-3, all profiles
c36 verified · fact
0–1000 SEC
Scope: products CPS SCA25KTL-DO/US-208, CPS SCA36KTL-DO/US-480, CPS SCA50-60KTL-DO/US-480
Conditions: CPS frequency trip times, IEEE 1547-2018 and ISO-NE profiles
verified by: review-workflowverified on: 2026-10-24
c37 drafted · lead
0–655 SEC
Scope: products CPS SCA25KTL-DO/US-208, CPS SCA36KTL-DO/US-480, CPS SCA50-60KTL-DO/US-480; standard CA Rule 21 proposed
Conditions: CPS under-frequency trip times FrqMinTripT1-3, Rule 21 profile
c38 verified · fact
0–1310 SEC
Scope: products CPS SCA100K-T-US-480 / SCA50K-T-US-208
Conditions: CPS frequency trip times (FrqMaxTripT1/T2/T3, FrqMinTripT1)
verified by: review-workflowverified on: 2026-10-24
c39 verified · fact
0.016–600 SEC
Scope: products Fronius Galvo 208-240
Conditions: Fronius Galvo frequency limit violation tolerance time
verified by: review-workflowverified on: 2026-10-24
trip_threshold
c7 disputed
nominal 58.5 HZ
Conditions: PPL EU required UF1 shall-trip setting
review note: possible conflict with c9 (same source; check the conditions); possible conflict with c11 (same source; check the conditions); possible conflict with c13 (same source; check the conditions)conflicts with: Frequency trip (c15)conflicts with: Frequency trip (c17)conflicts with: Frequency trip (c21)
c9 verified · fact
nominal 56.5 HZ
Conditions: PPL EU required UF2 shall-trip setting
verified by: review-workflowverified on: 2026-10-24review note: possible conflict with c7 (same source; check the conditions); possible conflict with c11 (same source; check the conditions); possible conflict with c13 (same source; check the conditions); review: the compiler-flagged conflict (func:frequency-trip#c15, func:frequency-trip#c17, func:frequency-trip#c19) is a scenario difference, resolved at review
c11 disputed
nominal 61.2 HZ
Conditions: PPL EU required OF1 shall-trip setting
review note: possible conflict with c7 (same source; check the conditions); possible conflict with c9 (same source; check the conditions); possible conflict with c13 (same source; check the conditions)conflicts with: Frequency trip (c15)conflicts with: Frequency trip (c19)conflicts with: Frequency trip (c21)
c13 disputed
nominal 62 HZ
Conditions: PPL EU required OF2 shall-trip setting
review note: possible conflict with c7 (same source; check the conditions); possible conflict with c9 (same source; check the conditions); possible conflict with c11 (same source; check the conditions)conflicts with: Frequency trip (c17)conflicts with: Frequency trip (c19)conflicts with: Frequency trip (c21)
c15 disputed
nominal 62 HZ
Conditions: Generac PWRmicro OF2 frequency trip
review note: possible conflict with c17 (same source; check the conditions); possible conflict with c19 (same source; check the conditions); possible conflict with c21 (same source; check the conditions)conflicts with: Frequency trip (c7)conflicts with: Frequency trip (c9)conflicts with: Frequency trip (c11)
c17 disputed
nominal 61.2 HZ
Conditions: Generac PWRmicro OF1 frequency trip
review note: possible conflict with c15 (same source; check the conditions); possible conflict with c19 (same source; check the conditions); possible conflict with c21 (same source; check the conditions)conflicts with: Frequency trip (c7)conflicts with: Frequency trip (c9)conflicts with: Frequency trip (c13)
c19 disputed
nominal 58.5 HZ
Conditions: Generac PWRmicro UF1 frequency trip
review note: possible conflict with c15 (same source; check the conditions); possible conflict with c17 (same source; check the conditions); possible conflict with c21 (same source; check the conditions)conflicts with: Frequency trip (c9)conflicts with: Frequency trip (c11)conflicts with: Frequency trip (c13)
c21 verified · fact
nominal 56.5 HZ
Conditions: Generac PWRmicro UF2 frequency trip
verified by: review-workflowverified on: 2026-10-24review note: possible conflict with c15 (same source; check the conditions); possible conflict with c17 (same source; check the conditions); possible conflict with c19 (same source; check the conditions); review: the compiler-flagged conflict (func:frequency-trip#c7, func:frequency-trip#c11, func:frequency-trip#c13) is a scenario difference, resolved at review
c23 drafted · lead
nominal 62 HZ
Scope: regions ISO New England market area proposed
Conditions: SolarEdge ISO New England setting FgMax1
review note: possible conflict with c25 (same source; check the conditions); possible conflict with c27 (same source; check the conditions); possible conflict with c29 (same source; check the conditions)
c25 drafted · lead
nominal 61.2 HZ
Scope: regions ISO New England market area proposed
Conditions: SolarEdge ISO New England setting FgMax2
review note: possible conflict with c23 (same source; check the conditions); possible conflict with c27 (same source; check the conditions); possible conflict with c29 (same source; check the conditions)
c27 drafted · lead
nominal 58.5 HZ
Scope: regions ISO New England market area proposed
Conditions: SolarEdge ISO New England setting FgMin1
