Solar Lattice

Product

CSI-125K-T600GL02-U

ID
prod:canadian-solar-125k-t600gl02
IRI
https://solarlattice.org/kb/prod/canadian-solar-125k-t600gl02
Status
active
Also known as
CSI-125-T600GL02-U
Category
Inverters
Make
canadian-solar
Product level
family

The CSI-125K-T600GL02-U is a Canadian Solar three-phase transformerless, grid-support, utility-interactive PV inverter that converts array DC power to AC for local loads and the grid. It delivers up to 125000 VA of apparent power on a 600 V three-phase grid at 60 Hz, with a maximum output current of 120 A. Maximum efficiency is 99.1% and EU efficiency is 98.6%, and the unit operates in ambient temperatures from -25 to 60 °C. For communication it has RS485 and Ethernet, with power line communication available as an option. The standard warranty is 10 years and can be extended to 20 years. An OV-BUS alarm means the inverter has detected high DC voltage on its internal bus. Possible causes are internal damage or a wire that came loose during shipping. Measure the DC and AC voltages and compare them with the LCD. If the readings confirm the fault, replace the inverter.

<!-- review notes

Claims

manufactured_by

c1 drafted · lead Canadian Solar

review note: support check: partial - Passage says Canadian Solar inverter manual covers CSI-125-T600GL02-U; the exact model name differs slightly (no K) but manufacturer is stated.

instance_of

c2 drafted · lead Inverter

Three-phase transformerless grid-support utility-interactive PV inverter

rated_power

c3 drafted · lead nominal 125000 V-A

Conditions: Maximum apparent output power

max_input_voltage

c4 verified · fact ≤ 1500 V

Conditions: Maximum DC input voltage

verified by: review-workflowverified on: 2026-10-24

rated_output_current

c5 drafted · lead ≤ 120 A

Conditions: Maximum AC output current at 600 V

nominal_voltage

c6 drafted · lead nominal 600 V

Conditions: Rated three-phase grid voltage (3/PE)

frequency

c7 drafted · lead nominal 60 HZ

Conditions: Rated grid frequency

c8 verified · fact 59.5–60.5 HZ

Conditions: Grid frequency range

verified by: review-workflowverified on: 2026-10-24

efficiency

c9 drafted · lead nominal 99.1 PERCENT

Conditions: Maximum (peak) efficiency

review note: possible conflict with c10 (same source; check the conditions)

c10 drafted · lead nominal 98.6 PERCENT

Conditions: EU weighted efficiency

review note: possible conflict with c9 (same source; check the conditions)

operating_temperature

c11 drafted · lead -25–60 DEG_C

Conditions: Operating ambient temperature range

warranty_term

c12 drafted · lead nominal 10 YR

Conditions: Standard warranty

c13 drafted · lead ≤ 20 YR

Conditions: Extended warranty option

uses_protocol

c14 drafted · lead RS-485

c15 drafted · lead Ethernet

c16 drafted · lead Power line communication

Optional

certified_to

c17 drafted · lead UL 1741 proposed

c18 drafted · lead UL 1741 SA proposed

c19 drafted · lead CA Rule 21 proposed

Including Rule 21 Phase II and III

c20 drafted · lead UL 1998 proposed

c21 drafted · lead IEEE 1547 proposed

Edition not stated

c22 drafted · lead FCC Part 15 proposed

Class A and B

c23 drafted · lead CSA C22.2 No. 107.1 proposed

107.1-16

Referenced by

Data