Concept
Reactive power sign convention
- ID
concept:reactive-power-sign-convention
- IRI
https://solarlattice.org/kb/concept/reactive-power-sign-convention
- Status
- active
- Also known as
- generator reference-arrow system, consumer reference system, injecting vs absorbing, power sign convention, generator sign convention, consumer reference-arrow system, load sign convention, IEEE VAR sign convention, meter sign convention
- Category
- Grid
- Concept kind
- electrical
The reactive power sign convention sets which direction of power flow counts as positive. Two systems are common: the generator reference-arrow system and the consumer (load) reference system. In the generator convention, power flowing from the plant into the grid is positive. Active power output is positive and active power drawn from the grid is negative. Positive reactive power means over-excited operation, where current lags voltage and the device injects vars, which tends to raise voltage. Negative reactive power means under-excited operation, where current leads voltage and the device absorbs vars, which tends to lower voltage. In the consumer reference system, current absorbed from the grid is positive, so exported power appears as negative. To convert values from one system to the other, invert the signs of both active and reactive power. On the P-Q capability diagram this mirrors the plot through the origin. IEC, IEEE and IEEE 1547-2018 use the generator convention. The VDE application guide uses the consumer convention. Meters and plant controllers may use their own conventions. Some let you configure the power sign, and power factor sign modes vary, so check the documentation before you enter reactive power or power factor setpoints.
<!-- review notes
- sentence 7: support check: partial - Passages show configurable power sign, varying PF sign modes and meter-specific conventions, but none explicitly advise checking documentation before entering setpoints.
-->
Claims
explains
c1 drafted · lead
Reactive power
Defines whether positive reactive power means over-excited injection (raising voltage) or under-excited absorption (lowering voltage).
related_to
c2 drafted · lead
Active power
In the generator convention, active power output is positive and active power drawn from the grid is negative.
c3 drafted · lead
P-Q capability diagram
To convert between the consumer and generator conventions, invert the signs of P and Q. On the P/Q diagram this mirrors the plot through the origin.
c4 verified · fact
Power factor
Meters and controllers sign power factor in different ways, for example by following real power, by following reactive power, or by quadrant.
verified by: review-workflowverified on: 2026-10-24
c5 verified · fact
IEEE 1547-2018 proposed
This standard states its requirements in generator sign convention, which is the opposite of load sign convention.
verified by: review-workflowverified on: 2026-10-24
c6 drafted · lead
IEC
The units say IEC uses the generator reference-arrow system internationally.
c7 drafted · lead
IEEE
The units say IEEE uses the generator reference-arrow system internationally.
c8 verified · fact
VDE
The VDE application guide uses the consumer reference-arrow system.
verified by: review-workflowverified on: 2026-10-24
c9 drafted · lead
SEL-735 Power Quality and Revenue Meter proposed
This meter reports VARs in four quadrants, following the IEEE VAR sign convention.
c10 drafted · lead
Tesla Site Controller proposed
This controller assumes a defined meter sign convention when it measures and sets control points.