Function
Communication-loss fallback
- ID
func:communication-loss-fallback
- IRI
https://solarlattice.org/kb/func/communication-loss-fallback
- Status
- active
- Also known as
- fallback mode, reversion, heartbeat timeout, setpoint timeout, Fallback, Fallback Behavior, fallback plan, system fallback
- Category
- Control
- Function kind
- control
Communication-loss fallback puts inverters into a defined feed-in state when control communication fails or setpoints stop arriving. After an adjustable timeout, the inverter either keeps the last values it received or applies preset fallback values. The SMA Cluster Controller supports two fallback types, and each is configured separately. One covers a missing or invalid external setpoint. The other covers failure of Speedwire communication between the controller and the inverters. The Speedwire fallback cannot be configured on inverters with a Speedwire Webconnect Piggy-Back. It is designed for inverters with the Speedwire/Webconnect data module and for Sunny Boy Smart Energy. Inverters controlled by the SMA Inverter Manager switch to their fallback state when communication is interrupted, and they report status events 2055 and 2056. Fallback is set up through the grid code file or the LCS-Tool. The system-level fallback toward a SCADA or power plant controller needs the LCS-Tool and a Grid Guard code. On the Sunny Tripower CORE2 you set a waiting time of at least 20 seconds and a fallback value. A fallback value of 0 percent still lets about 1 to 2 kW feed in, and fallback cannot be set to disconnect from the grid. SMA states that the activation and configuration of fallback must be agreed with the grid operator.
Claims
requires
c1 drafted · lead
Grid Guard code holder
An SMA Grid Guard code is needed to change fallback settings on the Cluster Controller and the superordinate fallback on the Inverter Manager.
c2 drafted · lead
SMA LCS-Tool
Scope: products SMA Inverter Manager
The superordinate system fallback between the SMA Inverter Manager and a higher-level controller can only be configured with the LCS-Tool.
c3 drafted · lead
Installer access level
Scope: products SMA Inverter Manager
The Inverter Manager system fallback is set under the Installer user group.
- 278879
sec=5.2.6 h=9f7e6e82c227
c5 verified · fact
FIMER Installer app
The FIMER export limitation fallback plan is enabled and configured in the Installer for solar inverters app.
verified by: review-workflowverified on: 2026-10-24
part_of
c4 drafted · lead
Export limitation
In FIMER inverters the fallback plan belongs to the export limitation control and is triggered when communication with the export meter is lost.
setting_range
c6 drafted · lead
≥ 20 SEC
Scope: products Sunny Tripower CORE2
Conditions: Waiting time before fallback takes effect when communication between SMA Data Manager and Sunny Tripower CORE2 fails; at least 20 s must be set
Referenced by
Data