review note: possible conflict with c23 (same source; check the conditions); possible conflict with c25 (same source; check the conditions); possible conflict with c29 (same source; check the conditions)
c29 drafted · lead
nominal 56.5 HZ
Scope: regions ISO New England market area proposed
Conditions: SolarEdge ISO New England setting FgMin2
review note: possible conflict with c23 (same source; check the conditions); possible conflict with c25 (same source; check the conditions); possible conflict with c27 (same source; check the conditions)
trip_time
c8 disputed
nominal 301 SEC
Conditions: PPL EU required UF1 clearing time
review note: possible conflict with c10 (same source; check the conditions); possible conflict with c14 (same source; check the conditions)conflicts with: Frequency trip (c16)conflicts with: Frequency trip (c18)conflicts with: Frequency trip (c20)conflicts with: Frequency trip (c22)
c10 disputed
nominal 0.2 SEC
Conditions: PPL EU required UF2 clearing time
review note: possible conflict with c8 (same source; check the conditions); possible conflict with c12 (same source; check the conditions)conflicts with: Frequency trip (c16)conflicts with: Frequency trip (c18)conflicts with: Frequency trip (c20)conflicts with: Frequency trip (c22)
c12 verified · fact
nominal 301 SEC
Conditions: PPL EU required OF1 clearing time
verified by: review-workflowverified on: 2026-10-24review note: possible conflict with c10 (same source; check the conditions); possible conflict with c14 (same source; check the conditions); review: the compiler-flagged conflict (func:frequency-trip#c16, func:frequency-trip#c18, func:frequency-trip#c20, func:frequency-trip#c22) is a scenario difference, resolved at review
c14 disputed
nominal 0.2 SEC
Conditions: PPL EU required OF2 clearing time
review note: possible conflict with c8 (same source; check the conditions); possible conflict with c12 (same source; check the conditions)conflicts with: Frequency trip (c16)conflicts with: Frequency trip (c18)conflicts with: Frequency trip (c20)conflicts with: Frequency trip (c22)
c16 verified · fact
nominal 0.16 SEC
Conditions: Generac PWRmicro OF2 clearing time
verified by: review-workflowverified on: 2026-10-24review note: possible conflict with c18 (same source; check the conditions); possible conflict with c20 (same source; check the conditions); review: the compiler-flagged conflict (func:frequency-trip#c8, func:frequency-trip#c10, func:frequency-trip#c12, func:frequency-trip#c14) is a scenario difference, resolved at review
c18 verified · fact
nominal 300 SEC
Conditions: Generac PWRmicro OF1 clearing time
verified by: review-workflowverified on: 2026-10-24review note: possible conflict with c16 (same source; check the conditions); possible conflict with c22 (same source; check the conditions); review: the compiler-flagged conflict (func:frequency-trip#c8, func:frequency-trip#c10, func:frequency-trip#c12, func:frequency-trip#c14) is a scenario difference, resolved at review
c20 disputed
nominal 300 SEC
Conditions: Generac PWRmicro UF1 clearing time
review note: possible conflict with c16 (same source; check the conditions); possible conflict with c22 (same source; check the conditions)conflicts with: Frequency trip (c8)conflicts with: Frequency trip (c10)conflicts with: Frequency trip (c12)conflicts with: Frequency trip (c14)
c22 verified · fact
nominal 0.16 SEC
Conditions: Generac PWRmicro UF2 clearing time
verified by: review-workflowverified on: 2026-10-24review note: possible conflict with c18 (same source; check the conditions); possible conflict with c20 (same source; check the conditions); review: the compiler-flagged conflict (func:frequency-trip#c8, func:frequency-trip#c10, func:frequency-trip#c12, func:frequency-trip#c14) is a scenario difference, resolved at review
c24 drafted · lead
nominal 160 MilliSEC
Scope: regions ISO New England market area proposed
Conditions: SolarEdge ISO New England setting FgMax1 time
review note: possible conflict with c26 (same source; check the conditions); possible conflict with c28 (same source; check the conditions)
c26 verified · fact
nominal 300000 MilliSEC
Scope: regions ISO New England market area proposed
Conditions: SolarEdge ISO New England setting FgMax2 time
verified by: review-workflowverified on: 2026-10-24review note: possible conflict with c24 (same source; check the conditions); possible conflict with c30 (same source; check the conditions)
c28 drafted · lead
nominal 300000 MilliSEC
Scope: regions ISO New England market area proposed
Conditions: SolarEdge ISO New England setting FgMin1 time
review note: possible conflict with c24 (same source; check the conditions); possible conflict with c30 (same source; check the conditions)
c30 drafted · lead
nominal 160 MilliSEC
Scope: regions ISO New England market area proposed
Conditions: SolarEdge ISO New England setting FgMin2 time
review note: possible conflict with c26 (same source; check the conditions); possible conflict with c28 (same source; check the conditions)