- Update Firmware of Sunny Tripower CORE2 Inverter
sec=h1h=db3be204ec68 - STP110-60 Core2 Inverter Commissioning checklist
sec=h1h=cd96a02fc932
Sunny Tripower CORE2
The Sunny Tripower CORE2, also called STP110-60, is a three-phase string inverter family from SMA. The SMA Data Manager M controls and monitors it over SunSpec Modbus, using the SunSpec profile and Unit ID 1. Before commissioning, update the inverter and the Data Manager M firmware, then register the inverter. Do these steps in the stated order. To update the firmware, log in as Installer and set the country data set first. Do the update while there is enough sunlight, because AC supply alone is not sufficient. Export limitation and zero export are set up through the Data Manager with an energy meter, using closed-loop active power setpoints. At a 0% setpoint the inverter can either disconnect from the grid or regulate down to a minimum of 1-2 kW. The parameter WlimitShutdownENA selects which. A fallback value applies if communication with the Data Manager is lost. The communication board can be reset in two ways. A short button press restarts the communication processor without changing settings. A press of about 30 seconds does a factory reset, which clears passwords and network settings. The grounding conductor needs a low-impedance connection within the specified cross-section range. Poor grounding can cause transient overvoltages that damage the device, and that damage is not covered by the warranty.
<!-- review notes
- sentence 1: support check: partial - The passages show STP110-60 is the CORE2 and that it is an SMA string inverter, but they do not say it is three-phase.
- sentence 1: review: partial - The passages confirm that STP110-60 is the CORE2 and that it is an SMA string inverter, but they never say it is three-phase. -->
Claims
instance_of
uses_protocol
c2 drafted · lead SunSpec Modbus
The SMA Data Manager controls and monitors the inverter over SunSpec Modbus. Register it with the SunSpec profile and Unit ID 1.
- Registering Sunny Tripower CORE2 for support of SMA Data Manager M
sec=h1h=a17fc3cdf3cc - STP110-60 Core2 Inverter Commissioning checklist
sec=h1h=cd96a02fc932
For a direct Ethernet connection the default inverter IP is 169.254.12.3. If DHCP gives no address, the board falls back to that address or the next free local address.
- Update Firmware of Sunny Tripower CORE2 Inverter
sec=h1h=db3be204ec68 - Communication Board Reset for Sunny Tripower Core2
sec=h1h=6fa40dc62ba3
compatible_with
c4 drafted · lead SMA Data Manager M
Scope: firmware from 1.00.04.R
Conditions: Before registration, update the inverter firmware to 1.00.04.R or later and the Data Manager M firmware to 1.09.06.R or later. Follow the commissioning steps in the stated order.
- Registering Sunny Tripower CORE2 for support of SMA Data Manager M
sec=h1h=a17fc3cdf3cc - Commissioning Notes of Sunny Tripower CORE2 and SMA Data Manager M
sec=h1h=624f3b810331 - STP110-60 Core2 Inverter Commissioning checklist
sec=h1h=cd96a02fc932
c5 drafted · lead SMA Energy Meter
Conditions: For export limitation through the Data Manager. The source uses the EM-20 as its example and says other meters can also be used.
- SMA Sunny Tripower STP 110-60 (CORE2) Export Limit and Control
sec=h1h=370ce31aa472
requires
c6 drafted · lead SMA Data Manager M
Conditions: Export limitation and control need an SMA Data Manager (EDMM-10) acting as master.
- SMA Sunny Tripower STP 110-60 (CORE2) Export Limit and Control
sec=h1h=370ce31aa472
review note: support check: partial - The passages say a Data Manager (EDMM-10) is needed for export limitation and control, but they do not say the CORE2 requires it in general; the Data Manager is described as optional.
c13 drafted · lead Installer access level
Conditions: Firmware updates are done after logging in to the inverter user interface as Installer. The country data set must be configured as part of the procedure.
- Update Firmware of Sunny Tripower CORE2 Inverter
sec=h1h=db3be204ec68
review note: support check: partial - The passages show that the firmware update procedure uses an Installer login and a mandatory country data set, but they do not say the CORE2 generally requires installer access.
implements
c7 drafted · lead Export limitation
Conditions: Configured in the Data Manager. Use closed-loop control, and set the active power setpoint as a percentage of total system power.
- SMA Sunny Tripower STP 110-60 (CORE2) Export Limit and Control
sec=h1h=370ce31aa472
c8 drafted · lead Active power setpoint proposed
- SMA Sunny Tripower STP 110-60 (CORE2) Export Limit and Control
sec=h1h=370ce31aa472 - Zero feed-in Power with Sunny Tripower STP110-60 (CORE2)
sec=h1h=5a8fe0a4eb3f
c9 drafted · lead Zero export
Scope: firmware from 1.01.03.R
Conditions: With the parameter WlimitShutdownENA set to On, a 0% setpoint disconnects the inverter from the grid. With it set to Off, the inverter regulates down to a minimum of 1-2 kW. Requires firmware 1.01.03.R or later.
- SMA Sunny Tripower STP 110-60 (CORE2) Export Limit and Control
sec=h1h=370ce31aa472 - Zero feed-in Power with Sunny Tripower STP110-60 (CORE2)
sec=h1h=5a8fe0a4eb3f
c10 drafted · lead Communication-loss fallback
Conditions: Sets a waiting time (minimum 20 seconds) and a fallback value for when communication with the Data Manager fails. In fallback, the inverter cannot be set to disconnect from the grid.
- Zero feed-in Power with Sunny Tripower STP110-60 (CORE2)
sec=h1h=5a8fe0a4eb3f
c11 drafted · lead Ramp rate control
Conditions: With firmware 1.00.08.R or earlier, set the active power gradient at the inverter web interface. Set it right after the grid code is first set, so it is not overwritten.
- SMA Sunny Tripower STP 110-60 (CORE2) Export Limit and Control
sec=h1h=370ce31aa472 - Active Power Gradient / Ramp Rate at STP 110-60 Web Interface
sec=h1h=c9124120d168
c12 drafted · lead Global MPP scan
SMA ShadeFix. Since March 2023 it can be scheduled with the parameter MPPSHdwTime in the group Extended Model 2-1 RW.
- Can I set the time interval for SMA ShadeFix in the Core2?
sec=h1h=7f5b5bf6b179
Referenced by
- SMA Data Manager M
compatible_withc10